Page 1
Installation and Operation Manual Hochiki America Corporation 7051 Village Drive, Suite 100 Version 1.90 - UL Buena Park, CA 90621-2268 Created: 08/15/05 714.522.2246 Corporate Headquarters Updated: 08/24/2010 800.845.6692 Technical Support http://www.hochiki.com PN# 1700-09948 FireNET 4127 I & O Manual v1.90 UL...
3.5.1 Voltage Routing Outputs ................35 3.5.2 Relay Outputs ....................36 3.6 Digital Input Connection ..................37 3.7 Using a Printer ....................38 Section 4 – Expander Board Installation ............................... 39 FireNET 4127 I & O Manual v1.90 UL...
Page 3
5.17 SCI Short Circuit Isolator Module ..............78 5.17.1 Class A Operation ..................79 5.17.2 Class B Operation ..................80 5.18 ASB Analog Sounder Base ................81 5.19 AMS Addressable Manual Pull-Station ............82 FireNET 4127 I & O Manual v1.90 UL...
Page 4
8.2.2 Set Times....................112 8.2.3 View Print Event Log ................. 113 8.2.4 Print Configuration ..................114 8.2.5 System Disablements ................114 8.2.6 Loop Data Test ..................115 FireNET 4127 I & O Manual v1.90 UL...
Page 5
9.2 Installing Loop Explorer .................. 116 9.3 Launching Loop Explorer ................117 9.4 Connecting Your PC to the FireNET 4127 ............117 9.4.1 Using PC Connect ..................117 9.4.2 Setting a COM Port ..................122 ...
Page 6
A.7 Using the FNV-MP with FireNET ..............214 A.8 Changing the FN-PS402 Power Supply to 240VAC operation ....... 215 Appendix B – Panel Door Label Drawing ................. 216 Appendix C - WARRANTY ......................217 FireNET 4127 I & O Manual v1.90 UL...
Section 1 – Introduction The FireNET 4127 is an analog addressable fire alarm system that meets the requirements of UL 864 9 Edition. 1.1 Basic Features The basic FireNET 4127 control panel includes two SLC (Signaling Line Circuit) loops. Each loop is capable of supporting 127 analog addressable points (can be any combination of sensors and modules) for a total of 254 analog addressable points on the basic panel.
1.2 System Devices and Equipment The following boards, expanders and devices are available from Hochiki America Corp. to be used with the FireNET 4127 analog addressable fire alarm system. For a complete description and installation instructions of each product, please see the appropriate section of this manual and the literature supplied with the device itself.
Page 10
Dual Input Monitor Module Conventional Zone Module Analog Sounder Base AMS/KL/LP Addressable Manual Pull-Station Accessories TCH-B100-NS Hand-held Programmer FN-ACC Battery/Accessory Enclosure (houses up to 33AH size batteries) FN-ETR Enclosure Trim Ring for Panel Flush Mount FireNET 4127 I & O Manual v1.90 UL...
1.2A System Devices BOSCH The following boards, expanders and devices are available from BOSCH to be used with the FireNET 4127 analog addressable fire alarm system. For a complete description and installation instructions of each product, please see the appropriate section of this manual and the literature supplied with the device itself.
1.2B System Devices Silent Knight The following boards, expanders and devices are available from Silent Knight to be used with the FireNET 4127 analog addressable fire alarm system. For a complete description and installation instructions of each product, please see the appropriate section of this manual and the literature supplied with the device itself.
1.2.1 System Replacement Parts Control Panel Repair / Replacement Parts FN-4127-BO FireNET 4127 Control Unit Board Only (K6002) FN-4127-CPA-BO FireNET 4127 Panel Annunciator Board Only (K6001) FN-PS4 FireNET 4 Amp Power Supply (UL864 8 Edition Compliant) FN-PS402* FireNET 4 Amp Power Supply (UL864 9...
Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off or give early warning in as many as 35% of all fires. FireNET 4127 I & O Manual v1.90 UL...
Page 15
• Heat Detectors: Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life. FireNET 4127 I & O Manual v1.90 UL...
Page 16
Property owners should continue to act prudently in protecting the premises and the people in their premises and should properly insure life and property and buy sufficient amounts of liability insurance to meet their needs. FireNET 4127 I & O Manual v1.90 UL...
1.4 Agency Listings, Approvals, Requirements 1.4.1 Federal Communications Commission (FCC) The FireNET 4127 has been verified to comply with FCC Rules Part 15, Class A Operation is subject to the following conditions: 1. This device may not cause radio interference.
F or humidity outside the range of 10%-85% non-condensing. The FireNET 4127 control panel must be installed so that it is not subjected to damage by water and condensation. AVOID mounting the control panel cabinet directly on exterior masonry walls, in areas subject to plumbing leaks, in areas subject to splash from sprinkler test valves, or in high humidity areas.
2.3 Control Panel Layout 2.3.1 Front Panel Layout, Standard Build 8-Line x 40 character LCD Front Panel Indicators Front Panel Controls Enable Controls Key-switch (Access Level 2) Figure 2-3-1 FireNET 4127 I & O Manual v1.90 UL...
Main Control Unit PC Connection SLC Loops Front Panel Controls Programmable Relays Notification Appliance Circuits Programmable Outputs Remote Control and Aux Inputs Expansion Board Connections Network Connections Aux Power Output Figure 2-3-3 FireNET 4127 I & O Manual v1.90 UL...
2.4 Mounting the Control Panel Consult the environmental specifications listed in Section 2.2 to determine a suitable location to mount the FireNET 4127 main control panel. The panel should be mounted so that it is accessible to service personnel and located in a secure area.
DO NOT route AC input power across the main control board (K6002), the ribbon cable interconnects, or directly across or adjacent to the low- voltage connections made on terminal strips X1 (top) or X2 (side). FireNET 4127 I & O Manual v1.90 UL...
NAC 3 Required. 2.5 A* 24VDC 2.5 A* 24VDC Notification Appliance Circuit #4. 10K EOLR NAC 4 Required. 2.5 A* 24VDC *Note: See Section 2.8 for additional details regarding NAC circuit ratings FireNET 4127 I & O Manual v1.90 UL...
Page 28
500mA Auxiliary 24V supply 24VDC 500mA RS485 to other panels 12VDC 100mA NETWORK RS485 to other panels 12VDC 100mA RS485 to other panels 12VDC 100mA NETWORK RS485 to other panels 12VDC 100mA FireNET 4127 I & O Manual v1.90 UL...
Page 29
0 - 4 Amps + Battery +24 VDC - Battery DC Common NOTE: Earth ground fault detection impedance is approximately 15K ohms between earth ground and the FireNET internal floating DC supply. FireNET 4127 I & O Manual v1.90 UL...
FireNET panels dated 1/24/05 or later with s/n 411-00412 or later have NAC circuits rated at 2.5AMPS each. All FireNET panels dated earlier than 1/24/05 with s/n prior to 411-00412 have NAC circuits rated at 1.6AMPS each. FireNET 4127 I & O Manual v1.90 UL...
3.2 Battery Connection The FireNET 4127 fire alarm control panel can charge up to 60AH batteries. Up to 17 AH will fit in the control panel enclosure, as well as larger sizes that have the same size footprint as 17AH batteries.
The total output from the Auxiliary Power terminals must not exceed .500 amps. Any devices powered from the auxiliary power terminals should be entered into Table 2.6 and taken into consideration for standby battery size. Figure 3.3 Four-Amp Power Supply Detail FireNET 4127 I & O Manual v1.90 UL...
Page 33
ADDITIONAL AUX 24VDC Power 500mA Max I/O BOARDS Used for expansion boards and low current auxiliary devices (See Section A.4 for compatible 24VDC Devices) NETWORK NETWORK Figure 3.4 Auxiliary Power Connection Detail FireNET 4127 I & O Manual v1.90 UL...
4. CN T Main REMOTE CONTR OL AND AUX. 5. SIL Control INPU TS Unit 6. PR1 7. PR2 8. PR3 COMMS ADDITIONAL I/O BOARDS AU X Figure 3.5 Notification Appliance Circuit Connection Detail FireNET 4127 I & O Manual v1.90 UL...
INPUTS M ain C ontrol U nit 6. PR 1 7. PR 2 8. PR 3 C O M M S AD D ITIO N AL Figure 3.6 Voltage Routing Outputs Detail FireNET 4127 I & O Manual v1.90 UL...
Unit NC C NO NC C NO NC C NO NC C NO NC C NO NAC 1 NAC 2 FIRE 1 TROUBLE FIRE 2 SUPERVISORY AUXILIARY Figure 3.7 Relay Outputs Detail FireNET 4127 I & O Manual v1.90 UL...
4. CNT REMOTE (EXAMPLE FOR INPUTS 1-8) CONTROL 5. SIL AND AUX. INPUTS (Not Supervised) 6. PR1 Main Control Unit 7. PR2 8. PR3 COMMS Figure 3.8 Remote Control Input Connection Detail FireNET 4127 I & O Manual v1.90 UL...
(see section 8.2.4) or to print the panel’s history log (see section 10.2.2). Serial Printer Properties: • 19.2K Baud • 8 Bits • No Parity • 1-Stop Bit FireNET 4127 I & O Manual v1.90 UL...
Section 4 – Expander Board Installation 4.1 Compatible Expander Boards The following Hochiki America Corp. expander boards are listed as compatible with the FireNET 4127 analog addressable fire alarm system. Expanders • FN-4127-SLC - Dual SLC Loop Expander (Local FACP Expander) •...
RS485 bus devices. Specific wiring connections for each device are included later in this section. For specific wiring distance, connections, and mounting of the FN-LCD-S serial LCD Annunciator, see Section 4.7. FireNET 4127 I & O Manual v1.90 UL...
J3 as shown in figure 4.2.3.1 LED1 LED2 Even if only 1 RS485 bus device is connected to the panel this LED3 jumper must be installed. Jumper J3 Figure 4.2.3.1 FireNET 4127 I & O Manual v1.90 UL...
TO NEXT I/O OUTPUT BOARD 1. TBL 2. RES 3. INT 4. CNT REMOTE CONTROL 5. SIL AND AUX. INPUTS 6. PR1 7. PR2 8. PR3 COMMS ADDITIONAL I/O BOARDS NETWORK NETWORK FireNET 4127 I & O Manual v1.90 UL...
4.3 FN-4127-IO - Input / Output Board In addition to the basic 508 points that the FireNET 4127 can accommodate on the SLC loops additional input and output points can be added by using FN-4127-IO Input/Output boards on the RS485 bus.
Wire Distance 18AWG 875ft 16AWG 1400ft 14AWG 2300ft When powering the I/O board from a separate Aux 24VDC UL Fire listed supply the maximum voltage drop cannot exceed 4VDC. FireNET 4127 I & O Manual v1.90 UL...
If this LED does not flicker then it is LED2 not responding to the control panel and the comms connection should be LED3 checked. LED 1 LED 2 4.4 Reserved for Future Use 4.5 Reserved for Future Use FireNET 4127 I & O Manual v1.90 UL...
Once the detection circuits have been connected, the devices for the new detection circuits can be automatically detected using the auto learn feature from the menu on the control panel (see Section 8 of this manual). FireNET 4127 I & O Manual v1.90 UL...
4.7 FN-L LCD-S S Serial Liqu uid Cryst tal Displa ay Annun ciator The FN-L LCD-S Seria al LCD Ann nunciator du uplicates th he indication ns of the FN N-4127 fire alarm con ntrol panels s. The FN-L LCD-S conn nects to the e control pa anel via RS4...
Page 48
Figure 4.7.3 FN-LCD-S Wiring Detail FireNET 4127 I & O Manual v1.90 UL...
Page 49
FN-4127 Panel Aux 24VDC output or FN-LCD-S. The FN-LCD-S current draw is rated as follows: Standby: 20mA @ 24VDC Alarm: 110mA @ 24VDC Available colors are RED and CHARCOAL as identified below: FN-LCD-S-R = RED FN-LCD-S-C = CHARCOAL FireNET 4127 I & O Manual v1.90 UL...
Section 5 – SLC Device Installation 5.1 Compatible SLC Devices The following Hochiki America Corp. SLC devices are listed as compatible with the FireNET 4127 analog addressable fire alarm system. Detectors (Sensors) • ALK-V / ALK-V2 Analog Photoelectric Smoke Detector •...
Page 51
The “DCP” prefix will be dropped throughout the body of this manual and the shortened model name will be used. Please take note of this when referencing these devices within this manual. FireNET 4127 I & O Manual v1.90 UL...
5.2 Number of Devices The FireNET 4127 comes with 2 SLC loops built-in to the panel. Each loop can support up to 127 analog addressable detectors and modules as well as 127 analog sounder bases for a total of 254 possible per loop. By adding the FN-4127-SLC expander card, 2 additional SLC loops can be added to the panel for a total of 4 loops.
#14 AWG. When using a Class B SLC wiring configuration, be sure that the 0 ohm jumpers supplied with the panel are properly installed between –OUT to –IN and +OUT to +IN (Hochiki part # 0400-01025). Figure 5.3.1 Maximum Wiring Distance for Class B SLC Circuits FireNET 4127 I &...
14 AWG 10,000 Feet 10 11 12 13 14 15 16 LOOP 1 LOOP 2 LOOP 3 LOOP 4 MAIN CONTROL UNIT Figure 5.3.2 Maximum Wiring Distance for Class A SLC Circuits FireNET 4127 I & O Manual v1.90 UL...
+ 127). Example: The sensor address is 36. 36 +127 = 163. The ASB will have an address of 163. This address is what the FireNET 4127 control panel uses to identify each addressable device and control its functionality. All Hochiki addressable devices come from the factory preset to address 127.
Page 56
3. Mini-modules such as the FRCME-S and FRCME-P should not be connected to the SLC loop when using the TCH-B100-NS programmer to set addresses. 4. When programming the AMS, use the same method as the 4-S type addressable modules. FireNET 4127 I & O Manual v1.90 UL...
5.4.1 Detector Addressing This section applies to the following Hochiki analog detectors – ALK-V, ALK-V2, ALG- V, AIE-EA, DH-98, ATG-EA, and ACA-V. Follow these steps to program a new address into any one of these analog detectors. (Refer to Figure 5-4) 1.
5.4.3 Mini Module Addressing This section applies to the Hochiki FRCME-S, FRCME-P and FRCME-M addressable mini-module. Follow these steps to program a new address into any of these addressable modules. (Refer to Figure 5-4) 1. Using the single ended programming plug, plug the end with the jack on it into the programming jack on the programmer.
5.5 Smoke and Heat Detector Wiring This section includes wiring instructions for connecting the following analog detectors to the FireNET 4127 fire alarm control panel: ALK-V / ALK-V2 Photoelectric Smoke Detector, ALG-V Photoelectric Smoke Detector, AIE-EA Ionization Smoke Detector, ATG-EA Heat Detector, ACA-V Multi Detector. All FireNET analog detectors must be installed using a YBN-NSA-4 four-inch detector base, or a HSB-NSA-6 six-inch detector base.
5.6 Analog Duct Detector Wiring This section includes wiring instructions for connecting the DH98-A analog duct detector, and the DH98-AR analog duct detector with relay, to the FireNET 4127 control panel SLC loop. For detailed instructions on the physical mounting and wiring of FireNET analog duct detectors please refer to the installation instructions that are included with each device.
Figure 5.6.1 DH98-A 5.6.1 DH98-A Analog Duct Detector Connect the DH98-A analog duct detector to the FireNET 4127 control panel SLC loop as shown in Figure 5.6.1. Terminals 3 and 4 can be used to power a remote alarm LED. The ratings on these terminals are 24 VDC at .008 amps maximum.
(10mA standby and 55mA alarm) connected to terminals 3+ and 4-. This power may come from the FireNET 4127 main control panel auxiliary power (500 mA max.) connections (terminals 18 and 19) or from an external power supply.
FireNET 4127 SLC loop. More than one switch can be connected to a FRCME-4 however you must not mix multiple switch types on a single FRCME-4. For example: three waterflow switches connected to a single FRCME-4 is acceptable.
The FRCME-S input module is used to connect standard normally open dry contact types of fire alarm devices such as manual pull stations to the FireNET 4127 SLC loop. The FRCME-S must be programmed with a unique address from 1-127. All of the dry contact type devices connected to a single FRCME-S appear at the main control panel as a single address.
The FRCME-P input module is used to connect standard normally open dry contact types of fire alarm devices such as manual pull stations to the FireNET 4127 SLC loop. The FRCME-P must be programmed with a unique address from 1-127. All of the dry contact type devices connected to a single FRCME-P appear at the main control panel as a single address.
The FRCME-M input module is used to connect standard normally open dry contact types of fire alarm devices such as manual pull stations to the FireNET 4127 SLC loop. The FRCME-M must be programmed with a unique address from 1-127. All of the dry contact type devices connected to a single FRCME-S appear at the main control panel as a single address.
IN - IN SC - OUT + OUT - IN S + 12 13 LOOP 1 LOOP 2 LOOP 3 LOOP 4 MAIN CONTROL UNIT Figure 5.11.1 FRCMA-I Input Module Class A Detail FireNET 4127 I & O Manual v1.90 UL...
Page 68
Reference the input wiring distance limitation table below for all types of FRCM modules: Maximum Distance Between Module and EOL Device 14 AWG 1500 Ft. 16 AWG 900 Ft. 18 AWG 550 Ft. FireNET 4127 I & O Manual v1.90 UL...
5.12 R2M Dual Relay Module Wiring The R2M provides two separately programmable relay outputs on the FireNET 4127 SLC loop. These outputs may be used for a variety of purposes including door holders, elevator recall, and other fire safety functions.
OUT (-) Compatible UL listed signaling device(s) UL Listed EOLR Part # 0400-01046 10K Ohm LOOP 1 LOOP 2 LOOP 3 LOOP 4 MAIN CONTROL UNIT Figure 5.13.1 SOM Supervised Output Module Detail FireNET 4127 I & O Manual v1.90 UL...
The SOM-A / SOM-AI is suitable for use only with non-synchronized audible devices. Figure 5.14.1 SOM-AI Supervised Output Module Detail FireNET 4127 I & O Manual v1.90 UL...
4. The SOM-R-DS keyswitch connected to the FRCME module must be connected to the FireNET SLC. Use the TCH-B100 programmer to assign an address to the module and then connect the SLC circuit to the S+ and SC- terminals on the module. FireNET 4127 I & O Manual v1.90 UL...
Page 73
Output delays are not applied to the activation of the SOM-R. The SOM-R output is activated immediately upon detection of a fire condition by the FireNET control panel. FireNET 4127 I & O Manual v1.90 UL...
Page 74
NOTE: DO NOT DISABLE THE SOM-R OR KEYSWITCH MODULE BY USING THE DISABLEMENTS MENU ON THE FIRENET CONTROL PANEL! Solenoid Compatibility List Manufacturer Model Number Standby Current (Amps) Alarm Current ASCO 8210G207 44mA Parker/Skinner 73218BN4UNLVNOC111C2 42mA FireNET 4127 I & O Manual v1.90 UL...
