Setting Up The Com600 Computer; Accessing The Com600 Computer - ABB COM600 series User Manual

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS756125
5.5.
5.5.1.
COM600 series, version 4.1
User's Manual
To convert a project:
1. Open the old project in the new SAB600. The conversion wizard is launched auto-
matically. Follow the wizard instructions.
2. If the conversion wizard was canceled, you can run the conversion by right-clicking
on the Gateway object and selecting Convert project. Follow the wizard instructions.
3. Check the Gateway object properties to see if the COM600 version is the latest
version to confirm the conversion.
You can use SAB600 4.1 only to configure COM600 version
4.1.

Setting up the COM600 computer

Accessing the COM600 computer

Local and Remote LAN ports
The COM600 computer has by default two LAN ports, a local port (LAN 1) and a remote
port (LAN 2), see Figure 4.1-1.
There are two firewall profiles: Private (home and work) and Public. The Private profile
is intended for a local substation LAN with substation protocols and SAB600 configur-
ation allowed. The Public profile is intended for remote LAN connection.
You cannot pre-configure a specific profile for a specific network adapter. Therefore,
you must select the correct profile when configuring COM600 and connecting it to the
network. The operating system tries to identify the connected network based on the
configured default gateway. If the default gateway is found, you can select the firewall
profile to be used for the network in Control Panel > Network and Sharing Center.
If no default gateway is configured or found, the network is considered unidentified. For
unidentified networks the firewall profile is selected based on the local security policy
settings. By default unidentified networks use the Public firewall profile. All unidentified
networks use the same profile.
To change the profile used for unidentified networks:
1. Select Control Panel > Administrative Tools > Local Security Policy.
2. Browse to Network List Manager Policies and modify the Location type in the
Unidentified Networks properties.
For more information about firewall configuration, see Microsoft Windows 7 Firewall
documentation.