2.6 Other

Electrolytic capacitor and resistor for voltage distribution
Guide of check electrolytic capacitor and resistor for voltage distribution
1) Disconnect an terminal of voltage distribution resistor from each DC link
electrolytic capacitor
2) Set the multi meter to resistance mode, connect the probe to +,- terminal
of the capacitor. If the estimated resistance value is increase
continuously without short(value is 0), then the resistor is normal
3) Set the multi meter to resistance mode, confirm that the resistance value
of the resistor is around 270 kOhm
In case that the control box is opened and before checking electrical parts,
Caution
it should be checked that the LED 01Y turned off (wait 3 minutes after main power
OFF), otherwise it may cause electrical shock.
Check and replace inferior
components