Kohler 14RESA Installation Manual page 31

Hide thumbs Also See for 14RESA:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Generator Set
Notes:
D See Figure 2-4 for terminal block location on generator set. Check
the decal on the generator set for terminal block connections.
D See Section 1.10.2, Cable Specifications (3 runs with 1 module
each shown).
D See Figure 1-24 for communication connection detail (A and B,
PWR and COM).
D Use splices or wire nuts to collect multiple leads for connection to
the generator set terminal block. See Figure 1-27.
Figure 1-26 Accessory Module Connections (three cable runs with one module each)
Generator Set
1. Generator Set Terminal Block. See the dimension drawings in Section 2 for location. Check the decal on the generator set for terminal
block connections.
2. Splice.
3. Connect all of the shield leads on this end to GROUND at the generator set.
Figure 1-27 Multiple Connections to the Generator Set
TP-6803 1/15
Terminal
Block
1
2
A
RBUS
B
PWR
12 VDC
COM
4
3
RXT ATS
LCM
or load
shed kit
PIM
tp6803
3
A
B
SHIELDED
CABLE
PWR
COM
3
A
B
SHIELDED
CABLE
PWR
COM
tp6803
Section 1 Installation
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

20resa14resal20resal

Table of Contents