LG R410A Service Manual page 151

Multi v space system
Table of Contents

Advertisement

Error
Error Contents
Code
Low voltage / High
25
voltage
I Defect inspection method
1) Check whether the input power (3 phase = 380V-10% ~ 415+10% single phase = 220V-10% ~ 240+10%).
In case there is a deviation from the required power in each phase or is not the rated voltage, then please
request the building electricity in charge to supply the required power.
2) Check whether the Outdoor Unit PCB power input is 220V-10%, 240+10%.
Otherwise, Outdoor Unit line fuse be installed and required input voltage should be supplied.
3) In case the Outdoor Unit PCB power input is normal then replace the PCB.
Meaning
1.Input voltage in the instal-
lation region= 3 phase
380-10%, 415+10%
2. Single phase = 220-10%,
240+10%
Main Causes
1. Abnormality of the input voltage
2. Outdoor Unit main line fuse dam-
age
3. Outdoor Unit main PCB defect
Troubleshooting Guide
Error display
position
Concerned
Remote con-
troller
Panel Display
Outdoor unit
Service Manual 151

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arun seriesAruv seriesArnu series

Table of Contents