Summary of Contents for TempMaster OmniElite TMAL 050-061
Page 1
FORM TPM1-EG1 (516) TempMaster OmniElite ® ™ SINGLE PACKAGE ROOFTOP UNITS ENGINEERING GUIDE 50–65 Tons Cooling and Heating (Gas, Electric, Water, and Steam) R-410A Mod F LD19892...
Page 2
M : Medium M : Packaged Rooftop V : VAV, VFD H : High B: Bottom 5 : 208/3/60 R: Rear T : TempMaster 230/3/60 S: Side 6 : 460/3/60 8 : 575/3/60 50 Ton Capacity F : Revision Level...
FORM TPM1-EG1 (516) Introduction The TempMaster OmniElite Single Package Units – ® ™ designed to meet the demands of the market for today and tomorrow. Better Economy... Lower total cost of ownership • Accurate Ventilation Control: Ensures that no more than the proper amount of ven- tilation air is utilized.
Page 6
FORM TPM1-EG1 (516) Outside Air Exhaust Air LD20074 FIGURE 1 - STANDARD CABINET ASSEMBLY TEMPMASTER...
• Easy access for diagnostics. • BACnet or LonWorks communications capabilities. 3. Double-Wall Construction • Standard construction of the TempMaster OmniElite. • Powder coated, pre-fabricated panels. • Corner post for maximum exterior surface protection 4. Filters Section - TempMaster OmniElite has multiple filtration options to improve IAQ • 2" cleanable • 2"...
Page 8
5/16- or 1/4-inch plastic tubing and a static pressure probe must be field supplied/installed approximately 3/4 down the longest supply duct run. Single Zone VAV – TempMaster OmniElite is available for single zone variable air volume (VAV) applications in compliance with ASHRAE 90.1-2010 and 2013. In cooling mode, refrigeration capacity or compressor stages are cycled on or off to maintain supply air temperature.
Page 9
(at no additional energy cost) for the air off the cooling coil. Educational facilities, places of worship, restaurants, gymnasiums, and museums/learning centers are all applications that benefit from the enhanced humidity control of TempMaster OmniElite Modulating HGRH rooftop option.
Page 10
Programmable Thermostat – This option is for a ship-loose thermostat to interface with the TempMaster OmniElite unit. All models, TMAL050-061, include an interface for a 7-wire thermostat as standard. COMMUNICATIONS BACnet MSTP (RS-485) Communications –...
Page 11
An exhaust hood with a modulating control damper is used to maintain building pressure via the building static pressure. The powered return fan is also available without the exhaust capabilities. For units with no exhaust capabilities, the HVAC system must provide alternate means of controlling building pressure. TEMPMASTER...
Page 12
That’s why TempMaster OmniElite Packaged Air Conditioners use established scroll compressor technology to deliver dependable, economical perfor- mance in a wide range of applications. With the TempMaster OmniElite Packaged Roof- top Units, you get the latest generation of compressor enhancements added to the scroll’s inherent strengths.
Page 13
Industry-leading 1,000-hour salt-spray rating, per ASTM B117, keeps unit in superior con- dition. TempMaster OmniElite packaged systems are offered with two common foot prints (stan- dard and extended). The extended cabinet allows for left or right side discharge with hydronic heating coils. Note: Electric heat and gas are not available options for extended cabinet.
Page 14
FORM TPM1-EG1 (516) THIS PAGE INTENTIONALLY LEFT BLANK. TEMPMASTER...
FORM TPM1-EG1 (516) Application Data GENERAL The TempMaster OmniElite air conditioning units are designed for outdoor installation. When selecting a site for installation, be guided by the following conditions: • Unit must be installed on a level surface. • For the outdoor location of the unit, select a place having a minimum sun exposure and an adequate supply of fresh air for the condenser.
Page 16
LD08044 NOTE: 1. Under certain conditions these clearances may be encroached upon. However, doing so may impact system performance. 2. This is a visual reference for all TempMaster OmniElite units. FIGURE 2 - UNIT CLEARANCES RIGGING Proper rigging and handling of the equipment is mandatory during unloading and setting it into position to retain warranty status. Rigging and lifting should only be done by a profes- sional rigger in accordance with a written rigging and lifting plan.
Page 17
OA = Outside Air NOTE: This diagram is provided as a visual reference of the TempMaster OmniElite discharge & return air openings & locations for all sizes. Please refer to the dimensional data for exact size & location of panels and openings.
Page 18
If the applica- tion calls for horizontal supply and return air, TempMaster can ship it from the factory as a horizontal unit. This option alleviates the need for field modification of equipment, sav- ing time and money.
Page 19
In this application, a powered exhaust fan may be suitable, however careful consideration of the fan type is necessary. TempMaster offers a centrifugal powered exhaust fan to perform this function. Some manufacturers use a propeller exhaust fan, which cannot handle the static pressure requirements.
Page 20
FORM TPM1-EG1 (516) THIS PAGE INTENTIONALLY LEFT BLANK. TEMPMASTER...
Cu Tube, Al Fin Cu Tube, Al Fin Cu Tube, Al Fin Quantity of Coils Tube Type 0.5" 0.5" 0.5" 0.5" Rows (each) Total Face Area (sq ft), Standard Cabinet 30.7 ft 30.7 ft 30.7 ft 30.7 ft Total Face Area (sq ft), Extended Cabinet 20.1 ft 20.1 ft 20.1 ft 20.1 ft TEMPMASTER...
Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit blower tables to select the blower speed and the BHP requirement. Solution: As in the example above, no temperature information is given so 70.0 °F is as- sumed. TEMPMASTER...
Page 26
Enter the blower table at 6000 CFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft. Suppose that the corresponding BHP listed in the blower table is 3.2. This value must be corrected for elevation. BHP at 5,000 ft = 3.2 x .832 = 2.66 TEMPMASTER...
TABLE 18 - FORWARD-CURVED FAN Total Static Pressure (inches of water column) CFM STD. 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 10.5 NOTE: For performance at operating points not included in these tables, consult your local TempMaster representative. TEMPMASTER...
FORM TPM1-EG1 (516) Electrical Data ELECTRICAL SERVICE SIZING In order to use the electrical service required for the cooling-only TempMaster OmniElite, use the appropriate calculations listed below from U.L. 1995. Based on the configuration of the unit, the calculations will yield different MCA (minimum circuit ampacity), and MOP (maximum overcurrent protection).
Page 38
TABLE 25 - ELECTRIC HEAT AMP DRAW NOMINAL VOLTAGE 208V/3PH/60HZ 240V/3PH/60HZ 480V/3PH/60HZ DESCRIPTION 208V/230V 460V 575V AMPS AMPS AMPS AMPS AMPS AMPS 111.1 96.3 48.2 Control Transformer 0.5 KVA 222.3 192.7 96.3 Convenience Outlet 300.1 260.1 130.1 Gas Heat 180.6 TEMPMASTER...
Controls CONTROL SEQUENCES (VAV) FOR IPU CONTROLLER GENERAL The control system for the TempMaster Packaged Rooftop Unit is fully self-contained and based around a single package unit controller. To aid in unit setup, maintenance, and op- eration, the single package unit controller is equipped with a user interface that is based around a 4 line x 20 character backlit LCD display. The LCD displays plain language text in a menu-driven format to facilitate use.
Page 40
If economizer cooling alone is insufficient for the cooling load, the unit controller shall stage up compressors, one at a time, to meet demand. The control logic for the three types of economizers is as follows: TEMPMASTER...
Page 41
Outside Air damper to maintain the Minimum AirFlow Setpoint through the Air Mea- surement Station. The unit controller shall control the Outside Air damper to this flow rate as long as the unit is in the Occupied mode, and the economizer is not suitable for cooling. TEMPMASTER...
