CAUTION
Do not touch the heat exchanger fins. These fins are sharp
and could result in cutting injuries.
NOTICE
When cleaning the heat exchanger, make sure to remove
the switch box and fan motor. Water or detergent might
deteriorate the insulation of electronic components and
result in burnout of these components.
WARNING
Be carefull with ladders when working in high places.
6.2
Cleaning the air filter, suction
grille, air outlet and outside panels
6.2.1

To clean the air outlet and outside panels

WARNING
Do
NOT
let
the
indoor
consequence: Electric shock or fire.
NOTICE
▪ Do NOT use gasoline, benzene, thinner polishing
powder or liquid insecticide. Possible consequence:
Discoloration and deformation.
▪ Do NOT use water or air of 50°C or higher. Possible
consequence: Discoloration and deformation.
▪ Do NOT scrub firmly when washing the blade with
water. Possible consequence: The surface sealing
peels off.
Clean with a soft cloth. If it is difficult to remove stains, use water or
neutral detergent.
6.2.2

To clean the air filter

When to clean the air filter:
▪ Rule of thumb: Clean every 6  months. If the air in the room is
extremely contaminated, increase the cleaning frequency.
▪ Depending on the settings, the remote controller can display the
TIME TO CLEAN AIR FILTER notification. Clean the air filter
when the notification is displayed.
▪ If the dirt becomes impossible to clean, change the air filter
(= optional equipment).
How to clean the air filter:
1 Remove the air filters by pulling their cloth upward (in case of
rear suction) or backward (in case of bottom suction).
rear suction
2 Clean the air filter. Use a vacuum cleaner or wash with water. If
the air filter is very dirty, use a soft brush and neutral detergent.
ADEQ35~125C2VEB
Split system air conditioners
4P461580-1 – 2016.09
unit
get
wet.
Possible
bottom suction
6 Maintenance and service
3 Dry the air filter in the shadow.
4 Reattach the air filter. Align the 2 hanger brackets and push the
2 clips in their place and pull the cloth if necessary.
rear suction
5 Confirm that 4 hangers are fixed.
6 In case of bottom suction, shut the air inlet grille.
7 Turn ON the power.
8 Press the FILTER SIGN RESET button.
Result: The TIME TO CLEAN AIR FILTER notification
disappears from the remote controller.
6.3
Maintenance before a long stop
period
E.g., at the end of the season.
▪ Let the indoor units run in fan only operation for about half a day in
order to dry the interior of the units.
▪ Turn off the power. The remote controller display disappears.
When the main power is turned on, some wattage is being
consumed even if the air conditioner is not operating.
▪ Clean air filters and casings of indoor units. Contact your installer
or maintenance person to clean air filters and casings of the
indoor unit. Maintenance tips and procedures for cleaning are
provided in the installation/operation manuals of dedicated indoor
units. Make sure to install cleaned air filters back in the same
position.
6.4
Maintenance after a long stop
period
E.g., at the beginning of the season.
▪ Check and remove everything that might be blocking inlet and
outlet vents of indoor units and outdoor units.
▪ Check if the earth is connected properly.
▪ Check if there is somewhere a broken wire. Contact your dealer in
case of problems.
▪ Clean air filters and casings of indoor units. Contact your installer
or maintenance person to clean air filters and casings of the
indoor unit. Maintenance tips and procedures for cleaning are
provided in the installation/operation manuals of dedicated indoor
units. Make sure to install cleaned air filters back in the same
position.
▪ Turn on the power at least 6 hours before operating the unit in
order to ensure smoother operation. As soon as the power is
turned on, the remote controller display appears.
bottom suction
Operation manual