ARNING
Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code
NFPA70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
The information contained in the manual is intended for use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test instruments
Installation or repairs made by unqualified persons can result in hazards to you and others.
Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage,
personal injury and/or death.
KWIM Series
P
Service Manual
ulti zone Indoor

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KWIM09-H2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Klimaire KWIM09-H2

  • Page 1: Table Of Contents

    KWIM Series Service Manual ulti zone Indoor I N D O O odel Numbers: KWIM09-H2 KWIM12-H2 KWIM18-H2 Table of Contents Precaution Product Description And Label Dimension of indoor unit Operation Characteristics Electronic function iring Diagrams Trouble Shooting Disassembly instructions Exploded view...
  • Page 2 CONTENTS Precaution ............................2 1.1 Safety Precaution ........................2 1.2 Warning ............................2 Product Description And Label ......................6 Dimension of indoor unit ........................7 Operation Characteristics........................8 Electronic Function ..........................8 5.1 Abbreviation ............................8 5.2Main Protection ..........................8 5.3 Operation Modes and Functions ......................
  • Page 3: Precaution

    1. Precaution 1.1 Safety Precaution Improper wiring or installation may cause fore or electric shock. To prevent injury to the user or Use the correctly rated breaker of other people and property damage, fuse. the following instructions must be Do not modify or extend the power followed.
  • Page 4 Take care to ensure that the power (flooded submerged), cable could not be disconnected or discontinue immediately, damaged during operation. disconnect the power supply and Do not place anything on the contact authorized repair power cable. technician or installer. Do not unplug the power supply Turn the main power off when plug during operation.
  • Page 5 cause product malfunction failure of product. inefficient operation. Always insert the filter securely. Clean the filter every two weeks or more often if necessary. Operational A dirty filter reduces the efficiency Do not expose the skin directly to of the air conditioner and could cool air for long periods of time.
  • Page 6 If the liquid from the batteries gets leaked. onto your skin or clothes, wash it The chemical in batteries could well with clean water. Do not use cause burns other health the remote of the batteries have hazards...
  • Page 7: Product Description And Label

    2. Product Description And Label...
  • Page 8: Dimension Of Indoor Unit

    3. Dimension of indoor unit (mm(in)) D(mm(in)) H(mm(in)) Dimension 795(31.3) 165(6.5) 270(10.63) 845(33.27) 165 6.5) 286(11.26) 995(39.17) 194(7.64) 295(11.61) Model Dimension of installation hole KWIM09-H2 186mm 150mm 45mm (7.32in) (5.91in) (1.77in) KWIM12-H2 Φ65mm(2.56in) 138.5mm 150mm 45mm KWIM18-H2 (5.45in) (5.91in) (1.77in)
  • Page 9: Operation Characteristics

    ----When Indoor Fan Speed keeps too low or too 4. Operation Characteristics high for certain time, the unit will stop and the Temperature Cooling Heating Drying Mode operation operation operation LED will display the failure Room temperature 62 ~90 32 ~86 62 ~90 32 ~122 5.2.3 Indoor fan delayed open function...
  • Page 10 5.3.2 Cooling Mode Setting 5.3.2.1 Indoor fan running rules In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. Breeze TEL1 Super Auto fan in cooling mode acts as follow: Breeze TEL0 For 18K...
  • Page 11 5.3.5.1 Indoor fan speed is fixed at breeze and If T2>63℃, the indoor unit has no capacity can’t be changed. The louver angle is the same demand and resume till 48℃. as in cooling mode. 5.3.4 Auto-mode 5.3.5.2 Overlow room temperature protection This mode can be chosen by remote controller In dehumidifier mode, if room temperature is and the setting temperature can be changed...
  • Page 12 The indoor fan runs as breeze. After running for 5.3.7.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, 30 minutes, AC will turn to auto mode with 24℃ and then turn on automatically when reaching the setting temperature.
  • Page 13 timing is less than 7 hours, sleep function will be anti-cold-wind being released, Ionizer will be available again. cancelled when reaching the setting time. If the timing is more than 7 hours, the machine will not stop until reaches the setting time in sleep mode. 5.3.9 Auto-Restart function The indoor unit is equipped with auto-restart function, which is carried out through an auto-...
  • Page 14: Iring Diagrams

