Possible Architectures, Achievable Safety Levels And Prerequisites; Application Examples - ABB PLUTO Safety-PLC Operating Instructions Manual

Programmable safety system intended for safety applications
Hide thumbs Also See for PLUTO Safety-PLC:
Table of Contents

Advertisement

4.4.7 Possible architectures, achievable safety levels and prerequisites

This table is an overview of safety levels for different applications.
The achievable Cat / SIL / PL depends on the sensor which is used in the application and the
detection capability of faults listed in IEC 61800-5-2, table D.16.
Structure
1 sensor/encoder
2 sensors/encoders
homogeneous
redundant
2 sensors/encoders
diverse redundant

4.4.7.1 Application examples

Example with two incremental encoders.
Usage
Achievable
Cat/ PL/ SIL
Overspeed
Cat 2 / PL c
SIL 1
Stand still
Cat 2 / PL c
monitoring
SIL 1
Overspeed
Cat 3 / PL d
SIL 3
Stand still
Cat 3 / PL d
monitoring
SIL 2
Overspeed
Cat 4 / PL e
SIL 3
Stand still
Cat 3 / PL d
monitoring
SIL 2
Prerequisites, necessary diagnostic to be
realized in the application program
Monitoring of dynamic behavior.
(E.g. Stand still is off at expected movement)
Monitoring of dynamic behavior. Stand still
should not last in more than approx. 1 hour
Monitoring of dynamic behavior.
(E.g. Stand still is off at expected movement)
Monitoring of dynamic behavior. Stand still
should not last in more than approx. 1 hour
Monitoring of dynamic behavior.
(E.g. Stand still is off at expected movement)
Monitoring of dynamic behavior. Stand still
should not last in more than approx. 1 hour
Example of two channel solution with one
encoder and a second channel from a
frequency converter. (Cat 3/PL d/SIL 2)