[ VIII Troubleshooting ]
Check whether the BC board output signal corresponds with the solenoid valve operation correspond.
1) SVM1
SVM1 turns on or off according to the operation mode.
Operation
Cooling only
mode
SVM1
ON
2) 21S4a operation control
21S4a turns on or off according to the operation mode.
Operation
Cooling only
mode
21S4a
3. WCB transformer
CNTR(1)-(3)
CN03(1)-(3)
* Before measuring the resistance, pull out the connector.
HWE09070
Cooling main
Differential
temperature
control OFF or
ON
Cooling main
OFF
OFF
CNTR
Red
about 58 ohm.
about 1.6 ohm.
Heating only
Heating main
OFF
OFF
Heating only
Heating main
ON
OFF
WCB control board
CN03
White
Red
Red
Normal
Open-phase or shorting
- 96 -
Defrost
Stopped
ON
OFF
Defrost
The status be-
fore defrosting
maintained
Abnormal
Stopped
OFF
GB