Sensible Capacity Chart - Panasonic CS-E15DB4EW Service Manual

Philips air conditioner user manual
Hide thumbs Also See for CS-E15DB4EW:
Table of Contents

Advertisement

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

13.2. Sensible Capacity Chart

G CS-E15DB4EW CU-E15DBE
Indoor wet
bulb temp.
17.0°C
19.0°C
19.5°C
22.0°C
G CS-E18DB4EW CU-E18DBE
Indoor wet
bulb temp.
17.0°C
19.0°C
19.5°C
22.0°C
G CS-E21DB4ES CU-E21DBE
Indoor wet
bulb temp.
17.0°C
19.0°C
19.5°C
22.0°C
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
30
TC
SHC
IP
TC
4.07
3.08
1.19
3.80
4.10
4.46
3.23
1.21
4.17
4.87
3.35
1.24
4.55
30
TC
SHC
IP
TC
4.76
3.61
1.40
4.45
4.80
5.23
3.78
1.43
4.89
5.70
3.92
1.45
5.32
30
TC
SHC
IP
TC
5.85
4.44
1.88
5.47
5.90
6.43
4.65
1.91
6.01
7.00
4.82
1.95
6.54
Outdoor Temp. (°C)
35
40
SHC
IP
TC
SHC
2.96
1.28
3.53
2.84
1.30
3.10
1.31
3.88
2.99
3.22
1.33
4.23
3.11
Outdoor Temp. (°C)
35
40
SHC
IP
TC
SHC
3.46
1.51
4.14
3.33
1.53
3.63
1.54
4.55
3.50
3.77
1.56
4.95
3.64
Outdoor Temp. (°C)
35
40
SHC
IP
TC
SHC
4.26
2.02
5.09
4.09
2.05
4.46
2.06
5.59
4.30
4.63
2.10
6.09
4.47
78
46
IP
TC
SHC
IP
1.37
3.21
2.70
1.48
1.40
3.53
2.84
1.51
1.42
3.85
2.96
1.53
46
IP
TC
SHC
IP
1.61
3.76
3.16
1.74
1.64
4.13
3.33
1.77
1.67
4.50
3.47
1.80
46
IP
TC
SHC
IP
2.16
4.63
3.89
2.33
2.20
5.08
4.09
2.37
2.24
5.53
4.26
2.42
Indoor 27°C/19°C
Outdoor 35°C/24°C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-e15dbeCs-e18db4ewCu-e18dbeCs-e21db4esCu-e21dbe

Table of Contents