Bay control REC650
Product version: 1.1
output changes, the Event bit in the state
part is toggled. The function also
propagates timestamp and quality of input
signals.
• INDEXTSPQT extracts individual signals
from a group signal input. Value part of
single position input is copied to SI_OUT
output. Time part of single position input is
copied to TIME output. State bits in
common part and indication part of inputs
signal is copied to the corresponding state
output. The function also propagates
timestamp and quality of input signal.
Boolean 16 to Integer conversion
B16I
Boolean 16 to integer conversion function
(B16I) is used to transform a set of 16 binary
(logical) signals into an integer.
Boolean 16 to Integer conversion
with logic node representation
B16IFCVI
Boolean 16 to integer conversion with logic
node representation function (B16IFCVI) is
used to transform a set of 16 binary (logical)
signals into an integer.
Integer to Boolean 16 conversion
IB16A
Integer to boolean 16 conversion function
(IB16A) is used to transform an integer into a
set of 16 binary (logical) signals.
Integer to Boolean 16 conversion
with logic node representation
IB16FCVB
Integer to boolean conversion with logic
node representation function (IB16FCVB) is
used to transform an integer to 16 binary
(logic) signals.
IB16FCVB function can receive remote values
over IEC61850 depending on the operator
position input (PSTO).
26
1MRK 511 249-BEN -
Issued: February 2011

10. Monitoring

Measurements CVMMXN, CMMXU,
VNMMXU, VMMXU, CMSQI, VMSQI
The measurement functions are used to get on-
line information from the IED. These service
values make it possible to display on-line
information on the local HMI and on the
Substation automation system about:
• measured voltages, currents, frequency,
active, reactive and apparent power and
power factor
• primary and secondary phasors
• current sequence components
• voltage sequence components
Event counter CNTGGIO
Event counter (CNTGGIO) has six counters
which are used for storing the number of
times each counter input has been activated.
Disturbance report DRPRDRE
Complete and reliable information about
disturbances in the primary and/or in the
secondary system together with continuous
event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRPRDRE, always
included in the IED, acquires sampled data of
all selected analog input and binary signals
connected to the function block that is,
maximum 40 analog and 96 binary signals.
The Disturbance report functionality is a
common name for several functions:
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
The Disturbance report function is
characterized by great flexibility regarding
configuration, starting conditions, recording
times, and large storage capacity.
A disturbance is defined as an activation of
an input to the AxRADR or BxRBDR function
ABB