Alpha-InnoTec VenTower Operating Manual
Alpha-InnoTec VenTower Operating Manual

Alpha-InnoTec VenTower Operating Manual

Air/water heat pumps indoor installation

Advertisement

Quick Links

Air/Water Heat Pumps
Indoor Installation
Operating Manual
VenTower
83030600dUK – Translation into English of the original German operating manual
UK

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VenTower and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Alpha-InnoTec VenTower

  • Page 1 Air/Water Heat Pumps Indoor Installation Operating Manual VenTower 83030600dUK – Translation into English of the original German operating manual...
  • Page 2: Please Read First

    Please read first Symbols This operating manual provides important information The following symbols are used in the operating manual. on the handling of the unit. It is an integral part of the They have the following meaning: product and must be stored so that it is accessible in the immediate vicinity of the unit.
  • Page 3: Table Of Contents

    Contents INFORMATION FOR USERS AND QUALIFIED INSTRUCTIONS FOR QUALIFIED TECHNICIANS PERSONNEL SCOPE OF DELIVERY .............. 11 PLEASE READ FIRST ..............2 Scope of KHZ air/water unit..........11 Available unit variants ............11 SYMBOLS ..................2 ACCESSORIES ................12 INTENDED USE ................4 Accessories necessary for operation ......12 DISCLAIMER................4 Additional accessories ............12 EC CONFORMITY ..............4...
  • Page 4: Intended Use

    Intended use EC conformity The unit is solely to be used for its intended use together The unit bears the CE mark of conformity. with the heat pump supplied with it. This means: EC declarations of conformity, page 39 • for controlled apartment ventilation with heat recovery, •...
  • Page 5: Customer Service

    For a current list and additional partners of the manufac- DANGER! turer, please visit If there are open fireplaces in the apart- www.alpha-innotec.de ment (tiled stoves, hearths, etc.), ensure that when these fireplaces are in use the www.alpha-innotec.com combustion air flow is routed separate-...
  • Page 6: How The Ventilation Module Works

    How the ventilation Maintenance of the unit module works ATTENTION The heat recovery takes place via a highly efficient Keep the air inlet and air outlet openings in the counterflow plate heat exchanger. Energy is removed external wall free of leaves and snow. from the exhaust air.
  • Page 7: Counterflow Plate Heat Exchanger

    • Fold the swivelling door of the ventilation and domestic hot water module upwards… COUNTERFLOW PLATE HEAT EXCHANGER Pull out the two filters on the top right and left- hand side of the heat exchanger, one after the other, Clean the counterflow plate heat exchanger once a year. from the front, check each for dirt and if necessary Proceed as follows: replace…...
  • Page 8: Fans

    FANS Then lift the heat exchanger up slightly and carefully pull it out of the unit from the front… Once a year, have the fans checked by qualified personnel and if necessary have them cleaned. If the air-handling capacity of the unit no longer seems to be sufficient, check the two filters at the top right and left-hand side of the heat exchanger for dirt first and if necessary replace.
  • Page 9: Summer Function

    Summer function Unscrew the front facing panel of the ventilation and domestic hot water module… Drain the domestic hot water tank through the valve NOTICE. mounted on site at the cold water connection… The summer function can only be used in con- junction with a geothermal heat exchanger (pro- After completely draining the tank, remove the vided by the customer).
  • Page 10: Malfunctions

    Malfunctions Then push the left and right-hand filters back into the unit… In case of malfunctions, you can read out the cause of the fault from the diagnostics program of the heating and ATTENTION heat pump controller. Ensure the filters are installed in the correct po- sition.
  • Page 11: Scope Of Delivery

    “Compact” brine/water heat pump delivered on a separate pallet together form the central building services control (KHZ). SCOPE OF KHZ AIR/WATER UNIT 1 VenTower VTL ventilation and VenTower ventilation and domestic domestic hot water module hot water module with plus 2 “Compact”...
  • Page 12: Accessories

    Accessories Replacement filter (accessories for additional cost) for the air inlet cover. Replacement filter (accessories for additional cost) for the defroster heating. ACCESSORIES NECESSARY FOR OPERATION Room remote adjuster (accessories for additional cost) ATTENTION for increasing or lowering the set temperature by up to Use only original accessories from the manufac- 5 K and with forced ventilation function.
  • Page 13: Transport To Installation Location

