Process pressure measurement
pressure transmitter with ceramic and metal sensors
overload-resistant and function-monitored; communication via
hart, profibus pa or foundation fieldbus (96 pages)
Pressure transmitter with ceramic and metal sensors overload-resistant and function-monitored; communication via hart profibus pa or foundation fieldbus (84 pages)
Summary of Contents for Endress+Hauser Cerabar S PMC71
Page 1
Brief Operating Instructions Cerabar S PMC71, PMP71, PMP75 Pressure transmitter These are Brief Operating Instructions. For more detailed information, please refer to the Operating Instructions and the additional documentation on the CD-ROM provided. These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply.
Safety Instructions listed in this Ex document must be observed. The documentation number of the related Safety Instructions is also indicated on the additional nameplate. Return Follow the instructions on returning the device as outlined in the Operating Instructions on the CD-ROM provided. Endress+Hauser...
"zero" key on the electronic insert, or on the outside of the device or via the on-site display. → See Page 13, Section 4.2.1 "Position of operating elements", Page 14, Section 4.2.2 "Function of the operating elements" and Page 23, Section 5.1 "Position adjustment". Endress+Hauser...
• To ensure optimal readability of the on-site display, it is possible to rotate the housing up to 380°. • Endress+Hauser offers a mounting bracket for installing on pipes or walls. Installation instructions for devices without diaphragm seals PMP71, PMC71 Cerabar S without diaphragm seal are mounted as per the norms for a manometer (DIN EN 837-2).
• vibration-free (in order to avoid additional pressure fluctuations) • not in the vicinity of heating or cooling lines • insulate if the ambient temperature is below ore above the reference temperature • with a bending radius of ≥100 mm. Endress+Hauser...
Page 7
Cerabar S PROFIBUS PA Installation 2.3.1 Vacuum application For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter underneath the diaphragm seal. A vacuum load of the diaphragm seal caused by the presence of filling oil in the capillary is hereby prevented.
Mount the housing on a wall or pipe using the mounting bracket (item 7). When mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at least 5 Nm. Mount the cable with a bending radius (r) ≥ 120 mm. Endress+Hauser...
For devices with 7/8" or M12 plug see Operating Instructions. Housing Internal earth terminal External earth terminal Supply voltage, for version in non-hazardous area = 9...32 V DC Devices with integrated overvoltage protection are labelled OVP (overvoltage protection) here. Endress+Hauser...
Cerabar S must be earthed, for example by means of the external earth terminal. Different earthing and screening installation methods are available for PROFIBUS PA networks such as: • Isolated installation (see also IEC 61158-2) • Installation with multiple earthing • Capacitive installation Endress+Hauser...
Parameter Measured value display Identification Function name Value number Header line Main line Unit Information line Symbol – Bargraph Bargraph Editing modes Operating keys Selection options Value that can be edited Current measured value P01-xxxxxxxx-07-xx-xx-xx-011 Endress+Hauser...
Page 12
The primary value of the Transducer Block is increasing. Tendency symbol (decreasing) The primary value of the Transducer Block is decreasing. Tendency symbol (constant) The primary value of the Transducer Block has remained constant over the past few minutes. Endress+Hauser...
(zero point-correction) or total reset Operating key for position adjustment (zero point-correction) or total reset DIP switch for hardware address Slot for optional display ® Slot for optional HistoROM /M-DAT DIP-switch for locking/unlocking measured-value-relevant parameters DIP-switch for damping on/off Endress+Hauser...
Page 14
S D A 0 1 2 3 4 5 6 7 8 Address P01-xxxxxxxx-19-xx-xx-xx-109 – DIP-switch 1: for locking/unlocking measured-value-relevant parameters τ Factory setting: off (unlocked) – DIP switch 2: damping on/off Factory setting: on (damping on) P01-xxxxxxxx-19-xx-xx-xx-108 Endress+Hauser...
Page 15
Set address in the bus. → See also Page 19, Section 4.4 "Configuring the device S D A 0 address". 1 2 3 4 5 6 7 8 Address P01-xxxxxxxx-19-xx-xx-xx-109 – DIP-switch 1: for locking/unlocking measured-value-relevant parameters τ Factory setting: off (unlocked) – DIP-switch 2: damping on/off, Factory setting: on (damping on) P01-xxxxxxxx-19-xx-xx-xx-057 Endress+Hauser...