    Diagrams KWIM09-H2, KWIM12-H2, KWIM18-H2...
  • Page 15: Troubleshooting

    7. Troubleshooting 7.1 Display Function TIMER display Illuminated during Timer operation. CLEAN AIR display(optional) Illuminated when Ionizer is activated. TURBO operation display Illuminated when select TURBO function in cooling operation or in heating operation. DIGITAL DISPLAY Displayed the current setting temperature or malfunction code when the air conditioner is in operation.
  • Page 16: Indoor Unit Error Display

    7.2Indoor Unit Error Display Display Failure Indoor EEPROM malfunction Indoor/ outdoor units communication error Zero-crossing signal error Indoor fan speed has been out of control Open circuit or short circuit of outdoor temperature sensor or outdoor EEPROM malfunction Open circuit or short circuit of T1 or T2 temperature sensor IPM module protection or IGBT over-strong current protection Voltage protection Temperature protection of compressor top...
  • Page 17: Outdoor Unit Error Display

    7.3 Outdoor Unit Error Display For KSIM20912-H216 - 2G, KSIM30912-H216 - 1G, KSIM330-H219, KSIM40912-H216 - 2G Display LED STATUS Error Error (KWIL / KWIM) (KDIM Outdoor EEPROM malfunction Indoor / outdoor units communication error —— —— Communication malfunction between IPM board and outdoor main board Open or short circuit of outdoor temperature sensor(T3 T4 T5 T2B) Voltage protection PFC module protection(Only for KSIM40912-H216 - 2G)
  • Page 18 For M2OC-18HRDN1-M, M3OC-27HRDN1-M, KSIM40912-H216 - 1G Display Error LED STATUS Error digital tube KDIM (KWIL / KWIM) Outdoor EEPROM malfunction —— —— No A Indoor unit coil outlet temp. sensor or connector of sensor is defective —— —— No B Indoor unit coil outlet temp. sensor or connector of sensor is defective ——...
  • Page 19: Diagnosis And Solution

    7.4 Diagnosis and Solution 7.4.1 Indoor unit trouble shooting 7.4.1.1 E0( Indoor EEPROM malfunction ) error diagnosis and solution Error Code Malfunction decision PCB main chip does not receive feedback from EEPROM chip conditions Supposed causes Installation mistake PCB faulty Trouble shooting: EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage.
  • Page 20 7.4.1.2 E1(Communication malfunction between indoor and outdoor units) error diagnosis and solution. Error Code Malfunction decision Indoor unit does not receive the feedback from outdoor unit conditions during 120 seconds. Supposed causes Wiring mistake Indoor or outdoor PCB faulty Trouble shooting:...
  • Page 22 Pic 1:Use a multimeter to test the DC voltage between L2 port and S port of outdoor unit. The red pin of multimeter connects with L2 port while the black pin is for S port. When AC is normal running, the voltage will move alternately between positive value and negative value.
  • Page 23 PIC3 :Main board LED when power on and unit standby. PIC 4: Check point button, press 1 time for check how many indoor units are connected.(for KSIM20912-H216 - 2G,KSIM30912-H216 - 1G,KSIM330-H219,KSIM40912-H216 - 2G) Check point button, press 18 times for check how many indoor units are connected.(for KSIM20912- H216 - 1G, KSIM30912-H216 - 1G, KSIM40912- H216 - 1G)
  • Page 24 7.4.1.3 E2(zero-crossing signal error) diagnosis and solution. Error Code Malfunction decision When PCB does not receive zero crossing signal feedback for conditions 4 minutes or the zero crossing signal time interval is abnormal. Supposed causes Connection mistake PCB faulty Trouble shooting:...
  • Page 25 7.4.1.4 E3(indoor fan speed has been out of control) diagnosis and solution. Error Code Malfunction decision When indoor fan speed keeps too low (300RPM) for certain time, the unit conditions will stop and the LED will display the failure. Supposed causes Wiring mistake Fan ass’y faulty Fan motor faulty...
  • Page 26 Index 1: 1: Indoor AC fan motor Power on and set the unit running in fan mode at high fan speed. After running for 15 seconds, measure the voltage of pin1 and pin2. If the value of the voltage is less than 100V(208~240V power supply)or 50V(115V power supply), the PCB must have problems and need to be replaced.
  • Page 27 7.4.1.5 E5(open or short circuit of outdoor temperature sensor) diagnosis and solution E6 (open or short circuit of room or indoor temperature sensor) diagnosis and solution. Error Code E5/E6 Malfunction decision If the sampling voltage is lower than 0.06V or higher than conditions 4.94V, the LED will display the failure.
  • Page 28 7.4.1.6 P0(IPM module or IGBT over-strong current protection) diagnosis and solution. Error Code Malfunction decision When the voltage signal that IPM send to compressor drive conditions chip is abnormal, the display LED will show “P6” and AC will turn off. Supposed causes Wiring mistake IPM malfunction...
  • Page 30 7.4.1.7 P1(over voltage or too low voltage protection) diagnosis and solution.
  • Page 31 7.4.1.8 P2( temperature protection of compressor top) diagnosis and solution. Error Code Malfunction decision If the sampling voltage is not 5V, the LED will display the conditions failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty 7.4.1.9 P4 Inverter compressor drive error diagnosis and solution The trouble shooting is same with one of IPM module protection(P0).
  • Page 32 7.4.1.10 P5: Mode conflict. Error Code Malfunction decision The indoor units cannot work cooling mode and heating at same time. conditions Heating mode has a priority. Unit action Suppose Indoor unit A working in cooling mode or fan mode, and indoor unit B is set to heating mode, then A will change to off and B will work in heating mode.
  • Page 33 KSIM20912-H216 - 2G, KSIM218-H221,KSIM30912-H216 7.4.2 Outdoor unit trouble shooting (For - 1G, KSIM330-H219, KSIM40912-H216 - 2G 7.4.2.1 E0(Outdoor EEPROM malfunction) error diagnosis and solution Error Code Malfunction decision PCB main chip does not receive feedback from EEPROM chip conditions Supposed causes Installation mistake PCB faulty Trouble shooting:...
  • Page 34 7.4.2.2 E2(Communication malfunction between indoor and outdoor units) error diagnosis and solution. Error Code Malfunction decision Indoor unit does not receive the feedback from outdoor unit conditions during 120 seconds or outdoor unit does not receive the feedback from any one indoor unit during 180 seconds. Supposed causes Wiring mistake Indoor or outdoor PCB faulty...
  • Page 36 Pic 1:Use a multimeter to test the DC voltage between L2 port and S port of outdoor unit. The red pin of multimeter connects with L2 port while the black pin is for S port. When AC is normal running, the voltage will move alternately between positive value and negative value.
  • Page 37 Pic 2: :IPM (For qua-zone) Power, Self-Check Operating PIC3 :Main board LED when power on and unit standby. PIC 4: Check point button, press 1 time for check how many indoor units are connected.
  • Page 38 7.4.2.3 E3(Communication malfunction between IPM board and outdoor main board) error diagnosis and Error Code Malfunction decision PCB main chip does not receive feedback from IPM module conditions during 60 seconds. Supposed causes Wiring mistake PCB faulty Trouble shooting:...
  • Page 39 Remark: Use a multimeter to test the DC voltage between black pin and white pin of signal wire The normal value should be around 5V. Use a multimeter to test the DC voltage between black pin and red pin of signal wire. The normal value should be around 12V.
  • Page 40 7.4.2.4E4(open or short circuit of outdoor temperature sensor) diagnosis and solution F1/F2/F3/F4/F5 (open or short circuit of indoor coil temperature sensor) diagnosis and solution. Error Code E4/F1/F2/F3/F4/F5 Malfunction decision If the sampling voltage is lower than 0.06V or higher than conditions 4.94V, the LED will display the failure.
  • Page 41 7.4.2.5 E5(Voltage protection) error diagnosis and solution. Error Code Malfunction decision An abnormal voltage rise or drop is detected by checking the conditions specified voltage detection circuit. Supposed causes Power supply problems. System leakage or block PCB faulty Trouble shooting:...
  • Page 42 IPM (for dual/tri- zone) IPM (for qua- zone) P-N (for dual/tri-zone)
  • Page 43 P-N (for qua-zone)
  • Page 44 bridge rectifier (for dual/tri-zone) bridge rectifier (for qua-zone)
  • Page 45 Remark: Measure the DC voltage between + and - port. The normal value should be 190V~250V.
  • Page 46 7.4.2.6 E6(PFC module protection) error diagnosis and solution. (Only for KSIM40912-H216 - 2G) Error Code Malfunction decision When the voltage signal that PFC sends to main control board conditions is abnormal, the display LED will show “E6” and AC will turn off.
  • Page 47 Inductance Two ports of the inductance...
  • Page 49 7.4.2.7 E8(Outdoor fan speed has been out of control) diagnosis and solution(Only for DC fan motor models). Error Code Malfunction decision When outdoor fan speed keeps too low (300RPM) or too high(2400RPM) conditions for certain time, the unit will stop and the LED will display the failure. Supposed causes Wiring mistake Fan ass’y faulty...
  • Page 50 Index 1: 1. DC fan motor(control chip is inside fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must have problems and need to be replaced.
  • Page 52 7.4.2.8 P0(Temperature protection of compressor top) error diagnosis and solution. (Only for KSIM30912-H216 - 1G) rror Code If the sampling voltage is not 5V, the LED will display the failure. Malfunction decision conditions Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 54 7.4.2.9 P1(High pressure protection) error diagnosis and solution. (Only for KSIM40912-H216 - 2G) Error Code Malfunction decision If the sampling voltage is not 5V, the LED will display the conditions failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 57 7.4.2.10 P2(Low pressure protection) error diagnosis and solution. (Only for KSIM40912-H216 - 2G) Error Code Malfunction decision If the sampling voltage is not 5V, the LED will display the conditions failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 60 7.4.2.11 P3(Current protection of compressor) error diagnosis and solution. Error Code Malfunction decision If the outdoor current exceeds the current limit value, the LED conditions will display the failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 62 7.4.2.12 P4(Temperature protection of compressor discharge) error diagnosis and solution. Error Code Malfunction decision When the compressor discharge temperature(T5) is more conditions than 115℃ for 10 seconds, the compressor will stop restart till T5 is less than 90℃. Supposed causes Refrigerant leakage Wiring mistake The discharge temperature sensor faulty...
  • Page 63 7.4.2.13 P5(High temperature protection of condenser) error diagnosis and solution. Error Code Malfunction decision When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temperature is less conditions than 52°C Supposed causes The condenser temperature sensor faulty Heat exchanger dirty System block...
  • Page 64 7.4.2.14 P6(IPM module protection) error diagnosis and solution. Error Code Malfunction decision When the voltage signal that IPM send to compressor drive conditions chip is abnormal, the display LED will show “P6” and AC will turn off. Supposed causes Wiring mistake IPM malfunction Outdoor fan ass’y faulty Compressor malfunction...
  • Page 66 7.4.3 Outdoor unit trouble shooting (For KSIM20912-H216 - 1G, KSIM30912-H216 - 1G, KSIM40912- H216 - 1G 7.4.3.1 E0(Outdoor EEPROM malfunction) error diagnosis and solution Error Code Malfunction decision PCB main chip does not receive feedback from EEPROM chip conditions Supposed causes Installation mistake PCB faulty Trouble shooting:...
  • Page 67 7.4.3.2 E4(open or short circuit of outdoor temperature sensor) diagnosis and solution E1/E2/E3/E6 (open or short circuit of indoor coil temperature sensor) diagnosis and solution. Error Code E1/E2/E3/E4/E6 Malfunction decision If the sampling voltage is lower than 0.06V or higher than conditions 4.94V, the LED will display the failure.
  • Page 68 7.4.3.3 E5(Voltage protection) error diagnosis and solution. Error Code Malfunction decision An abnormal voltage rise or drop is detected by checking the conditions specified voltage detection circuit. Supposed causes Power supply problems. System leakage or block PCB faulty Trouble shooting: Voltage protection Check the voltage of outdoor unit power supply,...
  • Page 69 IPM (for dual/tri- zone) bridge rectifier IPM (for qua- zone)
  • Page 70 Remark: Measure the DC voltage between + and - port. The normal value should be 190V~250V.
  • Page 71 7.4.3.4 E7(Communication malfunction between IPM board and outdoor main board) error diagnosis and Error Code Malfunction decision PCB main chip does not receive feedback from IPM module conditions during 60 seconds. Supposed causes Wiring mistake PCB faulty Trouble shooting:...
  • Page 72 Remark: Use a multimeter to test the DC voltage between black pin and white pin of signal wire The normal value should be around 5V. Use a multimeter to test the DC voltage between black pin and red pin of signal wire. The normal value should be around 12V.
  • Page 73 7.4.3.5 P0(Temperature protection of compressor discharge) error diagnosis and solution. Error Code Malfunction decision When the compressor discharge temperature(T5) is more conditions than 115℃ for 10 seconds, the compressor will stop restart till T5 is less than 90℃. Supposed causes Refrigerant leakage Wiring mistake The discharge temperature sensor faulty...
  • Page 74 7.4.3.6 P0(Temperature protection of compressor top) error diagnosis and solution. (Only for KSIM20912-H216 - 1G & KSIM30912-H216 - 1G) Error Code Malfunction decision If the sampling voltage is not 5V, the LED will display the conditions failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty...
  • Page 76 7.4.3.7 P1(High pressure protection) error diagnosis and solution. (Only for KSIM40912-H216 - 1G) Error Code Malfunction decision If the sampling voltage is not 5V, the LED will display the conditions failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 79 7.4.3.8 P2(Low pressure protection) error diagnosis and solution. (Only for KSIM40912-H216 - 1G) Error Code Malfunction decision If the sampling voltage is not 5V, the LED will display the conditions failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 82 7.4.3.9 P3(Current protection of compressor) error diagnosis and solution. Error Code Malfunction decision If the outdoor current exceeds the current limit value, the LED conditions will display the failure. Supposed causes Wiring mistake Over load protector faulty System block Outdoor PCB faulty Trouble shooting:...
  • Page 84 7.4.3.10 P4(IPM module protection) error diagnosis and solution. Error Code Malfunction decision When the voltage signal that IPM send to compressor drive conditions chip is abnormal, the display LED will show “P4” and AC will turn off. Supposed causes Wiring mistake IPM malfunction Outdoor fan ass’y faulty Compressor malfunction...
  • Page 86 7.4.3.11 P6(High temperature protection of condenser) error diagnosis and solution. Error Code Malfunction decision When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temperature is less conditions than 52°C Supposed causes The condenser temperature sensor faulty Heat exchanger dirty System block...
  • Page 87 7.4.3.12 P7(Inverter compressor drive protection) error diagnosis and solution. The same as P4(IPM module protection) 7.4.3.13 PF(PFC module protection) error diagnosis and solution. (Only for KSIM40912-H216 - 1G) Error Code Malfunction decision When the voltage signal that PFC sends to main control board conditions is abnormal, the display LED will show “PF”...
  • Page 88 Inductance Two ports of the inductance...
  • Page 90: Trouble Criterion Of Main Parts

    7.5 Trouble Criterion Of Main Parts. Spec. Indoor unit KWIM09-H2 KWIM12-H2 KWIM18-H2 Model Indoor fan motor RPG20B RPG20B RPG28H Outdoor unit Model KSIM40912-H216 - 2G KSIM30912-H216 - 1G KSIM20912-H216 - 2G KSIM330-H219 Compressor DA130S1C-20FZ DA150S1C-20FZ DA250S2C-30MT TNB306FPGMC-L Outdoor fan motor...
  • Page 91 1.Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor. Measure the resistance value of each winding by using the multi-meter.
  • Page 92 Appendix 1 Temperature Sensor Resistance Value Table (℃--K) K Ohm K Ohm K Ohm K Ohm ℃ ℃ ℃ ℃ 12.6431 2.35774 0.62973 115.266 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241 0.57683 89.5865 10.4736 2.03732 0.56038 84.2190 10.000 1.96532...
  • Page 93 Appendix 2 Unit: ℃---K Discharge temp. sensor table 542.7 68.66 13.59 3.702 511.9 65.62 13.11 3.595 62.73 12.65 3.492 455.9 59.98 12.21 3.392 430.5 57.37 11.79 3.296 406.7 54.89 11.38 3.203 384.3 52.53 10.99 3.113 363.3 50.28 10.61 3.025 343.6 48.14 10.25 2.941...
  • Page 94 Appendix 3: 10 11 12 13 14 15 16 17 18 19 20 21 22 ℃ 48 50 52 54 56 58 60 62 64 66 68 70 72 23 24 25 26 27 28 29 30 31 32 33 34 35 ℃...
  • Page 95 3.IPM continuity check Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N. Normal Normal resistance Digital tester Digital tester resistance value value...
  • Page 96 Position Resistance Value YDK180- YDK53- YDK70-6FB YSK27-4G YSK68-4B YDK45-6B YSK25-6L 6FB(B) 56Ω±8% 24.5Ω±8% 317Ω±8% 145Ω±8% 345Ω±8% 627Ω±8% 88.5Ω±8% Black - Red (20℃) (20℃) (20℃) (20℃) (20℃) (20℃) (20℃) 76Ω±8% 19Ω±8% (20 252Ω±8% 88Ω±8% 150Ω±8% 374.3Ω±8% 138Ω±8% (20 Red - (20℃) (20℃) (20℃) (20℃)
  • Page 97 6.EXV check Disconnect the connectors.
  • Page 98 Resistance to EXV coil Color of lead wire Normal Value Red- Blue Red - Yellow About 50Ω Brown-Orange Brown-White...
  • Page 99 ed- Blue ed - Yellow...
  • Page 100 Brown-Orange Brown-White...
  • Page 101: Disassembly Instructions

