  • Page 1 SERIES OUTDOOR UNIT Installation Manual IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.
  • Page 2: Installation Instructions - Outdoor Unit

    Outdoor Unit Installation Installation Instructions – Outdoor Unit Step 1: Select installation location Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit. Proper installation locations meet the following standards: ...
  • Page 3 If the drain joint comes with a rubber seal SPECIAL CONSIDERATIONS FOR EXTREME (see Fig. 4.4 - A ), do the following: WEATHER 1. Fit the rubber seal on the end of the drain joint If the unit is exposed to heavy wind: that will connect to the outdoor unit.
  • Page 4: Unit Mounting Dimensions

    Step 3: Anchor outdoor unit The outdoor unit can be anchored to the ground or to a wall-mounted bracket. UNIT MOUNTING DIMENSIONS Air inlet The following is a list of different outdoor unit sizes and the distance Air inlet between their mounting feet. Prepare the installation base of the unit according to the dimensions Air outlet...
  • Page 5 If you will install the unit on a wall-mounted BEFORE PERFORMING bracket , do the following: ELECTRICAL WORK, READ THESE REGULATIONS CAUTION 1. All wiring must comply with local and national electrical codes, and must be Before installing a wall-mounted unit, make installed by a licensed electrician.
  • Page 6 PA Y ATTENTION TO LIVE WIRE WARNING While crimping wires, make sure you clearly BEFORE PERFORMING ANY ELECTRICAL distinguish the Live (“L”) Wire from other wires. OR WIRING WORK, TURN OFF THE MAIN POWER TO THE SYSTEM. WARNING 1. Prepare the cable for connection: ALL WIRING MUST PERFORMED STRICTLY USE THE RIGHT CABLE IN ACCORDANCE WITH THE WIRING...
  • Page 7: Refrigerant Piping Connection

    Refrigerant Piping Connection Note on Pipe Length The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16.5ft). Refer to the table below for specifications on the maximum length and drop height of piping. Maximum Length and Drop Height of Refrigerant Piping per Unit Model Model Capacity (BTU/h)
  • Page 8 DO NOT DEFORM PIPE WHILE CUTTING Flare nut Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit. Copper pipe Step 2: Remove burrs Burrs can affect the air-tight seal of refrigerant piping connection.
  • Page 9: Minimum Bend Radius

    6. Place flaring tool onto the form. Instructions for Connecting Piping to 7. Turn the handle of the flaring tool clockwise Indoor Unit until the pipe is fully flared. 1. Align the center of the two pipes that you will 8.
  • Page 10: Instructions For Connecting Piping To Outdoor Unit

    Instructions for Connecting Piping to USE SPANNE R TO GRIP MAIN Outdoor Unit BOD Y OF VALVE Torque from tightening the flare nut can snap 1. Unscrew the cover from the packed valve on off other parts of valve. the side of the outdoor unit. (See Fig. 5.9 ) Valve cover Fig.
  • Page 11: Air Evacuation

    Air Evacuation Preparations and Precautions Evacuation Instructions Air and foreign matter in the refrigerant circuit Before using the manifold gauge and vacuum can cause abnormal rises in pressure, which pump, read their operation manuals to familiarize can damage the air conditioner, reduce its yourself with how to use them properly.
  • Page 12: Note On Adding Refrigerant

    Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed. Flare nut Turn on the vacuum pump to evacuate the system. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-10 Pa).
  • Page 13: Electrical And Gas Leak Checks

    Electrical and Gas Leak Checks WARNING – RISK OF Electrical Safety Checks ELECTRIC SHOCK After installation, confirm that all electrical wiring ALL WIRING MUST COMPLY WITH LOCAL is installed in accordance with local and national AND NATIONAL ELECTRICAL CODES, regulations, and according to the Installation AND MUST BE INSTALLED BY A LICENSED Manual.
  • Page 14: Test Run Instructions

    Test Run Before Test Run List of Checks to Perform PASS/FAIL No electrical leakage Only perform test run after you have completed the following steps: Unit is properly grounded • Electrical Safety Checks – Confirm that the unit’ s electrical system is safe and All electrical terminals operating properly properly covered...
  • Page 15: Double-Check Pipe Connections

    DOUBLE-CHECK PIPE CONNECTIONS During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during your initial leak check. Take time during the Test Run to double-check that all refrigerant pipe connection points do not have leaks. Refer to Gas Leak Check section for instructions.
  • Page 16: European Disposal Guidelines

    European Disposal Guidelines This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the following options: •...
  • Page 17 The Klimaire logo is a registered Trademark of Klimaire Products inc. Copyright 2016 Klimaire Products Inc. 2190 NW 89 Place, Doral, FL 33172 - USA Tel: (305)593-8358 Fax (305) 675-2212 www.klimaire.com sales@klimaire.com The design and specifications are subject to change without prior notice for product...