Opening for input and output cable connections LP33 Series 20 & 30
44mm
Ø 0.75"
Ø19.05mm
ANCHOR LOCATIONS
Fig. 4.4-2 Opening on the bottom of the cabinet for input and output cables
LP33 Series 20 & 30 opening is provided on the bottom of the UPS for the connection of input and
output cables.
Pay attention to the position of this opening, when choosing the placement of the UPS.
The UPS cabinet is free standing and normally does not require to be bolted to the floor.
The UPS cabinet can be fixed however to the floor by bolting it to the floor with provided seismic
brackets in the anchor locations show.
Positioning of the UPS cabinet
Fig. 4.4-3 Bolts for stabilizing the cabinet
Modifications reserved
GE_UPS_ISG_LPS_3UL_20K_30K_2US_V010.docx
1.73"
20.16"
512mm
9.50"
241.3mm
ANCHOR LOCATIONS
BOTTOM CABLE ENTRY
AREA 100 SQ IN (64500 SQ mm
Front
2.00"
50.8mm
18.0"
457.2mm
Critical Power
4.25"
107.9mm
4X LIVELLING FEET
2.00"
50.8mm
2.81"
71.4mm
LP33 Series 20 & 30 is equipped with wheels for
easy placement of the UPS.
To make the UPS movable on wheels, the bolts
on each leg of the cabinet have to be turned
counter-clockwise, until they are free from the
floor and thus the cabinet supported on wheels.
After having positioned the UPS at its final
location, the cabinet has to be secured by
rotating the bolts on each leg clockwise, but the
wheels must still touch the floor.
Ø 0.75"
Ø19.05mm
ANCHOR LOCATIONS
Installation Guide LP33 Series 20 & 30 UL S2
Page 16/43