    8. Disassembly Instructions Parts name Procedures Remarks Overview: Front panel How to remove the front panel. One screw 1) Pull the below side Panel fixing the cover the panel and release the clips. Then remove the front panel. Clip Clip 2) Remove the filter horizontal louver.
  • Page 102 assembly. Electrical How to remove the Grounding Room temp. Swing motors parts electrical parts. screws sensor 1) After remove the front panel from Evaporator coil procedure 1, pull out the temp. sensor room temp. sensor and evaporator coil sensor. Remove the grounding screws.
  • Page 103 4) Remove the two fixing screws and then remove the electronic Two screws fixing control box and air outlet the electrical box ass’y. Evaporator How to remove the evaporator. 1) After remove the front panel ass’y and electrical parts following procedure 1 and procedure 2, remove the pipe holder at the rear...
  • Page 104 3) Remove two screws on the evaporator at the fixed plates and then lift the evaporator ass’y. Two screws at the fixed plates...
  • Page 105 Fan and How to remove the fan motor and motor. 1) After remove the evaporator ass’y following procedure 1, procedure 2 and procedure 3, remove the five screws. Five screws 2) Then separate the fan and motor.
  • Page 106: Exploded View

    9. Exploded View KWIM09-H2 Part Name Quantity BOM code Panel assembly 201132390011 Hinge Slide groove 201132300005 Air cleaner 201131410703 Bracket of air filter 201132200713 Air filter(left) 201132300002 Air filter(right) 201132300001 Display box assembly 203332590183 Display board assembly 201332590136 Cover of indoor electronic...
  • Page 107 Air inlet grille assembly 201132300027 Horizontal louver 201132300033 Air outlet assembly 201132390046 13.1 Louver motor 202400200017 13.2 Ionizer generator 202403000006 Drain hose 201101020038 Fix clamp of temperature 201130490002 sensor Evaporator assembly 201532390186 Pipe nut 201600330002 Pipe nut 201600330001 Fan motor cover 201132500017 Asynchronous motor 202400300137...
  • Page 108 KWIM12-H2 Part Name Quantity BOM code Panel assembly 201132590008 Hinge Slide groove 201132500010 Air cleaner 201131410703 Bracket of air filter 201132200713 Air filter(left) 201132500013 Air filter(right) 201132500011 Display box assembly 203332590183 Display board assembly 201332590136 Cover of indoor electronic 201132500012 control box Screw cap 201132500055...
  • Page 109 Fix clamp of temperature 201130490002 sensor Evaporator assembly 201532590004 Pipe nut 201600330003 Pipe nut 201600330001 Fan motor cover 201132500017 Asynchronous motor 202400300137 Bearing base 202730100201 Cross flow fan 201100200106 Chassis assembly 201132500007 Pipe clamp board 201232500001 Installation plate 201232590025 Electronic control box 203352090129 assembly Cover of electronic control...
  • Page 110 KWIM18-H2 Part Name Quantity BOM code Panel assembly 201132890054 Hinge Slide groove 201132890023 Air cleaner 201131410703 Bracket of air filter 201132200713 Air filter(left) 201132890025 Air filter(right) 201132890024 Display box assembly 203332890007 Display board assembly 201332890026 Cover of indoor electronic 201132490008 control box Screw cap 201132890026...
  • Page 111 Pipe nut 201600330003 Pipe nut 201600330001 Fan motor cover 201132890021 Asynchronous motor 202400300419 Bearing base 202730100201 Cross flow fan 201100200107 Chassis assembly 201132890048 Pipe clamp board 201130100204 Installation plate 201232790012 Electronic control box 203352090182 assembly Cover of electronic control 25.1 201132890015 25.2 Electronic control box...
  • Page 112 The Klimaire logo is a registered Trademark of Klimaire Products inc. Copyright 2016 Klimaire Products Inc. 2190 NW 89 Place, Doral, FL 33172 - USA Tel: (305) 593-8358 Fax (305) 499-4378 www.klimaire.com sales@klimaire.com The design and specifications are subject to change without prior notice for product...