    TRANSPORT TO INSTALLATION LOCATION TRANSPORT WITH A HAND TRUCK Always comply with the following safety information Remove packaging and set extra box aside (will be during transport: needed later on!)... Dispose of the transport and packaging materials DANGER! properly and under ecological aspects… Several people are required to transport the unit.
  • Page 14: Installation

    “Technical data/Scope of delivery” overview, TRANSPORT OVER STAIRS WITHOUT HAND CART “General unit data” section in the operating Secure the unit with ropes or similar and slowly slide it manual of the respective heat pump down two wooden planks. Mount feet. ATTENTION Use the base frame part of the rear of the unit ATTENTION...
  • Page 15: Domestic Hot Water Tank Integration

    NOTICE. NOTICE If the ventilation and domestic hot water mod- Close off any connections not required with ap- ule is operated with a “Compact” air/water heat propriate plugs. pump, position the ventilation and domestic hot water module f lu sh with either the right or left-hand side of the “Compact”...
  • Page 16: Installation Of The Ventilation Duct

    Installation of the Use the T-piece to connect this connection hose with the heating and domestic hot water inlet ventilation duct (return) at the rear of the heat pump (2)… Install a bleeder and a shut-off device at the heating flow of the ventilation and domestic hot water ATTENTION module …...
  • Page 17: Extract Air Integration (Khz-Lw

    EXTRACT AIR INTEGRATION (KHZ-LW… ONLY) To do this, push the flexible pipe over the connecting socket and fix with hose clips… First, insert the connecting sleeves supplied with the KHZ-LW  … in the opening provided in the intake cover also included with the KHZ-LW … Insulate flexible pipe.
  • Page 18: Electrical Connections

    Electrical connections Push the cables through the cable duct in the heat pump in the direction of the electrical switch cabinet (LWC) … The following applies to all work to be performed: DANGER! Danger of fatal injury due to electric current! Electrical connections may be installed only by qualified electricians.
  • Page 19 VenTower terminal diagram, page 37 Connect the power supply cable to the 230V terminal block in the electrical switch cabinet of the VenTower …...
  • Page 20: Control Unit Of The Ventilation And Domestic Hot Water Module

    Control unit of the ventilation Flush the domestic hot water tank until no more air and domestic hot water discharges from the valves at the taps… Close domestic hot water valves at the taps. module You can set the various parameters for controlling the Insulating the ventilation and domestic hot water module (air volume flows, operating mode, switching times, etc.) using the...
  • Page 21: Commissioning

    Commissioning Dismantling Ensure that the air ducting has been installed DANGER! according to this operating manual and the Danger of fatal injury due to electric ventilation project planning… current! Electrical connections may be worked on Ensure that all filters in the ventilation and domestic only by qualified electricians.
  • Page 22: Technical Data / Scope Of Delivery

    Technical data / scope of delivery Unit designation Installation location Inside ı Outside • Applicable ı — Not applicable Conformity Limits of application See heat pump General unit data Dimensions See dimensional drawing Weight (total) Ventilation module Air volume flow minimum/maximum m³/h / m³/h Maximum air volume flow at 100 Pa external compression m³/h...
  • Page 23 VT… 300 VT… 400 • ı — • ı — • • 50 ı 300 70 ı 400 • • • • 6 ı 114 18 ı 350 813302b 813303b Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 24: Available External Compression

    VenTower_300 Available external compression ∆p (Pa) DV WT DV Filter DV Umlenk DV Gesamt Lüfter max.ExtLüfter 490 ## 380 13,8 1,23 1,23 16,26 415 ## 340 55,2 4,91 4,91 65,02 357 ## 290 124,1 11,1 11,1 146,3 277 ## 205 “...
  • Page 25: Ventower_400

    Available external compression VenTower_400 ∆p (Pa) DV WT DV Filter DV Umlenk DV Gesamt Lüfter max.ExtLüfter 870 ## 380 13,8 1,23 1,23 16,26 805 ## 340 55,2 4,91 4,91 65,02 739 ## 290 124,1 11,1 11,1 146,3 683 ## 205 220,8 19,64 19,64...
  • Page 26: Fan Characteristic Curves Ventower_300

