Summary of Contents for Water Analytics AquaMetrix 2300

  • Page 1 AquaMetrix 2300 Multi-Input Controller Installation and Operation Manual Page 0...
  • Page 2 Table of Contents Page 1...
  • Page 3 Page 2...
  • Page 4 Page 3...
  • Page 5: Specifications

    1. Overview 1.1. Introduction The AquaMetrix 2300 Controller is the first multi-input controller that brings web-based operation down to a price that can be afforded by just about any facility. Its combination of features remote control, data logging, email alerts and seven inputs are unparalleled in the water monitoring market.
  • Page 6: Installation

    Control Web or LAN Viewing with a browser on a computer, tablet, or smart phone. Setup and control from any of these. Multi-user password protected. Front Panel Status, Probe enable/disable/calibrate, System Configuration Ratings Power Input 0.2 A @ 115 VAC or 15 W Power to probes Maximum supplied to probes is 150 mA Temperature 0 to 70°C...
  • Page 7 Figure 2-1 - 2.2. Power, Probe, and Network Cabling A picture of the rear of the 2300 is shown below in Figure 2-2. We recommend removing the Molex connectors and connecting wires to them and then attaching the connectors to the unit. Connect the: Power cord CAT-5 Ethernet cable...
  • Page 8 Figure 2-3 shows the wiring for the three most common analog sensors plus a current sinking flow meter. Please important for 3-wire probes, which differ in the power connection of the 4-20 mA wiring. Figure 2-3 - Probe wiring diagrams. There are other possible three-wire probe setups, so please refer to your specific probe instructions for proper hook up.
  • Page 9: Relay Wiring

    2.3. Relay Wiring The 2300 controller has 4 relays that can be expanded to 10 with the addition of a second card. The relays are capable of handling 120 V @ 10 A or 240 V @ 5 A. They can also be part of a 24 VDC circuit. Unlike the Shark-120 the relays are not powered.
  • Page 10: Front Panel Display

    Once the controller is connected a Local Area Network (LAN) the router will assign the 2300 its IP address. To find out what that IP is: Menu 1. Click on the button. View System Info 2. Click on the top-most menu item, 3.
  • Page 11 Figure 3-1 - The Run display on the left reports 4 process values at a time. If there are more than 4 pressing reveals Ð the hidden values. The identical image appears on the web browser. The Detail screen on the right shows the detailed status of the Tank pH condition, including process value and alarm or relay.
  • Page 12 It is not meant to replace simply meant to allow you to connect probes and verify that they produce signals. the web-based set-up. Analog 1 corresponds to the analog 1 input on the back of the unit. The first 4 software channels are shown on quad screen.
  • Page 13: Front Panel Menu

    The Detail screen lists alarm and relay set points, last calibration date, and will flash when the channel is in alarm mode. The configure screen allows resetting of the alarm and relay set points, alarm acknowledgement, and zeroing of the totalizer and dispenser functions and other channel-specific functions. 3.3.
  • Page 14 Figure 3-4 -Pressing the Menu button brings up the Main Menu screen. Enter Use the keys to highlight an item, and press the key to select it. If there are more than 4 choices Ï Ð available, the bottom (or top) corner on the right will show a white triangle or notch. Some front panel actions 48111 require a password to proceed.
  • Page 15 3.4. Calibrating Sensors from the Front Panel Most routine operation of the 2300 is most conveniently done through the web interface. However, for some installations especially industrial ones calibration may be more conveniently done through the front panel. Note that front panel calibration only allows 2-point calibrations. To calibrate from the front panel follow these instructions: Menu 1.
  • Page 16 Figure 3-6 - On the left is the numeric keypad for the manual entry of calibration numbers and the K-Factor. 3.5. Setting Relays from the Front Panel Another operation that may be performed at the front panel is configuring relay set points. Except in the rare case in which there is no access to a local area network, you will have already set up the relay trigger points in the Probe Configuration Wizard.
  • Page 17 Figure 3-7 The sequence of screens for changing relay set points from the front panel. 3.6. Saving and Restoring Your Configuration from the Front Panel Once you have configured the 2300 with probe definitions, relay/alarm set pings and email and server set ups, you can save these settings to the external microSD card via the front panel menu.
  • Page 18: Menu Button

    6. The next screen will display a message that the save was successful. If there is no microSD card you will get the message, Backup Failed. The Restore utility only works with units having the same firmware build. Upgrades to firmware will not change the configuration inside the 2300, so we suggest saving the configuration to a memory card after a firmware upgrade.
  • Page 19 Figure 4-1 - Sequence of menus for toggling between DHCP and Fixed determination of IP address. The main reason for assigning a fixed IP address to a 2300 is to configure it on a wide area network. However, even with DHCP, most routers very infrequently change IP addresses of devices. To configure the 2300 with a fixed IP address first set the unit up for that mode.
  • Page 20 Figure 4-2 - Assigning a fixed (static) IP address, With the port number configured you can log into the 2300 from anywhere in the world by entering the External IP Address:Port Number (e.g. 24.148.220.199:5000). If your router supports a Demilitarized Zone ( ) then you can forgo the use of a port number.
  • Page 21: Select Manual

    Figure 4-3 - Ethernet configuration with a fixed IP address on a Macintosh Manual IPv4 1. Select configuration and IP address Subnet Mask Default Gateway 2. Choose an a. For illustration purposes we will start with the static IP address that will be close to that of the 2300 192.168.7.7.
  • Page 22 Properties 6. In the contextual menu that appears when you right click on Ethernet choose . The Ethernet Properties window will pop up as shown in Figure 4-4. Figure 4-4 - Ethernet Properties window. Choose the IPv4 row. Internet Protocol Version 4 (TCP/IPv4) 7.
  • Page 23 The IP address and the gateway ID numbers are equal because the computer is the gateway. Fixed Menu > Advanced > Network Setup > 1. As outlined in Section 4.2.1, set the 2300 Network to Fixed 1. There are three fields in which to enter numbers. For illustration purposes we use the following set of numbers: The right-most digit of the IP address can be any digit other than 1, which is the digit for the Gateway.
  • Page 24 Enter Select Network 6. If you see this screen then simply press . You will then see a screen with the title Type Try DHCP Again . Enter 7. On your smart device WIFI connected to the Tenda network, open a browser and type in the IP address. admin aquametrix 5.
  • Page 25: Probe Status

    System Config Miscellaneous configuration options System Documentation System doc file Advanced Miscellaneous Logout Logs the current user out of the system after a confirmation 5.1. Probe Status The Probe Status button does not bring up a menu of options. It displays all enabled probes, their names, values, alarm and relay set points, and graphs showing the history of values for the previous 15 minutes.
  • Page 26: Remote Display

    Figure 5-2 Clicking anywhere within a graph of the Probe Status menu brings up the time history. Config Clicking on the button in any quadrant brings up a window with options for setting the limits of the y- axis to optimize the scaling. One can also acknowledge an alarm that has been triggered. 5.2.
  • Page 27: Probe Configuration

    JavaScript errors. Web Server Access Logs store each request sent from a web browser to the AquaMetrix 2300 Controller. It is not enabled by default but can be activated from the web server Setup / Network / Web Server setup page. It is only necessary when trying to diagnose web access issues.
  • Page 28 Figure 5-4 - Probe Configuration page There are 8 software channels for a maximum of 8 probes. These 8 inputs include 4 analog inputs, 3 pulse inputs and any combination of two probes whose outputs combine to create a function. Click her to add new probe or more pages setup that includes Submit...
  • Page 29: User Maintenance

    PIN may be added at this point for front panel (LCD) access. User access to the 2300 is logged, allowing traceability of changes made to the controller by username and by time. There are three different access levels provided by the AquaMetrix 2300: Administrator Can view all reports, add, change or delete Sensors, change system settings, and add or delete Users.
  • Page 30 User Can view all reports and logs but cannot change any configuration or Acknowledge Alarms or Zero counters admin By default, there is one user in the system, named , who has the Administrator access level. During first- time startup, the administrator is asked for a new default password for this user. At any time, an Administrator may add additional users to the system and assign any of the above access levels.
  • Page 31: Network Setup

