REU 610
26
Voltage Relay
Technical Reference Manual
Consequently, the set resetting time ensures that when the stage starts because
of voltage drops, it is not immediately reset. If stage U< has already tripped,
the stage is reset in 7 0 ms after the phase- to- phase voltages have fallen below
0.15 × U
. H owever, if stage U< has already tripped and the phase- to- phase
n
voltages have ex ceeded the set start value of the stage, the stage is reset when
the set resetting time has ex pired.
S tage U< tripping can be set to be blocked by the start of stage U<< or U
S tage U< can also be configured to be used for alarm purposes. W hen a trip
signal is generated for alarm purposes, the S tart/ Alarm indicator L E D
and the fault is indicated as an alarm instead of a trip.
W hen stage U< is configured to be used for alarm purposes:
S tart signal of stage is not generated
*
Trip signal of stage is generated, but it is indicated as an alarm
*
S tage cannot be used for triggering CBF P
*
N umber of starts is increased instead of number of trips
*
W hen the conventional protection mode is selected and the voltages fall
below the set start value of the high- set stage, U<<, the stage generates a start
signal after a ~ 5 0 ms' start time. W hen the set operate time at definite- time
characteristic or the calculated operate time at ID M T characteristic elapses,
the stage generates a trip signal. The stage is reset in 7 0 ms after the phase- to-
phase voltages have ex ceeded the set start value of the stage.
The undervoltage stages have a settable drop- off/ pick- up ratio, which is
adjustable between 1.01...1.05 , the default being 1.03 .
Un d er v oltage p r otec ti on b as ed on p os i ti v e p h as e- s eq u en c e
v oltage
The undervoltage protection based on calculated positive phase- sequence
voltage can be applied to disconnecting a smaller power plant from the
outside network, for instance in situations where there is a fault in the
network which can be critical for the power plant, such as a short circuit
either at the transmission or distribution network level.
A situation of this kind can be critical for different reasons. The power plant
can be left to feed an isolated network due to a trip caused by a fault. In this
case, there is a risk that the isolated network, which is in asynchronous state
compared to the rest of the network, is reconnected to the network as a result
of an autoreclosure, for instance. In addition, the power plant can also fall into
an asynchronous state in a fault situation. These critical situations can be
prevented by disconnecting the power plant from the network fast enough by
tripping the connecting circuit breaker.
1MRS755769
<.
1
is lit