Vacon Nxi_Xxxx 6 – Supply Voltage 640-1100 Vdc, Motor Voltage 525—690 Vac - Vacon NXI User Manual

Fi9-fi14
Table of Contents

Advertisement

18 • vacon
4.2.2
Vacon NXI_xxxx 6 – Supply voltage 640-1100 Vdc, Motor voltage 525—690 Vac
High overload = Max current I
Low overload = Max current I
All frames are available as IP21 and IP54.
Motor voltage 525-690 Vac, 50/60 Hz, 3~
Inverter type
Rated
continuou
s current
I
(A)
L
NXI_0125 6
125
N×I_0144 6
144
N×I_0170 6
170
NXI_0208 6
208
NXI_0261 6
261
NXI_0325 6
325
NXI_0385 6
385
NXI_0416 6
416
NXI_0460 6
460
NXI_0502 6
502
NXI_0590 6
590
NXI_0650 6
650
NXI_0750 6
750
NXI_0820 6
820
NXI_0920 6
920
NXI_1030 6
1030
NXI_1180 6
1180
NXI_1500 6
1500
NXI_1900 6
1900
NXI_2250 6
2250
Table 4-2. Power ratings and dimensions of Vacon NXI, supply voltage 640—1100Vdc
Note: The rated currents in given ambient temperatures are achieved only when the switching
frequency is equal to or less than the factory default.
4
Following continuous operation at rated output current, 150 % rated
output current (I
than rated current, and of such duration that the r.m.s output current,
over the duty cycle, does not exceed rated output current (I
Following continuous operation at rated output current, 110% rated
output current (I
than rated current, and of such duration that the r.m.s output current,
over the duty cycle, does not exceed rated output current (I
Loadability
@ 40 °C ambient temperature
Low
High
10%
Rated
50%
overload
continuous
overload
current
current
current
(A)
I
(A)
(A)
H
138
100
150
158
125
188
187
144
216
229
170
255
287
208
312
358
261
392
424
325
488
458
325
488
506
385
578
552
460
690
649
502
753
715
590
885
825
650
975
902
650
975
1012
820
1230
1133
920
1380
1298
1030
1464
1650
1300
1950
2090
1500
2250
2475
1900
2782
2 sec/20 sec, 150% overloadability; 1 min/10 min
S;
) for 1 min, followed by a period of load current less
H
, 2 sec/20 sec, 110% overloadability; 1 min/10 min
S
) for 1 min, followed by a period of load current less
L
Motor shaft
power
930Vdc
supply
50%
Max
10%
overload
current
overload
40°C
I
40°C P(kW)
P(kW)
S
200
110
90
213
132
110
245
160
132
289
200
160
375
250
200
470
315
250
585
355
315
585
400
355
693
450
400
828
500
450
904
560
500
1062
630
560
1170
710
630
1170
800
710
1476
900
800
1656
1000
900
1755
1200
1000
2340
1500
1300
2700
1800
1500
3335
2000
1800
Tel: +358-201-2121 • Fax: +358-201-212 205
technical data
)
H
)
L
Dimensions and weight
Frame
W×H×D/kg
FI9
239 × 1030 × 372/65
FI9
239 × 1030 × 372/65
FI9
239 × 1030 × 372/65
FI9
239 × 1030 × 372/65
FI10
239 × 1030 × 552/100
FI10
239 × 1030 × 552/100
FI10
239 × 1030 × 552/100
FI10
239 × 1030 × 552/100
FI12
2×239 × 1030 × 552/200
FI12
2×239 × 1030 × 552/200
FI12
2×239 × 1030 × 552/200
FI12
2×239 × 1030 × 552/200
FI12
2×239 × 1030 × 552/200
FI12
2×239 × 1030 × 552/200
FI13
708 × 1030 × 553/302
FI13
708 × 1030 × 553/302
FI13
708 × 1030 × 553/302
FI14
2×708 × 1030 × 553/302
FI14
2×708 × 1030 × 553/302
FI14
2×708 × 1030 × 553/302

Hide quick links: