General Information; Specific Features; How To Read The Model Name - Mitsubishi Heavy Industries SRK20HD-S Technical Manual

Wall mounted type room air-conditioner
Table of Contents

Advertisement

1

GENERAL INFORMATION

1.1 Specific features

The "Mitsubishi Daiya" room air-conditioner: SRK series are of split and wall mounted type and the unit consists of indoor unit and
outdoor unit with refrigerant precharged in factory. The indoor unit is composed of room air cooling or heating equipment with opera-
tion control switch and the outdoor unit is composed of condensing unit with compressor.
(1) Remote control flap
The flap can be automatically controlled by operating wireless remote controller.
¡ Air scroll: Flap operation is automatically control.
¡ Swing: This will swing the flap up and down.
¡ Memory flap: Once the flap position is set, the unit memorizes the position and continues to operate at the same position from
the next time.
(2) Automatic Operation
When the remote control switch is set on "auto ( ) ", it will either automatically decide operation mode such as cooling, heating
and thermal dry, or operate in the operation mode before it has been turned to automatic control.
(3) Self diagnosis function
¡ We are constantly trying to do better service to our customers by installing such judges that show abnormality of operation as
follows.
RUN lamp
1 time flash
TIMER lamp
2 time flash
ON
6 time flash

1.2 How to read the model name

Example :
Heat exchanger thermistor error
Room temperature thermistor error
Indoor fan motor error
SR K 40 H D - S
TIMER lamp
1 time flash
RUN lamp
2 time flash
keeps flashing
4 time flash
1 time flash
2 time flash
RUN lamp
ON
5 time flash
6 time flash
R410A models
Series No.
H: Heat pump type
C: Cooling only type
Product capacity
Wall mounted type
Split type room air-conditioner
1
-
-
Outdoor (LED)
Outdoor temperature thermistor
OFF
error
Outdoor unit heat exchanger
OFF
thermistor error
OFF
Discharge pipe thermistor error
1 time flash
Current cut
2 time flash
Outdoor unit error
5 time flash
Compressor overheat
6 time flash
Serial signal transmission error