Mitsubishi Electric CMB-PW202V-J Service Handbook page 69

Table of Contents

Advertisement

[ VII Test Run Mode ]
(2) Heating only operation
Model name of WCB
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
WCB (1/3)
High pressure(63HS1)/
Pressure
Low pressure(63LS)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
WCB
HWE09070
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger outlet
HIC inlet (TH14)
DB/WB
Unit
-
m
[ft]
-
kg
[lbs-oz]
A
V
Hz
Pulse
MPa
[psi]
°C
[°F]
- 60 -
Outdoor unit model
PURY-EP250YHM-A
CMB-PW202V-J
20°C/−
[68°F/-]
7°C/6°C
[45 °F/43 °F]
2
2
125/125
5 [16-3/8"]
10 [32-3/4"]
25 [82]
Hi
19.8 [43]
12.1
400
69
406/406
110/590
2.90/0.67
[421/97]
80 [176]
1 [34]
-1 [30]
-2 [28]
-2 [28]
41 [106]
38 [100]
70 [158]
37 [99]
GB

Advertisement

Table of Contents
loading

Table of Contents