Page 42
As the return and/or exhaust air dampers open, the return plenum pressure drops, the fan will speed up to maintain pressure. When the return and/or exhaust air dampers close, the return plenum pressure increases causing the VFD to slow the fan speed down. TEMPMASTER...
Page 43
Outside Air temperatures of 0.0 °F. SMOKE PURGE SEQUENCES General The controls of the TempMaster OmniElite are designed as standard with a Ventilation Override sequence to remove, exhaust, or ventilate smoke, fumes, or other air born con- taminates from the occupied space. This feature offers three selectable operations, which include Purge, Pressurization, and Evacuation. The sequence is activated via one of three...
Page 44
Hardwired and Communicated is the method the Unit Controller uses to deter- mine the “ZONE TEMP.” In the Hardwired mode, the input is an analog input to the control. In the Communicated mode, the input is a serial input from a BAS control system. TEMPMASTER...
Page 45
The only difference between Hardwired and Communicated is the method the Unit Con- “ZONE TEMP.” troller uses to determine the In the Hardwired mode the input is an ana- log input to the control. In the Communicated mode the input is a serial input from a BAS control system. TEMPMASTER...
If conditions are suitable for economizing, the single package unit controller will modulate the Outside Air damper in addition to staging heating steps up and down to maintain the zone temperature setpoint. TEMPMASTER...
1. 10’ Clearance minimum over the top of the condensing unit. 2. Only one adjacent wall can exceed unit height. 3. 12’ Clearance required to adjacent units 4. 8’ Service access recommended on one side. 5. Outside air hoods are folded for shipment. FIGURE 8 - GENERAL ARRANGEMENT DRAWING LD08436 TEMPMASTER...
Page 50
1. 10’ Clearance minimum over the top of the condensing unit. 2. Only one adjacent wall can exceed unit height. 3. 12’ Clearance required to adjacent units 4. 8’ Service access recommended on one side. 5. Outside air hoods are folded for shipment. FIGURE 9 - GENERAL ARRANGEMENT DRAWING LD08437 TEMPMASTER...
Page 51
1. 10’ Clearance minimum over the top of the condensing unit. 2. Only one adjacent wall can exceed unit height. 3. 12’ Clearance required to adjacent units 4. 8’ Service access recommended on one side. 5. Outside air hoods are folded for shipment. FIGURE 10 - GENERAL ARRANGEMENT DRAWING LD08438 TEMPMASTER...
Page 52
1. 10’ Clearance minimum over the top of the condensing unit. 2. Only one adjacent wall can exceed unit height. 3. 12’ Clearance required to adjacent units 4. 8’ Service access recommended on one side. 5. Outside air hoods are folded for shipment. FIGURE 11 - GENERAL ARRANGEMENT DRAWING (EXTENDED CABINET) LD08439 TEMPMASTER...
Page 53
1. U nit must be installed square and level. 2. C urb configuration for “bottom” return and “bottom” supply. 3, T hese drawings are not intended as construction documents for the field fabricated roof curbs. TempMaster will not be responsible for the unit fit up, leak integrity, or sound level for installation using field fabricated roof curbs. 4. The TMAL unit does not have a base pan under the condensing section of the unit. Field fabricated roof curbs must have a cap on the top of the condensing section of the curb to prevent moisture from entering the space.
1.5" MPT NOTES: 1. Location of return (steam) or supply (HW) line connection, horizontal from economizer corner post, in direction of airflow 2. Location of supply (steam) or return (HW) line connection, horizontal from economizer corner post, in direction of airflow 3. Location of both supply and return lines, horizontal from outside casing of unit, across direction of airflow 4. Location of supply and return lines, vertical from bottom edge of base rail MPT = Male Pipe Thread FPS = Female Pipe Sweat FPT = Female Pipe Thread Steam and Hot Water connections w/o controls are fittings connections facing side of the unit, at locations indicated. TEMPMASTER...
FORM TPM1-EG1 (516) Power/Control Entry Drawing – 50–61 Models CONTROL PANEL POWER AND CONTROL WIRING 166-3/16” PENETRATIONS THROUGH BOTTOM 8-1/4” AIRFLOW LD19504 FIGURE 14 - POWER/CONTROL WIRING LOCATION TEMPMASTER...
This coordination shall include, but not be limited to, the following: 1. Structural supports for units. 2. Roof curb transition. 3. Piping size and connection/header locations. 4. Electrical power requirements and wire/conduit and overcurrent protection sizes. 5. All costs incurred to modify the building provisions to accept the furnished units. TEMPMASTER...
Page 60
Section 01830 – Operation and Maintenance, including but not limited to instruc- tions for lubrication, filter replacement, compressor, motor and drive replacement, coil cleaning, filter maintenance, spare parts lists, and wiring diagrams. Warranties Equipment shall include the manufacturer’s warranty not less than eighteen months from the date of shipment. Extended parts warranty [optional] shall be included for an additional one [five] years Extended parts and labor warranty [optional] shall be included for an additional one [five] years TEMPMASTER...
Page 61
Latches shall be positive-action, creating an airtight seal between the door and unit. Panels and doors shall be completely gasketed with a closed-cell, neoprene gasket. Door tiebacks shall be provided for all doors to secure doors while servicing. TEMPMASTER...
Page 62
3. On/Off, Fan-Powered Exhaust: A DWDI forward-curved centrifugal exhaust fan shall be provided to exhaust building return air to relieve building static pressure. The fans shall be constant volume and operate based on either a building static pressure, or outside air-damper position. TEMPMASTER...
Page 63
Fan shafts shall be selected to operate well below the first critical speed and each shaft shall be factory coated after assembly with an anticorro- sion coating. Filter Section [SELECT A FILTER RACK, FILTER MEDIA, AND SWITCH IF DESIRED] 1. Angled Filter Rack: 2-inch throwaway filters shall be provided in an angled filter rack. 2. Angled Filter Rack: 2-inch carbon media filters shall be provided in an angled filter rack. TEMPMASTER...
Page 64
(L50) of at least 200,000 hours. All bearings shall be factory lubricated and equipped with standard hydraulic grease fittings and lube lines extended to the motor side of the fan. Fan drives shall be selected for a 1.5 service factor and antistatic belts shall be TEMPMASTER...
Page 65
3. VAV Fan Control: TempMaster OmniElite units are available for a traditional over- head Variable Air Volume system. In this configuration, the Supply Fan speed is controlled by a VFD to maintain duct pressure.
Page 66
Power connection to the heater is through the power panel for the unit. Electric heat is ETL certified to both US and Canadian safety standards. 6. Hot Water Heating Coil: A hot water coil shall be installed in the rooftop unit dis- charge plenum. TEMPMASTER...
Page 67
Each compressor shall include an oil sight glass. 4. Low Ambient: Compressors shall operate down to 0.0 °F Control [optional] by monitoring the refrigeration system discharge pressure and adjusting condenser airflow to maintain the proper head pressure to protect compressor operation. TEMPMASTER...
Page 68
A control points list shall be provided by the manufacturer to facilitate communica- tions programming with the building automation system. Programming, establishing communications, and commissioning shall be the responsibility of the installing con- trols contractor. Start-up assistance and support may be purchased from the manu- facturer. TEMPMASTER...
Page 69
Location: Locate the unit as indicated on drawings, including cleaning and service main- tenance clearance per Manufacturer instructions. Adjust and level the unit on support structure. INSPECTION AND START-UP SUPERVISION A factory-trained service representative of the manufacturer shall supervise the unit start- up and application specific calibration of control components. TEMPMASTER...
Need help?
Do you have a question about the OmniElite TMAL 050-061 and is the answer not in the manual?
Questions and answers