4. Select the device to import from the drop-down list. You can preview the configur-
ation on the right.
5. Click Import.
The new preconfigured objects appear in the object tree. If the configuration file is large,
the import may take time. To import a configuration file for a different device, right-
click the device, select SCL Import again and repeat the steps above.
For more information about the SCL Import function, see COM600 User's Manual.

Adding Logical Device objects

To add a Logical Device object:
1. Select an External OPC IED object and right-click it.
2. Select New > New or New > Communication > External OPC LD.
Each External OPC IED must have at least one Logical Device
object as a child object.

Adding Logical Node objects

To add a Logical Node:
1. Select a Logical Device object and right-click it.
2. Add a Logical Node object.
3. Rename the new object. The names of the Logical Node objects have to be unique.
You should have only one Logical Node 0 (LLN0) as a child
object to a Logical Device object.

Adding data objects

To add a data object:
1. Select a Logical Node object and right-click it.
2. Add a data object.
3. Rename the new object. The names of the data objects have to be unique. However,
you can have a data object with same name under a different Logical Node.

OPC Browser tool

The OPC Browser tool is a standalone software that can be used to read and save the
OPC namespace of the external OPC Server that is connected to COM600. The saved