Page 75
Test Weekly: The preaction system should be tested weekly to make sure SOM-R, FRCME and SOM-R-DS (Bypass Keyswitch) are working properly. The most common cause of an alarm system not functioning when a fire occurs is inadequate maintenance. FireNET 4127 I & O Manual v1.90 UL...
Refer to the installation instructions included with the CZM for more detailed wiring and installation instructions. FireNET Control Panel FireNET Control Panel Figure 5.15.1 CZM Conventional Zone Module FireNET 4127 I & O Manual v1.90 UL...
5.16 DIMM Dual Input Monitor Module The Hochiki DIMM Dual Input Monitor Modules were designed to work with pull stations, water flow switches, and other applications requiring the monitoring of dry contact alarm initiating devices. The DIMM can monitor two independent inputs with discrete reporting, yet the module only requires a single address on the SLC Loop.
Style 7 (see Section 5.17.1), no devices are lost from a single short on the SLC loop. Connect the SCI module to the FireNET 4127 control panel as shown in Figure 5.17.1. Refer to the installation instructions included with each SCI for more detailed wiring and installation instructions.
In the event of a short circuit on the SLC loop, the closest SCI to the short circuit will activate and it’s LED will turn on. All devices following the SCI module will be isolated and inoperative. All devices preceding the SCI module will remain operational. Figure 5.17.3 FireNET 4127 I & O Manual v1.90 UL...
The addressable sounder is independently controlled by the control panel, and does not have to follow the detector status to activate. Refer to the installation instructions included with the ASB for more detailed installation and wiring instructions. FireNET 4127 I & O Manual v1.90 UL...
Section 6 - Network Connections 6.1 Compatible Network Devices The following Hochiki America Corp. FireNET network devices are listed as compatible with the FireNET 4127 analog addressable fire alarm system. Network Interface Card • FN-4127-NIC Network Devices • FN-LCD-N Network LCD Annunciator This section covers the installation of the devices listed above.
Under normal circumstances, both LEDs will be lit, indicating that the card is communicating properly. If one or both of the LEDs are not lit then the connection to neighboring panels is not functioning properly. FireNET 4127 I & O Manual v1.90 UL...
Page 85
350 ft. (100m) and 3650 ft. (1100m) or 2000ft. (600m) and 2000ft. (600m). Using these general rules and the specified or equivalent cable types will provide a guaranteed performance of networks with plenty of tolerance. FireNET 4127 I & O Manual v1.90 UL...
Page 86
5. Open circuit troubles should allow the network to continue operating in the same way as short circuit troubles. 6. Network cabling should be standard RS485 type for up to 64 nodes. 7. The minimum cable size for the FireNET network is #20 AWG. FireNET 4127 I & O Manual v1.90 UL...
Page 87
In order to reduce the effects of such noise, terminate the shield to the earth ground terminal block in the main control panel. DO NOT ground the shield at both ends of the cable! FireNET 4127 I & O Manual v1.90 UL...
Page 88
6.1.1.5 C onnecting the netwo ork cable All panels s will have t two cables connected to another r panel or pa anels. If eit ther of thes is not con nnected the en a trouble e will be disp played.
Figure 6.1 FN-LCD-N Network LCD Annunciator When powering the FN-LCD-N from the FireNET Aux 24VDC power (limited to 500ma), the following maximum wiring distances apply at the gauges noted: Wire Distance 18AWG 925ft 16AWG 1500ft 14AWG 2400ft FireNET 4127 I & O Manual v1.90 UL...
Page 90
Aux 24VDC output (500ma max. each). The current limits during both standby and in alarm shall not exceed the 500 mA rating. Available Colors: RED and CHARCOAL, FN-LCD-N-R = RED, FN-LCD-N-C = CHARCOAL FireNET 4127 I & O Manual v1.90 UL...
All of these operations are performed from the front panel keypad. Please refer to the front panel photo in Figure 7.1 below while reading through this section. Figure 7.1 Front Panel Control FireNET 4127 I & O Manual v1.90 UL...
7.2.1 Performing a Lamp Test Press the “ Lamp Test ” button on the front panel to illuminate all front panel LED indicators, LCD display, and validate correct operation. Release the button to conclude the test. FireNET 4127 I & O Manual v1.90 UL...
“ Help ” button to display this additional information. Note: When using the Denver Door build of the FireNET panel, the front door of the panel must be opened to perform these commands. FireNET 4127 I & O Manual v1.90 UL...
7.3.1. Press the “ Resound Alarm ” button. Pressing the “ Resound Alarm ” button will reactivate any audible or visual notification appliances that were previously silenced using the Alarm Silence operation. FireNET 4127 I & O Manual v1.90 UL...
4127 main control panel. The user can silence the panel sounder by pressing the “ Panel Sounder Silence ” button on the front panel. This silences only the panel sounder. Other audible outputs such as horns or strobes require a different operation to silence. FireNET 4127 I & O Manual v1.90 UL...
Untimed disablements should be used only when it is necessary to disable a portion of the system for over 24 hours. Untimed disablements remain active until they are manually reset at the panel through the Access Level 2 Main Menu / Disablements command. FireNET 4127 I & O Manual v1.90 UL...
Page 97
Each SLC loop device on the system is assigned a unique address. In some cases an SLC loop device may have sub addresses as well. Using the Disable Address sub- menu command the user can individually disable any single address on the system. FireNET 4127 I & O Manual v1.90 UL...
The Test Zones sub-menu option is used by service personnel to quickly and easily perform periodic system tests. Please refer to Section 10 of this manual for a more detailed explanation. This feature is typically referred to as a “One Man Walk Test.” FireNET 4127 I & O Manual v1.90 UL...
• Output relays and circuits will operate performing fire alarm functions such as closing doors, recalling elevators, shutting down air handling equipment etc. • The panel buzzer will be pulsing. FireNET 4127 I & O Manual v1.90 UL...
The operations required following a trouble condition are as follows: • Press the “Panel Sounder Silence” button to silence the panel buzzer. (See section 7.3.1 for instructions on entering Access Level 2). FireNET 4127 I & O Manual v1.90 UL...
• If the supervisory condition cannot be resolved, contact your service company. • Once the supervisory condition has been cleared, reset the FN-4127 fire alarm control panel by entering Access Level 2 and pressing the “Reset” button. FireNET 4127 I & O Manual v1.90 UL...
• If the Pre-Alarm condition cannot be resolved, contact your service company. • Once the Pre-Alarm condition has been cleared, reset the FN-4127 fire alarm control panel by entering access level 2 and pressing the “reset” button. FireNET 4127 I & O Manual v1.90 UL...
(Access Level 3) 8.1 Access Level Overview The FireNET 4127 has 3 modes of operation. Access Levels 1 and 2 are operational levels that allow the user to perform operational commands such as silencing an alarm or resetting the panel. Access Levels 1 and 2 are explained in further detail in Section 7 - Basic Front Panel Operation and Programming.
Table 8.2.1 indicates these options. Table 8.2.1 Edit Configuration Menu Structure EDIT CONFIGURATION MENU ► EDIT SUPPLIERS NAME EDIT GENERAL ALARM MODE EDIT I/O ADD/DELETE DEVICE EDIT DEVICE ATTRIBUTES AUTO LEARN FireNET 4127 I & O Manual v1.90 UL...
Page 105
Terminal 12, which is 0V, and each input listed below. Please refer to Section 3.6 Digital Inputs for more detail on wiring & limitations of these inputs. • Trouble Input (Terminal 7) FireNET 4127 I & O Manual v1.90 UL...
Page 106
• Fire2 Contact (Terminals 23-25) • Supervisory Relay (Terminals 26-28) [Not User Programmable] • Auxiliary Relay (Terminals 29-31) • Fire Routing Voltage Output (Terminals 1 & 2) • Trouble Routing Voltage Output (Terminals 3 & 4) FireNET 4127 I & O Manual v1.90 UL...
Page 107
Cause and Effect. Edit Default Pattern “Edit Default Pattern” allows you to select the on-board NAC circuit output pattern. The available options are Continuous, Temporal and March. The default is Temporal. FireNET 4127 I & O Manual v1.90 UL...
Page 108
Press the right arrow key to select. 5. Press the “Enter” button to accept the new device. 6. Follow the prompts on screen or use the Help (?) button for further information. FireNET 4127 I & O Manual v1.90 UL...
Page 109
Day and night sensitivity times are configured in another menu location. o Set Input Action This option allows the user to change the detector’s (sensor) action type to Fire or Supervisory. FireNET 4127 I & O Manual v1.90 UL...
Page 110
Pattern (SOM and ASB only): This option allows the user to select the output pattern for the SOM module. Selections are Continuous, Temporal and March. Test Device Output: This option allows the output to be manually turned on or off by the user. FireNET 4127 I & O Manual v1.90 UL...
Page 111
Position, Power, General Supervision, General Purpose N/O EOL, General Purpose N/C EOL, General Purpose N/C no EOL, and Waterflow Non-Silence. The selected Input Type will appear as part of the message on the LCD display during device activation. FireNET 4127 I & O Manual v1.90 UL...
Default is 02:00. The time may be adjusted with the up/down arrow keys. The calibration time should be chosen based on an expected time of day when the environmental conditions in the building are stable. FireNET 4127 I & O Manual v1.90 UL...
Fire Drills, actually took place. The View Print Event Log menu option is covered in greater detail in Section 10 - Testing and Troubleshooting. FireNET 4127 I & O Manual v1.90 UL...
The following values must be set to be compliant with UL864 9 Edition. See prefix of this manual for additional details. • Buzzer – Enabled • Ground Trouble – Enabled • Buzzer Access Level - 2 FireNET 4127 I & O Manual v1.90 UL...
PRINT CONFIGURATION SYSTEM DISABLEMENTS ► LOOP DATA TEST Loop Data Test is an installer or service level diagnostic test that is explained in greater detail in Section 10 - Testing and Troubleshooting. FireNET 4127 I & O Manual v1.90 UL...
This section covers the use of the FireNET Loop Explorer software package. The FireNET 4127 is an extremely flexible and robust system that can grow modularly as the application requires. To take full advantage of the power and flexibility of the FireNET 4127 the Loop Explorer software must be used for programming the system.
9.3 Launching Loop Explorer Once FireNET Loop Explorer is installed to your PC’s hard drive, you can launch it from your Start Menu under Programs - Hochiki - FireNET Loop Explorer. Click the FireNET Loop Explorer icon to launch the program.
Page 118
Loop Explorer data not stored in the panel/network memory. Common practice should be to always use the source Loop Explorer project file and download to the panel/network. FireNET 4127 I & O Manual v1.90 UL...
Page 119
3. Upon customer verification, Hochiki will email the decrypted unlock code to the user. Upon receipt, open P.C. Connect. 4. In the Password window, click on the Enter Unlock Code.
Page 120
4. Click and select a device from the list to show the reading, and the calculated percentage of the Health. Press Save to create/save the Analog Values as an Excel spreadsheet file (*.csv). FireNET 4127 I & O Manual v1.90 UL...
Page 121
This is useful for seeing the real-time panel events being sent over the panel’s COM port. Press Save to create/save the Monitor Mode activity as a Word file (*.rtf). FireNET 4127 I & O Manual v1.90 UL...
There are several 3 party brands, types, and models available. They do not all perform the same and many have unique idiosyncrasies. Hochiki recommends the brand IO Gear model GUC232A unit or equivalent. 9.5 Getting Familiar with Loop Explorer...
All of the options at the top on the toolbar will become active or inactive according to what is selected in the Navigation tree and Device table. FireNET 4127 I & O Manual v1.90 UL...
Page 124
[+] or negative [ - ] boxes. To expand one level, click on the positive box next to the level you wish to expand. In figure 9.5, Hochiki Panel will be expanded. Click on the [+] box, and the level is expanded, revealing, it has two loops, and a local panel I/O (all panels have a local panel I/O).
View menu by clicking on Notes Toolbar . The Web view allows a user to connect to the Hochiki web site and access application and technical support services, as well as providing contact information for relevant questions.
Page 126
Create Loop Emulator File Allows the selected panel configuration to be exported as a *.hle file, which can be used with the Hochiki True Loop Emulator tool that will be released in the future. Export Loop Explorer Config Allows the selected panel network configuration to be exported as a *.lx2 file...
Page 127
• Fire Drill • Transparent In addition to these 11 predefined action messages you can add 9 custom action messages of your choosing. These custom messages can be up to 15 characters long. FireNET 4127 I & O Manual v1.90 UL...
