Specifications; Table 1.1 Power Specifications; Table 1.2 Ups Module Information - Mitsubishi Electric 9800A Series Owner Technical Manual

Mitsubishi motors uninterruptible power supply system owners/technical manual
Hide thumbs Also See for 9800A Series:
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC

1.4 Specifications

The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.

TABLE 1.1 Power Specifications

Rated output
Power
100kVA / 80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW

TABLE 1.2 UPS Module Information

UPS
CABLE
[kVA]
ENTRY
100
BOTTOM
43.3 / 1100
150
BOTTOM
47.2 / 1200
225
BOTTOM
55.1 / 1400
300
TOP
76.8 / 1950
375
TOP
76.8 / 1950
500
TOP
114.2 / 2900
750
TOP
129.9 / 3300
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Input voltage
Bypass input voltage
3 phase / 3 wire
3 phase / 4 wire
480V
480V
480V
480V
480V
480V
480V
WIDTH
DEPTH
[in / mm]
[in / mm]
29.8 / 758
29.8 / 758
29.8 / 758
37.7 / 958
37.7 / 958
37.7 / 958
49.5 / 1258
MITSUBISHI ELECTRIC 9800A SERIES UPS
3 phase / 3 or 4 wire
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
HEIGHT
WEIGHT
[in / mm]
[lb./ kg]
79.7 / 2025
2100 / 950
79.7 / 2025
2820 / 1275
79.7 / 2025
3310 / 1500
79.7 / 2025
4990 / 2260
79.7 / 2025
5250 / 2380
79.7 / 2025
6930 / 3140
79.7 / 2025
9655 / 4380
Page Number:
1-13
Output voltage
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
HEATING
[kBTU/h]
22.0
33.0
45.0
68.0
84.0
98.0
136.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents