GE GTD42GASJ0WW Installation Instruction page 13

Table of Contents

Advertisement

Available languages

Available languages

Installation
Instructions
(
• DO cut duct as short
as possible and install
straight
into wall.
DO use elbows when
turns are necessary.
Elbows
,DO NOT bend
or collapse
ducting. Use
elbows if turns
ore necessary.
@
,, DO NOT use
excessive
exhaust
length. Cut
duct us short
us possible.
• DO NOT
_,DO
NOT
crush duct
_}?"X,"
set dryer
against the
sx
rU I on duct.
wall.
_'
EXHAUST LENGTH
Using exhaust longer than specified
length will:
Increase the drying times and the energy cost.
Reduce the dryer life.
Accumulate
lint, creating a potential fire
hazard.
The correct
exhaust
installation
is YOUR
RESPONSIBILITY,
Problems
due to incorrect
installation
are not
covered
by the warranty.
The HAXIHUH ALLOWABLE length of the exhaust
system depends upon the type of duct, number of
turns, the type of exhaust hood (wall cap) and all
conditions
noted on the chart.
, Internal elbows added for side or bottom vent
conversions must be included in the total elbow
count.
, Any elbow greater than 45 ° should be treated as
a 90 ° elbow.
, Two 45 ° elbows will be treated like one 90 ° elbow.
, For every additional
90 ° elbow, reduce the
allowable
vent system length by 10 feet.
, When calculating
the total vent system length,
you must add all the straight
portions and
elbows of the system (including the transition
duct).
EXHAUST LENGTH
RECOMMENDEDMAXIMUM LENGTH
Exhaust Hood Types
Recommended
Use only for short
run installations
4" DIA.
___
2-1/2"
No. of 90°
Elbows
0
1
2
3
4
5
Rigid
Metal
120 Feet
100 Feet
85 Feet
70 Feet
60 Feet
55 Feet
Rigid
Metal
90 Feet
75 Feet
65 Feet
55 Feet
45 Feet
55 Feet
13