Page 128
As a safeguard to inadvertently deleting an entire panel, Loop Explorer requires that all of the devices on the SLC loops be deleted before a panel can be removed from the configuration. FireNET 4127 I & O Manual v1.90 UL...
Page 129
The Where Used in C&E option will display the name of all Cause and Effect relationships assigned to the selected SLC or I/O device. This summary can help establish where and how an input or output is being used in your custom C&E programming. FireNET 4127 I & O Manual v1.90 UL...
Page 130
Loop Explorer. Clicking this menu option shows or hides the status bar. Bold Fonts When selected, the fonts are bolded in the Navigation Pane and the Device Table. FireNET 4127 I & O Manual v1.90 UL...
Page 131
Flash The flash memory that the FN-4127 panel firmware utilizes can easily be upgraded as Hochiki adds new features to the product in future releases. This menu option will open a new window that will allow you to “flash” upgrade the FN-4127 panel firmware. This utility should only be used under the direction of Hochiki America technical support by Hochiki certified service professionals.
9.5.3 Ma ain Tool B ar Icons hough Loop p Explorer u uses menu items, it als so uses Nav vigation Ico ons for thos tions that a are more fre equent. Allows you t to add anothe er Panel to yo our site.
Page 133
The Where Used in C&E option will di splay the nam Where Use ed in of all Cause and Effect re elationships a assigned to th C&E Summ mary selected SL C or I/O devic ce. This summ mary can help establish wh here and how w an input or o...
Establishes communicati on between t the FN-4127 a PC Conne the PC. The e Loop Explor er serial cable e must be installed bet tween the PC C and the FN-4 4127, and the COM port of f the PC must t be identified d to the Loop Explorer sof...
Page 135
Adds an addressable Conventional Zone Module to a Loop DIMM Adds an addressable Dual Input Module to a Loop Adds a Aux Powered Sounder to a device Adds an addressable AMS Pull-Station FireNET 4127 I & O Manual v1.90 UL...
Page 136
This will select all the text in the text box, ready for a change that will affect the entire text. Print- This will bring up the usual print dialog, from where it’s possible to select a printer, and print out the contents of the Notes. FireNET 4127 I & O Manual v1.90 UL...
Page 137
Hide Toolbar- Check this option to hide the toolbar, which attaches to the top of the Notes page. The toolbar has the same options as the Right click menu. FireNET 4127 I & O Manual v1.90 UL...
Save icon after changes are made. You will now be presented with a blank project with only Cause and Effect in your navigation tree, and the “Welcome to Loop Explorer” task pane. FireNET 4127 I & O Manual v1.90 UL...
1. Click on the Site name in the Navigation tree after creating a new site. 2. Click on Edit from either the right click menu or the toolbar. 3. Enter the desired site name (25 characters maximum). FireNET 4127 I & O Manual v1.90 UL...
5. An Application Options window (as shown) will appear, click on the Other tab. 6. Select the Autosave Current Project checkbox. 7. Select the appropriate Interval you wish the project to Autosave. FireNET 4127 I & O Manual v1.90 UL...
The FireNET 4127 control panel offers an extensive list of features and options for fire alarm control and monitoring that can be configured via Loop Explorer or the front panel controls.
4. You will see a Protocol Options window; select the panel you wish to use. NOTE: To select either a 2 Loop or a 4 Loop panel, select Hochiki America Panel . 5. You will immediately be asked to configure the panel using the Configure Panel Settings window.
Page 143
This option will offset all panel loops by the total of the previous loop count. This is typically used when more than one panel is installed in a network, so that the loop numbering will be sequential across several panels. FireNET 4127 I & O Manual v1.90 UL...
Page 144
If a Graphics system is connected to the panel, check this box (future feature). Panel Text Panel Text is text displayed on the panel when there are no events showing on the LCD. The panel text is limited to 40 alpha/numeric characters max. FireNET 4127 I & O Manual v1.90 UL...
Page 145
The AC Fail report delay time value can be set between 0 and 24 hours. Default value is one (1) hour. This value must be set between 1 and 3 hours to be compliant with UL864 9 Edition. (See the prefix of this manual for additional details). FireNET 4127 I & O Manual v1.90 UL...
Page 146
(both local and network wide), while other panels print only local events. Buzz This gives the option to operate the node (panel/network annunciator) buzzer upon receipt of a network event. FireNET 4127 I & O Manual v1.90 UL...
SLC loops or NAC pattern properties to edit. The numbers of loops, loop offset, and NAC pattern options are grayed out. NOTE : See Section 9.7.2 for the proper method to access the Configure Node. 9.7.4 Reserved for Future Use FireNET 4127 I & O Manual v1.90 UL...
If you try to delete a panel when it still has devices attached to it, you will see an error message telling you to delete all of the devices attached to the Loops before attempting to delete the panel. FireNET 4127 I & O Manual v1.90 UL...
(or node). 9.8.1.1 Adding a SLC Board An SLC Expander board adds an additional two Loops to a Hochiki 2 Loop Panel. Follow the steps below to add an SLC expander to a 2 loop panel - 1.
2. Click on the Delete button in the menu or the delete button from the right-click button. 3. You will be given a confirmation window. To complete the deletion, click the Yes button. To cancel, click the No button. FireNET 4127 I & O Manual v1.90 UL...
The item you initially select from the Navigation tree or Device Table will determine the configuration window that will appear. For example, the configuration window options for an FRCME input module will be different than those of an SOM module. FireNET 4127 I & O Manual v1.90 UL...
Page 152
A Supervisory alarm will produce the following response by the panel: • Supervisory Alarm LED • Continuous Buzzer • Supervisory Contact • Outputs (if flag set) • LCD Supervisory Alarm Message, Address And Location Text Of Input FireNET 4127 I & O Manual v1.90 UL...
Page 153
When an input designated as a disablement is operated, the panel will display the following: • General Disablement Indicator • Continuous Buzzer For 5 Seconds • Address (1-127) • Zone (1-500) • LCD Disablement Message, Address And Location Text Of Input FireNET 4127 I & O Manual v1.90 UL...
Page 154
Zones are also used to group devices into logical groups or per the building and code requirements. Note : Do not assign SLC loop outputs to zone 0. FireNET 4127 I & O Manual v1.90 UL...
