Outdoor Clearance
If the condensing unit is operated in an atmosphere containing oils (including machine
oils), salt (coastal area), sulphide gas (near hot spring, oil refi nery plant), such as
• Where a wall or order obstacle is in the path of outdoor unit's intake or exhaust airfl ow, follow the
installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Model: RK25/35FXV19, RXN25/35FXV1
Wall facing one side
More than 50
More than 100
1200 or
less
Side View
Model: RK50/60CXV19, RXN50/60CXV1
A
AIR INLET
ALL MODELS
Minimum Distance
substances may lead to failure of the unit.
Wall facing two side
More than 50
Wall facing three side
More than 50
B
AIR DISCHARGE
A
300 mm
More than 150
More
than 100
Top View
More than 150
More than 300
Top View
C
SERVICE SPACE
AIR INLET
B
C
1000 mm
300 mm
Application Information
More than 50
Unit : mm
D
D
500 mm
7