MEASURING MODE ➀ ➁ SETTINGS DISPLAY POSITION ADJUSTMENT BASIC SETUP EXTENDED SETUP POS. ZERO ADJUST ➂ ➃ POS. INPUT VALUE CALIB. OFFSET P01-xxxxxxxx-19-xx-xx-xx-145 Fig. 7: Structure of the operating menu 1. Selection level 2. Selection level Function groups Parameter Endress+Hauser...
Page 17
The on-site display shows the parameter to be changed. The value highlighted in black can be changed. The "s" unit is fixed and cannot be changed. P01-xxxxxxxx-19-xx-xx-xx-023 Press "+" or "–" to get to the editing mode. The first digit is highlighted in black. P01-xxxxxxxx-19-xx-xx-xx-027 Endress+Hauser...
Page 18
– You can get back to the editing mode with "+" or "–". P01-xxxxxxxx-19-xx-xx-xx-032 4.3.4 Taking pressure applied at device as value Example: performing position adjustment. On-site display Operation The bottom line on the on-site display displays the pressure present, here 3.9 mbar. P01-xxxxxxxx-19-xx-xx-xx-158 Endress+Hauser...
• The FieldCare operating program is delivered from the factory with the address 1. There are two ways of assigning the device address to Cerabar S: • Using a DP Class 2 master operating program, such as FieldCare or • On site using the DIP switches Endress+Hauser...
Page 20
Set DIP switch 8 (SW/HW) to "Off". Configure the address with DIP switches 1 to 7. You have to wait 10 seconds for a change in address to take effect. The device is restarted. DIP switch Weighting in Position "On" Weighting in Position "Off" Endress+Hauser...
Select INSERT PIN NO. parameter, Menu path: GROUP SELECTION → OPERATING MENU → OPERATION → INSERT PIN NO. To lock operation, enter "0" for this parameter. Unlocking operation Select INSERT PIN NO. parameter. To unlock operation, enter "2457" for the parameter. Endress+Hauser...
– The sensor range does not have to be exceeded for the measuring application. – Position adjustment has to be carried out that has to correct a large measured error as a result of the orientation of the device (e.g. devices with a diaphragm seal). Endress+Hauser...
To correct the MEASURED VALUE to 0.0 mbar, you must enter the value 2.2 here. (MEASURED VALUE = MEASURED VALUE – CALIB. OFFSET) – MEASURED VALUE (after entry for calib. offset) = 0.0 mbar Factory setting: Endress+Hauser...
DAMPING TIME Enter damping time (time constant τ). The damping affects the speed at which all subsequent elements, such as the on-site display, measured value and OUT value of the Analog Input Block react to a change in the pressure. Endress+Hauser...
Page 25
Press key for at least 3 seconds. → See Page 13, Section 4.2.1 "Position of operating elements". If the LED on the electronic insert lights up briefly, the pressure applied has been accepted for position adjustment. If the LED does not light up, the pressure applied was not accepted. Observe the input limits. Endress+Hauser...
1) – LEVEL SELECTION "Level Easy Pressure" FULL CALIB. and CALIBRATION MODE "Wet" – LEVEL SELECTION = "Level Standard", LEVEL MODE = "Linear" and DAMPING VALUE CALIBRATION MODE = "Wet" P01-PMx7xxxx-19-xx-xx-xx-051 Fig. 10: Quick Setup menu for the Level measuring mode Endress+Hauser...
Page 27
OUT value of the Analog Input Block react to a change in the pressure. – LEVEL SELECTION "Level Easy Pressure" and CALIBRATION MODE "Wet" – LEVEL SELECTION "Level Standard", LEVEL MODE "Linear" and CALIBRATION MODE "Wet" (Menu path for CALIBRATION MODE: GROUP SELECTION → OPERATING MENU → SETTINGS → BASIC SETTINGS) Endress+Hauser...
Page 28
Press key for at least 3 seconds. → See Page 13, Section 4.2.1 "Position of operating elements". If the LED on the electronic insert lights up briefly, the pressure applied has been accepted for position adjustment. If the LED does not light up, the pressure applied was not accepted. Observe the input limits. Endress+Hauser...
Page 29
Cerabar S PROFIBUS PA Commissioning Endress+Hauser...
Page 30
Commissioning Cerabar S PROFIBUS PA Endress+Hauser...
Page 31
Cerabar S PROFIBUS PA Commissioning Endress+Hauser...