Page 155
If the output is Silenceable, the stage two delay option becomes available. The stage two delays gives additional time from 0 to 5 minutes in half-minute steps before the output operates after the alarm is acknowledged during the stage one delay period. FireNET 4127 I & O Manual v1.90 UL...
Page 156
Each output can be given location text of up to 40 characters. As well as being useful in identifying devices and locations, the location text can be useful in identifying the device when compiling cause and effects programs. FireNET 4127 I & O Manual v1.90 UL...
3. You will see a confirmation window when you delete a device. It will have a list of all information that is attached to the device. Click Yes if you still want to delete it or click No to abort the deletion. FireNET 4127 I & O Manual v1.90 UL...
Alarm Verification operation, you must select the “Verify” check box for that zone. Alarm Verification only applies to photo and ion smoke sensors in that zone. For more information on using Zones, see section 9.13. 9.10.5 Reserved for Future Use FireNET 4127 I & O Manual v1.90 UL...
This gives the option to print the network event. It may be that a master panel is required to print all events and that other panels print only local events. Buzz This gives the option to operate the panel buzzer upon a network event from other panels. FireNET 4127 I & O Manual v1.90 UL...
• GENERAL TROUBLE LED • CONTINUOUS BUZZER • TROUBLE CONTACT • TROUBLE ROUTING OUTPUT • LCD TROUBLE MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT OR EVENT FireNET 4127 I & O Manual v1.90 UL...
• INITIALIZING A DEVICE • INITIALIZING A PANEL • AUTOLEARNING A PANEL • RE-CONFIGURE BY PC • SILENCE • RESOUND • RESET FireNET 4127 I & O Manual v1.90 UL...
Page 162
9.11.10.5 Network card not installed If a control panel is configured to be part of a network by Autolearn or Loop Explorer, and a network card is not installed, the panel will display this message. FireNET 4127 I & O Manual v1.90 UL...
Page 163
This mechanism has been put in place to enable a control panel to identify a new or unknown network event type differing than its own. FireNET 4127 I & O Manual v1.90 UL...
Number of Loops Number of Zones Calibration Time 07:00 Day of week Start Sunday 08:00 18:00 Monday 08:00 18:00 Tuesday 08:00 18:00 Wednesday 08:00 18:00 Thursday 08:00 18:00 Friday 08:00 18:00 Saturday 08:00 18:00 FireNET 4127 I & O Manual v1.90 UL...
Page 168
Panel - LCD Annun #3 Panel Text Shinagawa Hotel Project LCD #3 Network Address First Node Address Last Node Address Access 2 Code 22222 Access 3 Code 33333 Number of Loops Number of Zones FireNET 4127 I & O Manual v1.90 UL...
Page 169
Facp #2 - Loop 1 Address 003.02 Facp #2 - I/O Module 32 32 - Channel 12 Zone 10 Action : Fire Pump Startup Logic from Waterflow Cause (OR) Facp #2 - Loop 1 Address 005.01 Effect (Temporal) FireNET 4127 I & O Manual v1.90 UL...
Page 170
D = Day mode N = Night Mode S = Silenceable R = Resetable L = Latching O = Delayed Output F = Trouble A = PreAlarm Output B = Output Delay Bypass FireNET 4127 I & O Manual v1.90 UL...
500, spare zones can be used to good effect to simplify network wide cause and effects by using zones as groups and operating upon these rather than individual devices to achieve the required functionality. See Section 9.10.4 for additional details regarding programming zones. FireNET 4127 I & O Manual v1.90 UL...
A custom splash screen may be used in place of default one. A custom splash screen can only be a file up to 2Mb in size, so as not to increase the loading time of the application. FireNET 4127 I & O Manual v1.90 UL...
The Autosave feature is also enabled within this screen. Once enabled, you may also set the time interval in which the Autosave occurs. FireNET 4127 I & O Manual v1.90 UL...
This means that your C&E statements can operate across the network on any or all panels! You must also choose an Action Operator for a C&E. There are three types of action operators: • AND/All • OR/Single • Coincidence/Any Two FireNET 4127 I & O Manual v1.90 UL...
Page 175
If you want an output to activate ONLY from a C&E, be sure that General Alarm and all other options are not selected in the Output’s Properties. Otherwise your output may activate at unexpected times. FireNET 4127 I & O Manual v1.90 UL...
R2M at address 5 will do nothing UNLESS the alarm comes from one of the smoke detectors used in the C&E statement. In this case the panel will respond normally but one of the R2M relays will activate too. FireNET 4127 I & O Manual v1.90 UL...
Page 177
This option allows the manager to disable many detectors with relatively few key presses at the panel. As you can see from these examples, FireNET’s Cause and Effect statements open up many possibilities. FireNET 4127 I & O Manual v1.90 UL...
Use the up/down arrow keys to select ON or OFF. Setting this option to ON will activate SLC loop output devices such as SOM modules for audible and visual devices, but will not activate R2M modules. Turning this option to OFF disables the SOM modules during test mode. FireNET 4127 I & O Manual v1.90 UL...
To view the event log, you must first enter Access Level 3 (see section 8.1.1). Once in Access Log 3, select VIEW PRINT EVENT LOG. Then select “View Event Log”. VIEW/PRINT EVENT LOG MENU ► View Event Log Print Event Log Clear Event Log FireNET 4127 I & O Manual v1.90 UL...
Then select the Event Type Option SELECT EVENT TYPES TO PRINT ► Fire Pre-Alarm Trouble - 120 Disablements Other Events - 94 All Events - 218 Then press the Enter key to start printing those event types. FireNET 4127 I & O Manual v1.90 UL...
Then press the Enter key to clear the Event Log, or EXIT to cancel. CLEAR EVENT LOG MENU Event Log has 218 entries Press ENTER to clear Event Log. Press EXIT to quit Press < to go back. FireNET 4127 I & O Manual v1.90 UL...
SET TIMES VIEW PRINT EVENT LOG PRINT CONFIGURATION SYSTEM DISABLEMENTS ► LOOP DATA TEST Then select which Loop you wish to test. LOOP DATA TEST ► SELECT LOOP 1 SELECT LOOP 2 FireNET 4127 I & O Manual v1.90 UL...
Page 183
The Loop Data Test result will then display in real time on the screen. LOOP DATA TEST (LOOP: 2) Start Date : 9/05/2003 12:28:00 Good Readings: 0017824 Bad Readings: 0000000 Current Date: 9/05/2003 13:06:01 Press the Exit button when the Loop Data Test is completed. FireNET 4127 I & O Manual v1.90 UL...