    Email Delivery . Email delivery can be set to periodically email the data log file every day at midnight, or more often. Page 3 is the summary page and is shown in Figure 5-7. This page allows you to change any of the five options. Figure 5-7 - Summary of Data Logging parameters Keep in mind: 1.
  • Page 32 Modbus communication occurs through the Ethernet cable using TCP. This window allows you to choose the port number, enable access over Modbus/TCP of the error and access logs, and whether you wish to restrict communication to read-only. Sending Email alerts is an invaluable feature of the 2300. There are two steps to setting up Email alerts: 1.
  • Page 33 Figure 5-8 - The Basic Information page of the SMTP Connection Wizard configures the Email server. 5. The next screen asks for the username and password. For the complimentary Email account enter the text: aquametrix2300 SMTP Authentication Login Name: water1000 SMTP Authentication Password: 6.
  • Page 34 Figure 5-9 - Email configuration Wizard screen showing successful test of the Email server. 5.6.4.2. Note for Gmail Users Google views email originating from a device like the 2300 as suspicious activity and is likely to block it. In order to prevent that from happenings you must lower the security level of Gmail.
  • Page 35 Connection time out If the e-mail server values are wrong you will get a message. Upon successful completion a summary screen will appear, as in Figure 5-10. Figure 5-10 Email server configuration Wizard Screen. The SMTP Authentication Password is water1000. 5.6.4.3.Send Test Email The Test Email function allows you to assure yourself that you will receive an Email alert.
  • Page 36 Figure 5-11 - The Email Message Setup allows you to set up as many email messages as you wish. Most wireless phone carriers have email addresses, which allow the content of emails to be sent to a phone as a text message.
  • Page 37: System Configuration

    Figure 5-12 The Email TO Addresses menu allows you to enter as many user e-mail addresses as you wish. 5.7. System Configuration This page allows you to customize the name of the 2300, identifying the unit by location or function. Time zone, date, and time are also set here.
  • Page 38: System Documentation

    5.8. System Documentation This section is reserved as a repository for documentation such as manuals. Files are loaded with the firmware upgrade. Expect future upgrades to include a manual and quick-start guide. 5.9. Advanced This is a non-editable list of Modbus addresses. This is the most useful of the advanced menus as it reveals who is logged into the 2300.
  • Page 39 Flow Dispenser Probe This totalizer probe takes input flow data from any pulse output to dispense fluid into a container. It starts the totalizer based on a preset value of an analog probe. Manual Dispenser Probe This dispenser probe differs from the flow dispenser probe in that it starts totalizing when a contact switch is closed.
  • Page 40 Figure 6-2 The first window of the Probe Configuration Wizard contains the probe type and input. The input drop-down menu appears after you choose the probe type. When you do so the same window adds a second drop-down menu to choose the input based on the analog Select Input probe.
  • Page 41 calibrates scales Strictly speaking, one a sensor that outputs a direct 4-20 mA signal but a transmitter that is connected to a probe, the latter of which has already been calibrated. In the case of a direct output probe, e.g. a pH sensor, the calibration requires the use of calibration standards in the case of pH probes standard buffers.
  • Page 42 If the analog signal is from a transmitter instead of a probe then this operation is a true scaling exercise. The procedure is similar to that of a true calibration. The difference is that the probe is connected to a transmitter 1.
  • Page 43 Figure 6-6 - Non-linear scaling window. One must enter the calibration points manually into the bottom text box. This example shows a true non- 3. Alternatively you may move your mouse cursor over the point in the where your calibration point ought to be and click on that point.
  • Page 44 Figure 6-7 - Probe Detail window. The Probe Description screen serves as a notepad where you can enter any descriptive text you wish about the sensor and its environment. Information such as the make and model of the probe, the process and the location of the probe can all be entered here.
  • Page 45: Control Options

    Each probe can be configured to provide multiple alarms, relay activations, and email notifications. The 2300 is designed to allow full flexibility of assigning any or all of these outputs to any or all of the probes, including virtual probes. You are limited only by the number of hardwired relays on your controller, four of which are standard but more of which may be added using an optional card.
  • Page 46 High Control Relay Rising process Trip pt > Reset pt Low Alarm Alarm Falling process Trip pt < Reset pt High Alarm Alarm Rising process Trip pt > Reset point In Range Alarm Alarm Within range Low trip pt < Low reset pt High trip pt >...
  • Page 47 2. The External ACK Control dropdown menu allows the user to acknowledge an alarm through a switch. The earlier AquaMetrix 2300 (Firmware version 1.7.2 or earlier) allows the user to close a switch wired to either one 4 contact inputs. This is shown on the left side of Figure 6-11.
  • Page 48: Connecting A Pulse Output (Flow) Sensor

