Unitary products group PS9*UP Installation Manual

High efficiency tubular heat exchanger series
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL

HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: PS9*UP / FC9S*UP / FL9S*UP
(Single Stage Upflow)
40 - 135 MBH INPUT
(11.7 - 39.6 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TWINNING AND STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Thermostat Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Typical Twinned Furnace Application . . . . . . . . . . . . . . . . . . . . . . . . 11
Single Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . 12
Two-Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Termination Configuration - 1 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Termination Configuration - 2 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 5
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Recommended Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical and Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Maximum Equivalent Pipe Length . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Equivalent Length of Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Elbow Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . . . . . . . . . .13
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
LIST OF FIGURES
Termination Configuration - 2 Pipe Basement . . . . . . . . . . . . . . . . . .16
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .18
Condensate Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Pressure Switch Tube Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
LIST OF TABLES
(All Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Free Area - Outdoor Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Blower Performance CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Field Installed Accessories - Non Electrical . . . . . . . . . . . . . . . . . . . .27
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
269436-UIM-A-0407

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PS9*UP and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group PS9*UP

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY TUBULAR HEAT EXCHANGER SERIES RATING CERTIFIED MODELS: PS9*UP / FC9S*UP / FL9S*UP (Single Stage Upflow) ISO 9001 Certified Quality 40 - 135 MBH INPUT Management System (11.7 - 39.6 KW) INPUT LIST OF SECTIONS SAFETY ..........1 COMBUSTION AIR AND VENT SYSTEM .
  • Page 2: Safety

    • Refer to the unit rating plate for the furnace model number, and then see the dimensions page of this instruction for return air ple- num dimensions in Figure 1. The plenum must be installed according to the instructions. Unitary Products Group...
  • Page 3 248 CMR 5.08(2)(a)1 through 4. installed so the burner(s) and the ignition source are located not less than 18 inches (46 cm) above the floor, and the furnace must be located or protected to avoid physical damage by vehicles. Unitary Products Group...
  • Page 4: Ductwork

    If the ducts are undersized, the result will be high duct static pres- sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death. Unitary Products Group...
  • Page 5: Minimum Duct Sizing For Proper Airflow

    To properly design the ductwork for the build- ing, Refer to the ASHRAE Fundamentals Handbook, Chapter on “DUCT DESIGN” or a company that specializes in Residential and Mod- ular Home duct designs. Unitary Products Group...
  • Page 6: Filters

    The furnace base is equipped with a rectangular blockoff panel that can Filters must be installed external to the furnace cabinet. DO NOT be removed by performing the following steps: attempt to install filters inside the furnace. Unitary Products Group...
  • Page 7: Gas Piping

    PRESSURE ADJUSTMENT ON/OFF SWITCH PORT side of the furnace casing. To line up with the opening in the right side (Shown in ON position) of the casing, two street ells should be used. FIGURE 2: Gas Valve Unitary Products Group...
  • Page 8: Electrical Power

    Field wiring to the unit must be grounded. Electric wires that are field Use copper conductors only. installed shall conform to the temperature limitation for 63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 6 in these instructions for specific furnace electrical data. Unitary Products Group...
  • Page 9: Electrical Wiring

    Green Wire. Connect the power supply as shown on the unit-wir- air conditioning unit contactor. ing label on the inside of the blower compartment door or Figure 4. The black furnace lead must be connected to the L1 (hot) wire Unitary Products Group...
  • Page 10: Thermostat Chart

    269436-UIM-A-0407 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. FIGURE 5: Thermostat Chart Unitary Products Group...
  • Page 11: Twinning And Staging

    When one duct system is used for two furnaces, it is necessary that the two blowers operate in unison. The twinning function of the board in this furnace ensures that both blowers turn on and off simultaneously, and operate on the same blower speed. Unitary Products Group...
  • Page 12: Single Stage Twinning Wiring Diagram

    The twinning func- tion of this board ensures that both blowers turn on and off simulta- neously, and operate on the same blower speed. Even when only one furnace is supplying heat, both furnace blowers must run. Unitary Products Group...
  • Page 13: Maximum Equivalent Pipe Length

    ABS pipe is to be used, any joint where ABS pipe is joined to PVC pipe must be glued with cement that is approved for use with BOTH materials. Metallic materials must not be used for venting or air intake. Unitary Products Group...
  • Page 14: Dimensions

    IMPORTANT: Accessory concentric vent / intake termination kits 1CT0302 and 1CT0303 are available and approved for use with these furnaces. Horizontal sidewall vent terminations kits 1HT0901 & 1HT0902 are also approved for use with these furnaces. Unitary Products Group...
  • Page 15: Home Layout

    Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer. Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent. Unitary Products Group...
  • Page 16: Termination Configuration - 1 Pipe

    Under NO circumstances can the two combus- ANTICIPATED SNOW tion air or vent pipes be tied together. The combustion air and vent LEVEL OR GRADE, WHICHEVER IS pipes must terminate in the same atmospheric zone. HIGHER FIGURE 13: Termination Configuration - 2 Pipe Unitary Products Group...
  • Page 17: Double Horizontal Sealed Combustion Air And Vent Termination

    Refer to Figure 20 for attic BE CLAMPED INTO and crawl space termination. Only the combustion air intake may OUTLET OF DRAIN terminate in the attic. The vent must terminate outside. COUPLING FIGURE 18: Combustion Airflow Path Through The Furnace Casing Unitary Products Group...
  • Page 18: Outside And Ambient Combustion Air

    4. The blocking effects of louvers, grilles and screens must be given AIR (b) AIR (a) consideration in calculating free area. If the free area of a specific louver aor grille is not known. FIGURE 19: Outside and Ambient Combustion Air Unitary Products Group...
  • Page 19: Condensate Piping

    IMPORTANT: Condensate must be disposed of properly. Follow local plumbing or wastewater codes. The drain line must maintain a 1/4" per foot (0.635 cm per meter) slope to the drain. Unitary Products Group...
  • Page 20: Safety Controls

    The operation of this control indicates a malfunction in the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. These are manual reset controls that must be reset before operation can continue. Unitary Products Group...
  • Page 21 Calculate the furnace input by using one of the following equa- The induced draft blower motor will start and come up to tions. speed. Shortly after inducer start-up, the hot surface igniter will glow for about 17 seconds. Unitary Products Group...
  • Page 22 If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifices with the gas orifices of the proper size for the type of gas you are using. Unitary Products Group...
  • Page 23: Gas Valve

    The gasket and may stick in place. Connect the positive side of the manometer to the gas valve as described in E above. There will be no second connection to the manometer, as it will reference atmo- spheric pressure. Refer to Figure 24 for connection details. Unitary Products Group...
  • Page 24: Reading Gas Pressure

    TWIN CONTINUOUS PARK FAN SPEED RED-LOW PARK JUMPER LO COOL YELLOW-MED. LOW HI COOL FAN OFF BLACK-HI ADJUSTMENT HEAT BLUE-MED. HI JUMPER EAC-H XFMR FIGURE 25: Furnace Control Board Unitary Products Group...
  • Page 25 8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure or faulty gas valve. The furnace will lock out for one hour and then restart. Unitary Products Group...
  • Page 26: Blower Performance Cfm

    1501 - 1750 42.49 - 49.55 2452 0.15 0.03736 0.14 0.03487 0.30 0.07473 1751 - 2000 49.56 - 56.63 2542 0.19 0.04733 0.18 0.04484 0.30 0.07473 2001 & Above 56.64 - Above 2987 0.19 0.04733 0.18 0.04484 0.30 0.07473 Unitary Products Group...
  • Page 27: Field Installed Accessories - Non Electrical

    17-1/2” CABINETS 1BR0121 BOTTOM RETURN FILTER KIT 1” FILTER 21” CABINETS 1BR0221 BOTTOM RETURN FILTER KIT 1-4” FILTER 21” CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1” FILTER 24-1/2” CABINETS 1BR0224 BOTTOM RETURN FILTER KIT 1-4” FILTER 24-1/2” CABINETS Unitary Products Group...
  • Page 28: Wiring Diagram

    SECTION XI: WIRING DIAGRAM FIGURE 26: Wiring Diagram Subject to change without notice. Printed in U.S.A. 269436-UIM-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 167484-UIM-C-0806 Unitary 5005 Norman Product York Group Drive 73069...

This manual is also suitable for:

Fc9s*upFl9s*up

Table of Contents