    VenTower_300 Fan characteristic curves Legend: UK81202xx “ Volume flow ∆p Compression Ventilator/fan speed Power consumption Sound pressure level Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 27: Ventower_400

    Fan characteristic curves VenTower_400 Legend: UK81202xx “ Volume flow ∆p Compression Ventilator/fan speed Power consumption Sound pressure level Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 28: Dimensional Drawings

    KHZ air/water Dimensional drawings 1910 1860 1778 1784 1334 1138 1132 Legende: 819330a Technische Änderungen vorbehalten. Alle Maße in mm. Pos. Bezeichnung Key: UK819330b All dimensions in mm. Vorderansicht Manometer Heizkreis Item Designation Draufsicht Durchführungen für Elektro-/ Fühlerkabel Front view Manometer heating circuit Seitenansicht von rechts Kondensatschlauch Ø...
  • Page 29: Installation Plans

    Installation plan version 1 KHZ air/water ≥600 ≥600 >2970 Legend: UK819329-1 All dimensions in mm. Bezeichnung Ä e t l ö ü f Item Designation Dim. e l l ß ö With finished wall thickness 240 to 320 1330 Zubehör: Luftkanal 700x700x1000 With finished wall thickness 320 to 400 1250 Bezeichnung...
  • Page 30: Installation Plan Version 2

    KHZ air/water Installation plan version 2 ≥600 ≥600 >2970 Bezeichnung Legend: Ä UK819329-2 e t l ö All dimensions in mm. ü f e l l ß ö Item Designation Dim. Zubehör: Luftkanal 700x700x1000 With finished wall thickness 240 to 320 1330 Bezeichnung ß...
  • Page 31 Installation plan version 3 KHZ air/water 1280 ≥600 ≥600 >3830 Bezeichnung Legend: UK819329-3 All dimensions in mm. Ä e t l ö ü f e l l ß ö Item Designation Dim. Zubehör: Luftkanalbogen 700x700x750 With finished wall thickness 240 to 320 Bezeichnung ß...
  • Page 32: Installation Plan Version 4

    KHZ air/water Installation plan version 4 1280 ≥600 ≥600 >3830 Bezeichnung Legend: UK819329-4 All dimensions in mm. Ä e t l ö ü f Item Designation Dim. e l l ß ö With finished wall thickness 240 to 320 Zubehör: Luftkanalbogen 700x700x750 With finished wall thickness 320 to 400 Bezeichnung ß...
  • Page 33 Installation plan version 5 KHZ air/water 2280 ≥600 ≥600 >4530 Bezeichnung Ä e t l ö ü f e l l ß ö Zubehör: Luftkanal 700x700x1000 Legend: UK819329-5 All dimensions in mm. Bezeichnung ß ö Item Designation Dim. Bei Fertigwandstärke 240 bis 320 Einbau über Erdgleiche: With finished wall thickness 240 to 320 Bei Fertigwandstärke 320 bis 400...
  • Page 34: Installation Plan Version 6

    KHZ air/water Installation plan version 6 2280 ≥600 ≥600 >4530 Legend: UK819329-6 All dimensions in mm. Bezeichnung Ä e t l ö ü f Item Designation Dim. e l l ß ö With finished wall thickness 240 to 320 Zubehör: Luftkanal 700x700x1000 With finished wall thickness 320 to 400 Bezeichnung ß...
  • Page 35: Default

    Default KHZ lucht-water Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 36: Legend Hydraulic Integration

    Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 37: Terminal Diagram

    Terminal diagram VenTower 1~N/PE/230V/50Hz ZUP/ZIP ZW2/SST Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 38: Circuit Diagram

    VenTower Circuit diagram yellow blue white yellow blue white Subject to change without notice | 83030600dUK – Translation into English of the original German operating manual | ait-deutschland GmbH...
  • Page 39: Ec Declaration Of Conformity

    EC Declaration of Conformity in accordance with the EC Machinery Directive 2006/42/EC, Annex II A The undersigned confirms that the following designated device(s) as designed and marketed by us fulfill the standardized EC directives, the EC safety standards and the product-specific EC standards. In the event of modification of the device(s) without our approval, this declaration shall become invalid.
  • Page 40 GmbH Industriestraße 3 D-95359 Kasendorf E info@alpha-innotec.de W www.alpha-innotec.de alpha innotec – an ait-deutschland GmbH brand...