From the Access Level 3 menu choose Edit Configuration then choose Edit I/O. Select Edit Panel I/O, then Edit Default Pattern. Use the up and down arrow keys to highlight the selected pattern, then press the Enter button. FireNET 4127 I & O Manual v1.90 UL...
Page 185
Configure Panel Settings window. You can also use the Battery Calculator spreadsheet software included on the Loop Explorer software CD. FireNET 4127 I & O Manual v1.90 UL...
In the near future, all of these tables are available in electronic format from the Hochiki America Corp. web site - www.hochiki.com. These installation records should be filled out for all installations and are useful in restoring the system configuration if the Loop Explorer backup file is missing or corrupt.
Page 187
Table 11.1 FireNET 4127 SLC Loop Point Record Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 188
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 189
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 190
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 191
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 192
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 193
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 194
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 195
Loop Address Zone Loop Address Zone Description Description (1-4) (Sub) (1-500) (1-4) (Sub) (1-500) FireNET 4127 I & O Manual v1.90 UL...
Page 196
Table 11.2 RS485 Bus Device Record Address Device Description Location (1-32) FireNET 4127 I & O Manual v1.90 UL...
Page 197
Table 11.3 Network Node Device Record Node Device Description Location (1-64) FireNET 4127 I & O Manual v1.90 UL...
Page 198
Node Device Description Location (1-64) These tables may be photocopied if additional pages are necessary. FireNET 4127 I & O Manual v1.90 UL...
Appendix A - Compatible Devices A.1 Two-Wire Smoke Detectors Table A.1 lists the 2-wire smoke detectors that are compatible with the CZM conventional zone module. Table A.1: Compatible 2-Wire Smoke Detectors with the Hochiki FireNET CZM Module Compatibility ID Number of Manufacturer...
A.1.1 Two-Wire Smoke Detectors BOSCH Table A.1.1 lists the 2-wire smoke detectors that are compatible with the CZM conventional zone module. Table A.1.1: Compatible 2-Wire Smoke Detectors with the Hochiki FireNET CZM Module Compatibility Number of ID Detector Base Detectors...
“ Special Application” by UL Laboratories. In this case specific device compatibility is not required. For these types of notification appliances the Hochiki 10K end of line resistor PN# 0400-01046 may be used in lieu of the end of line device PN# 0400- 01023 if desired.
Page 202
UL listing for that device. NOTE 3: The DCP-SOM-A and DCP-SOM-AI modules are suitable for use with Amseco/Potter notification appliances in both a Class A and Class B configuration with the Amseco/Potter sync module employed. FireNET 4127 I & O Manual v1.90 UL...
Page 203
UL listing for that device. NOTE 3: The DCP-SOM-A and DCP-SOM-AI modules are suitable for use with Cooper/Wheelock notification appliances in both a Class A and Class B configuration with the Cooper/Wheelock sync module employed. FireNET 4127 I & O Manual v1.90 UL...
Page 204
UL listing for that device. NOTE 3: The DCP-SOM-A and DCP-SOM-AI modules are suitable for use with Gentex notification appliances in both a Class A and Class B configuration with the Gentex sync module employed. FireNET 4127 I & O Manual v1.90 UL...
Page 205
Sensor notification appliances in a Class B configuration with the System Sensor sync module employed. The DCP-SOM-A and DCP-SOM-AI modules are NOT suitable for use with the System Sensor notification appliances when connected to the System Sensor sync module in a Class A configuration. FireNET 4127 I & O Manual v1.90 UL...
For proper operation use 24VDC polarized devices. When used on a supervised output or NAC, be sure to use with a Hochiki 10K end of line resistor PN# 0400-01046. When used on the AUX24VDC output the supervision resistor is not necessary.
For proper operation use 24VDC polarized devices. When used on a supervised output or NAC, be sure to use with a Hochiki 10K end of line resistor PN# 0400-01046. When used on the AUX24VDC output the supervision resistor is not necessary.
• Trouble Contact (Common Trouble) • Supervisory Output (Common Supervisory) • Trouble Input (Common Trouble) 3. The auxiliary contact connected to Bosch D9068 Dialer Input #1 is a spare and can be programmed for any function. FireNET 4127 I & O Manual v1.90 UL...
Page 210
Bosch D9068 dialer, use the following steps : 1. Program the onboard “Fire 2” relay for “AC Fail Delay” operation: Select AC Fail Delay when using the Bosch D9068 Dialer with FireNET. FireNET 4127 I & O Manual v1.89UL...
Page 211
• Trouble Contact (Common Trouble) • Supervisory Output (Common Supervisory) • Trouble Input (Common Trouble) 4. The auxiliary contact connected to Bosch D9068 Dialer Input #1 is a spare and can be programmed for any function. FireNET 4127 I & O Manual v1.89UL...
• AC Fail Delay = 0, 4 – 24 hours (does not comply with UL864 Ed. 9) Please see the beginning of this manual for a list of all program settings that can be adjusted outside compliance of the UL864 Edition 9 standard. FireNET 4127 I & O Manual v1.89UL...
Wiring Polarity Shown in Signaling Devices Alarm Condition. ISSUE NO. BF-8887 E.O.L. DEVICE PART NUMBER 0400-01046 10K OHM 1/4W All Wiring is Power Limited, Connect only to Power Limited Circuits. For Use Only With Supervised Circuits. FireNET 4127 I & O Manual v1.89UL...
A.7 Using the FNV-MP with FireNET When using the FNV-MP with FireNET panel, refer to below wiring diagram. Please reference the installation instructions of the FNV-5010 for all other connection details. FireNET 4127 I & O Manual v1.89UL...
WARNING – Do NOT apply 240 VAC to the FireNET control panel unless the power supply has been configured to operate at 240 volts! Doing so will damage the panel, requiring it to be returned to the factory for repair! FireNET 4127 I & O Manual v1.89UL...
10,000 Feet - Commercial Protected- Premises Control Unit for Local signaling. Install Indoors only in a dry The FireNET 4127 has been verified to comply with See FireNET Installation Manual as noted below environment. FCC Rules Part 15, Class A Operation is subject to the...
(3) year from date of original shipment. HOCHIKI will repair or replace, at its option, any equipment which it determines to contain defective material or workmanship. Said equipment must be shipped to HOCHIKI prepaid.
Need help?
Do you have a question about the FireNET 4127 and is the answer not in the manual?
Questions and answers