    Subject screen, titled Email Send Configuration. There is a drop down menu for that contains messages already configured in the Email setup (Section 5.6.4.4). You can create a new subject and message and that choice will be Email List Configuration added to the library of email subjects in the (Network Setup >...
  • Page 49 pulse sensors (Dig in 1 and Dig in 2) before connecting a flow sensor to the single pulse input probe connector Select Input (Dig in 3). Clicking on the button brings up a picture of the back of the 2300 with a red rectangle surrounding the unused pulse probe (Dig in) connectors.
  • Page 50 Figure 6-16 - The K-factor is supplies by the manufacturer and is specific for the volume and time units. Those units must be entered in this screen so that the 2300 calculates flow in the correct units. Figure 6-16 shows the screen in which one enters the factory-supplied K-factor. In order for the 2300 to calculate flow in the correct units you must also enter the units of volume and time.
  • Page 51 Figure 6-18 - The Probe Description in this case lists the model and the location of the flow sensor. The setup of alarms and relays is identical to the instructions in Section 6.2.10. 6.4. Connecting Virtual Probes One of the common type of virtual sensor is the totalizer, which integrates the flow over time to calculate a total volume.
  • Page 52 units, denoted by firmware version 1.7.2 or earlier, use a contact connector as shown on the left side of Figure 6-11. Config 5. To reset the totalizer from the web interface, click on the button to top right of the graph and Zero {Totalizer name} then click on button below description window...
  • Page 53 total is reached if the Totalizer is set up with a K-factor or linear scaling. Use of the non-linear scaling feature Periodic Counter Alarm allows for more complex functions of this Figure 6-22 - Action Configuration for a totalizer probe attached to a flow probe. Differential Sensor combines two existing analog or digital probes and performs a subtraction operation between them, displaying the resulting differential value as a separate, virtual, probe.
  • Page 54: Probe Information

    Dispenser Probe options allow the 2300 Controller to function as one to four complete batch controllers. They are specialized flow totalizers that are used to fill containers in an automated batch filling operation. There are two types of Dispenser Probes selectable in the 2300 Controller. Both are used to action a flow in order Manual Start Dispenser, to dispense a fixed volume of fluid.
  • Page 55 Figure 6-25 Dispenser Control page for both Dispenser probes. Enter the value of the volume at which the dispenser is Dispenser Off at Value turned off in the field and the blackout period before another dispensing operation can begin in Time to Delay after Off Reached field.
  • Page 56 The 6-channel Relay Output card provides four normally open relay outputs and two relay outputs that have both normally open and normally closed contacts with the following connections: Figure 7-2 - 6 Relay Output Card connections The 7-channel Digital Input card provides seven additional digital inputs with the following connections: Figure 7-3 - Input Card connections This card provides for 4 channels of 4-20 mA output loops, which may be programmed via the Action function in the Probe Configuration Wizard.
  • Page 57 Figure 7-4 - During set-up of an analog probe to a 2300 with an analog output card, the analog output connector (on top) appears. Analog Output Control of the analog output signal is through the action type, . As Figure 7-5 shows, this action type only shows when the analog output card is installed.
  • Page 58 2. The 4-20 mA output is scaled so that the process value maps linearly into any range of 4-20 mA output. Figure 7-6 shows the example of a pH probe for which a pH value of 4.0 outputs a current of 4 mA and a pH value of 10 outputs a current of 20 mA.
  • Page 59 Email keywords allow you to customize email alerts so that they tell the receiver precisely what happened in your process. Keyword Name Email Keyword Description System Name {{#systemname}} Name of the AquaMetrix 2300 sensor that sent the email message System Time {{#systemtime}} Time that the email message was sent Sensor Name {{#sensorname}}...
  • Page 60 7.4. Panel Mounting SIDE VIEW FRONT VIEW TOP VIEW Max Panel Thickness 0.3 in 3.65 PANEL CUTOUT 8. Register and Get the Latest Firmware Because the 2300 is so ground-breaking we are always working to improve the user interface with cool new features and easier to use old ones.