Carrier SYSTXCCUID01-B Installation Instructions Manual
Hide thumbs Also See for SYSTXCCUID01-B:

Advertisement

SYSTXCCUID01-- B
Infinityt Control
HOLD
Fig. 1 - - Infinityt Control
Installation Instructions
COOL
OFF
A03149
NOTE: Read the entire instruction manual before starting the
installation.

TABLE OF CONTENTS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or
installation may damage the Infinity System. Recognize safety
information. This is the safety- -alert symbol
this symbol on the equipment and in the instruction manual, be
alert to the potential for personal injury. Understand the signal
words DANGER, WARNING, and CAUTION.
These words are used with the safety- -alert symbol. DANGER
identifies the most serious hazards, which will result in severe
personal injury or death. WARNING signifies a hazard, which
could result in personal injury or death. CAUTION is used to
identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
PAGE
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. When you see
1
2
2
2
4
6
7
8
8
8
9
12
13
14
16
17

Advertisement

Table of Contents
loading

Summary of Contents for Carrier SYSTXCCUID01-B

  • Page 1: Table Of Contents

    SYSTXCCUID01-- B Infinityt Control Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS ......INTRODUCTION .
  • Page 2: Introduction

    Infinity Network Interface Module (P/N SYSTXCCNIM01) allows take the place of the User Interface internal temperature sensor. connection of a Carrier HRV or ERV without the need for a This allows the Infinity Control to be mounted in areas with less separate wall control.
  • Page 3 It is not mandatory that the above color code be used, but each ABCD connector in the system MUST be wired consistently. Mounting Infinity Control There are two options for mounting the Infinity Control to the wall. First, become familiar with all plastic assembly pieces shown in Fig.
  • Page 4: Installing Infinity Control

    INSTALLING INFINITY CONTROL WARNING ELECTRICAL SHOCK HAZARD Surface Mount Backplate to wall Failure to follow this warning could result in personal injury or death. Before installing Infinity Control, turn off all power to equipment. There may be more than one power source to disconnect.
  • Page 5 9. Push any excess wire into the wall. Seal hole in wall to pre- Variable-Speed vent any air leaks. Leaks can affect operation. Furnace/Fan Coil User Interface 10. Attach Infinity Control to the mounting plastic by lining up the plastic guides on the back of the control with the open- Green ing on the mounting plastic and push on.
  • Page 6: Initial Power- -Up

    transformer. Applying 24VAC isolation relay coil to furnace or fan “SEARCHING FOR OUTDOOR EQUIPMENT” (see Fig. 16). coil HUM and COM terminals will allow the Infinity Control to Once the indoor and outdoor equipment has been found, the automatically energize the HUM output during a call for Installer will be asked to select Accessories.
  • Page 7: Heat

    Equipment Summary NOTE: Range of electric heaters available is limited by model number of the equipment installed. The Infinity Control will not allow an electric heater size that is not supported by the installed EQUIPMENT SUMMARY SETUP equipment. FURNACE 58MVB0100-12 COMPLETE! 24ANA136A003 Hydronic Heat Applications...
  • Page 8: Install / Service Menus

    8. Press the red HEAT button to select heating humidity. INSTALL/SERVICE 9. Adjust desired heating humidity level using either (+/- -) but- EQUIPMENT SUMMARY ton. INSTALL SETUP 10. Press the blue COOL button to select cooling humidity. CHECKOUT SERVICE 11. Adjust the desired cooling humidity level using ei- ther(+/- -)button.
  • Page 9: Setup Menu

    SETUP MENU English/Metric Display: _F or _C, (default = _F) This menu has several layers, allowing modification of equipment Reset Factory Defaults: settings. No settings will need to be made at equipment (i.e. DIP switches on a furnace). All configuration settings made effective Program Schedule: from this menu will override equipment configuration made by dip Yes/No to reset back to Energy Star default Time and...
  • Page 10 G Terminal Off Delay This setup option selects desired operation when the R- -G circuit 90 seconds changes state on the furnace control board depending on setup. 120 seconds (default) DISABLED (Default) 150 seconds FAN - - turns on fan to selected fan speed when G termi- 180 seconds nal is energized.
  • Page 11 Setup - - Heat Pump / AC Setup - - Hybrid Heat Cooling Lockout: HYBRID HEAT SETUP NONE (default) OUTSIDE LOCKOUT TEMPS 45_F / 7_C FURNACE LOCKOUT: > 30 F 50_F / 10_C HEAT PUMP < 15 F LOCKOUT: 55_F / 13_C DEFROST W/FURNACE: Outside temperature below which cooling will not be provided.
  • Page 12: Checkout Menus

    BLOWER ON DELAY - - Time after hot water is requested that the SYSTEM MAINTENANCE blower will turn on. REMIND OWNER OF Available settings - - 0 to 240 seconds in 30 second incre- MAINTENANCE EVERY: ments 12 MONTHS Default is 30 % USED: BLOWER OFF DELAY- - Time after hot water request terminates before the blower will turn off.
  • Page 13: Service Menus

    Checkout - - Heat Pump Heating Heat Stage: OFF, LOW, HIGH HIGH HEAT RUNTIME: 5 min. Displays stage of heat that the furnace is currently delivering. LOW HEAT RUNTIME: 5 min. Airflow CFM: DEFROST: NO (furnace model dependent) The heat pump heating mode can be exercised with this menu option.
  • Page 14: Operational Information

    If static pressure cannot be accurately calculated, the dis- To edit: play will read UNKNOWN. When this is seen, the sys- Use Temp +/- - button to move cursor left and right. tem is adjusting to high static pressure by cutting back Use Time +/- - button to select numbers and letters.
  • Page 15 Three- - Minute Minimum On Time dehumidify operation. If set to EFFICIENCY or MAXIMUM, no special dehumidify operation will take place during a normal In normal operation, when a stage turns on, it will remain on for a cooling call. Cooling will only operate to satisfy the space minimum of three minutes.
  • Page 16: Troubleshooting

    TROUBLESHOOTING Please refer to the Troubleshooting Guide available on HVAC Partners for more detail. Infinity Control does not power up. 1. Recheck wiring to ABCD on all devices. 2. Make sure all colors match for every terminal. 3. Make sure power is applied to the indoor unit, and the amber LED is lit on indoor control circuit board. 4.
  • Page 17: System Malfunction Screen

    SYSTEM MALFUNCTION SCREEN Outdoor Unit The code number represents flash code on circuit board of outdoor OUTSIDE: 84_ | FAN: AUTO unit. Code 25 - - Invalid model plug Code 45 - - Control Failure Code 47 - - No 230V at unit Code 73 - - Contactor shorted HVAC SERVICE 1--- 800--- 555--- 1212...
  • Page 18 Catalog No: UID01---3SI Copyright 2007 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in China Edition Date: 03/07 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: UID01--- 2SI...

This manual is also suitable for:

Infinity systxccuid01-b

Table of Contents