Sharp AY-XP08CE Service Manual page 28

Split type room air conditioners
Hide thumbs Also See for AY-XP08CE:
Table of Contents

Advertisement

AY-XP08/10/13CE
AE-X08/10BE-C
AE-X13BE
Function
NO
7
Compressor
Lowers the operating frequency if the
overheating
temperature of the compressor chamber
control
thermistor (TH1) rises above 105°C or
101°C.
Stops the compressor if the thermistor
stays above 105°C or 101°C for 1 minutes
at minimum frequency or less.
8
Compressor
Stops the compressor if the compressor
high
chamber thermistor is above 114°C.
temperature
(Or when TH1 shorts)
error
9
Outdoor heat
Lowers the operating frequency if the
exchanger
temperature of the outdoor heat exchanger
overheating
rises above 56°C during cooling. Stops the
control
compressor if the temperature stays above
56°C for 1 minute at minumum frequency.
10
Outdoor
Stops the compressor if an outdoor
thermistor
thermistor (excluding TH1) shorts.
short
11
Outdoor
Stops the compressor if the circuit of an
thermistor
outdoor thermistor breaks.
open
12
AC abnormal
Stops the compressor if if the operating
frequency is above 70 Hz and the
current error
compressor current is below 1.0 A.
13
Serial signal
Turns the compressor relay off if the indoor
error
unit does not receive a serial signal from
the outdoor unit for 8 minutes.
Stops the compressor if the outdoor unit
does not receive a serial signal from the
indoor unit for 30 seconds.
14
Power factor
When an power factor module error input
module
is detected.
(Active filter)
error
Operation
Description
During
compressor
operation
During
operation
During
compressor
operation
When
compressor is
activated
When
compressor is
activated
During
compressor
operation
During
operation
During
operation
During
compressor
operation
28
Detection
Restart
time
condition
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts when
thermistor (TH1)
temperature falls
below 100°C
(approximately 30
minutes)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts less than 8
minutes after
operation stops
Restarts after
reception of serial
signal
Automatically
restarts after safety
time (170 seconds)
Self diagnostic
display
Restart
Indoor Outdoor
times
No limit
No
No
4 times
Yes
Yes
No limit
No
No
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes
No limit
Yes
No limit
Yes
4 times
Yes
Yes