Wiring And Setting Up - Tannoy CVS 4 (EN54) Operation Manual

Compact and medium format ceiling loudspeakers
Table of Contents

Advertisement

Available languages

Available languages

7. Wiring and Setting Up

7. Wiring and Setting Up
1. Remove the wiring cover at the back of the speaker can to access
the Euro-type connector plug and socket. Feed the cable through the
gland and attach the Euro-type connector. (Fig.1)
2. For connection to an amplifier, use Pins 1 and 2 (Fig.2):
• Pin 1 is positive
• Pin 2 is negative
For connection to additional speakers in a distributed line,
Pins 3 and 4 are in parallel where:
• Pin 3 is negative
• Pin 4 is positive
3. Tighten the cable gland and plug in the Euro-type connector.
Replace the cover and fix using the supplied screws.
THE SPEAKER IS SUPPLIED IN LOW IMPEDANCE MODE. NEVER
CONNECT THE SPEAKER TO A 70/100 VOLT AMPLIFIER WHILE IT
IS SET FOR LOW IMPEDANCE.
4. The CVS 4 (EN54) is fitted with a 30 W transformer. When used
in distributed-line systems, the transformer can be tapped at 30 W,
15 W and 7.5 W, with an additional 3.75 W tapping for 70.7 V line
systems. (Fig.3)
5. The CVS 6 (EN54) is fitted with a 60 W transformer. When used
in distributed-line systems, the transformer can be tapped at 60 W,
30 W, and 15 W, with an additional 7.5 W tapping for 70.7 V line
systems.
10
CVS (EN54) Operation Manual rev 1.1.1
Fig.1
Fig.2
Fig.3