How To Close The Terminal Compartment; Terminal Tightening Capacity; Equipotential Bonding System; Ex Ia / Ex Iad Equipment - Ametek DR6300 SERIES Supplementary Instructions Manual

Radar level instrument for 2-wire control systems (solids)
Hide thumbs Also See for DR6300 SERIES:
Table of Contents

Advertisement

ELECTRICAL CONNECTIONS
3

3.2.2 How to close the terminal compartment

WARNING!
If dirt collects on the terminal compartment gasket, clean it before you attach the terminal
compartment cover.
DANGER!
Ex d applications
Ex d applications
Ex d applications
Ex d applications
Make sure that the terminal compartment is correctly sealed. An explosion can cause death or
injury to personnel and/or damage to equipment. Obey the instructions that follow:
Ex d / Ex tD applications
• Attach the terminal compartment cover 2. Turn the terminal compartment cover carefully to
prevent damage to the thread and the gasket.
• Make sure that the terminal compartment cover is tight.
• Use a 3 mm Allen wrench to attach the cover stop 1.
• Make sure that the cover stop 1 screw is tight.

3.3 Terminal tightening capacity

The terminal tightening capacity for curent output terminals 1 and 2 is:
Type of wire

3.4 Equipotential bonding system

There is a terminal in the terminal compartment and another on the side of the converter
support pillar that can be used as equipotential bonding conductors.

3.5 Ex ia / Ex iaD equipment

3.5.1 How to connect the electrical cables

Cable entries are supplied on customer demand. If you supply the cable entries, this part must
have a degree of ingress protection IP≥6X (EN 60529).
• Use the electrical connection procedure in the Handbook.
• If possible, use galvanically-isolated equipment.
• Supply the Ex i / Ex iD equipment connected to the device. Use only certified intrinsically-safe
equipment.
• Connect only to separate certified, intrinsically-safe circuits. Make sure that the electrical
circuit characteristics are not more than the values that follow.
15
Rigid
Flexible
Terminal tightening capacity
[mm²]
www.drexelbrook.com
DR6300 SERIES
[AWG]
4
2.5
DR6300-LM ATEX, EDO 2-13-118, Issue 1
11
13