GENERAL GENERAL 1.1 Features Duct Type Air Conditioner Features Save Installation Space The indoor unit can be installed inside the ceiling conveniently. Optional Static Pressure 18k: optional 10Pa /30Pa, 24K/36K 50Pa/80Pa(For AUD-24UX4SALH1&AUD-36UX4SAMH1, freely changed between1-80Pa), 48K/60K: 80Pa/120Pa static Pressure. One unit, mute optional installation method. High Efficiency and Environment Friendly New Refrigerant-R410A R410A can protect the environment and do not harm to the ozone layer.
Page 5
GENERAL GENERAL Cassette Type Air Conditioner Features Save Installation Space The indoor unit can be installed inside the ceiling conveniently. High Efficiency and Environment Friendly New Refrigerant-R410A R410A can protect the environment and do not harm to the ozone layer. 24-hour Timer ON and OFF This Timer can be set to automatically turn the unit on or off within a 24-hour period.
GENERAL GENERAL or on the floor. One unit, Two installation method. High Efficiency and Environment Friendly New Refrigerant-R410A R410A can protect the environment and do not harm to the ozone layer. 24-hour Timer ON and OFF This Timer can be set to automatically turn the unit on or off within a 24-hour period. Mute Operation The excellent fan design enable the airflow to be quiet and smooth with minimum noise.
GENERAL GENERAL Ceiling&Floor WAV- ● ● ● ● ● type 1.3 MODEL IDENTIFICATION DC IINVER AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.3...
Page 8
GENERAL GENERAL WAW-18/INV W----WINTAIR A-----AIR CONDITIONER W----OUTDOOR UNIT 18----18000 BTU /INV---INVERTER MACHINE WAD-18IN/INV W----WINTAIR A-----AIR CONDITIONER D----D FOR DUCTED,C FOR CASSETTE,V FOR FLOOR CEILING 18----18000 BTU /INV---INVERTER MACHINE 1.4 Product Picture Duct Type Model WAD-18IN/INV WAD-24IN/INV Indoor Outdoor Model WAD-36IN/INV WAD-48IN/INV DC IINVER AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.3...
Page 9
GENERAL GENERAL Indoor Outdoor WAD-18IN/INV1 WAD-24IN/INV1 Model Indoor Outdoor DC IINVER AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.3...
Page 10
GENERAL GENERAL WAD-36IN/INV1 Model Indoor Outdoor Cassette Type Model WAC-18IN/INV WAC-24IN/INV Indoor Outdoor WAC-48IN/INV Model WAC-36IN/INV WAC-60IN/INV DC IINVER AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.3...
Page 11
GENERAL GENERAL Indoor Outdoor WAC-24IN/INV Model WAC-18IN/INV WAC-36IN/INV Indoor Outdoor DC IINVER AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.3...
Page 12
GENERAL GENERAL Ceiling &Floor Type Model WAV-18IN/INV1 WAV-24IN/INV1 Indoor Outdoo WAV-48IN/INV Model WAV-36IN/INV1 WAV-60IN/INV DC IINVER AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.3...
4-2MAX. Refrigerant pipe length and height difference *Do your best to reduce the pipe length. Long pipe may cause capacity of the indoor unit incline. Total refrigerant pipe length Outdoor unit precharged 0m~5m 5m~60m 1270g 0g WAW-18/INV Xg = 15g / m × (Total pipe length(m) ‐5) 1500g 0g WAW-24/INV 2100g 0g WAW-36/INV 1400g 0g WAW-18/INV1 1680g 0g WAW-24/INV1 2100g 0g ...
& & 4-3ELECTRIC Diagrams Recommend Wire Size Power Source Transmitting Cable Model POWER SUPPLY Cable Size Size (mm2) (mm2) 220-240V,50Hz 3×1.5 4×0.75 24K/36K 220-240V,50Hz 3×2.5 4×0.75 380~415V,3N~,50Hz 48K/60K 5×2.5 4×0.75 ● Use an ELB (Electric Leakage Breaker). If not used, it will cause an electric shock or a fire.
Page 41
& & (B) Check to ensure that the stop valves of the outdoor unit are fully opened and then start the system. ● Pay attention to the following items while the system is running. (A) Do not touch any of the parts by hand at the discharge gas side, since the compressor chamber and the pipes at the discharge side are heated higher than 90 .
& & 4-4Air flow and ESP Chart Diagrams(for duct type) 18K 18K Curve for 10Pa ESP 1000 Air flow(m3/h) 18K Curve for 30Pa ESP 1000 1100 Air flow(m3/h) DCINVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 43
& & 24K 24K Curve for 50Pa ESP 700 800 900 1000 1100 1200 1300 1400 Air flow(m3/h) 24K Curve for 80Pa ESP 600 700 800 900 1000 1100 1200 1300 1400 1500 Air flow(m3/h) DCINVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 44
& & (AC MOTOR) 36K Curve for 50Pa ESP 900 1100 1300 1500 1700 1900 Air flow(m3/h) 36K Curve for 80Pa ESP 800 1000 1200 1400 1600 1800 2000 Air flow(m3/h) DCINVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 45
& & 48K 48K Curve for 80Pa ESP 1500 1700 1900 2100 2300 2500 Air flow(m³/h) 48K Curve for120Pa ESP 1500 1700 1900 2100 2300 2500 Air flow(m³/h) DCINVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 46
& & 60K 60K Curve for 80Pa ESP 1500 1700 1900 2100 2300 2500 Air flow(m³/h) 60K Curve for120Pa ESP 1500 1700 1900 2100 2300 2500 Air flow(m³/h) DCINVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
5-2. Electric control Board 1. Indoor control board Duct type 18K,48K,60K &WAD-24IN/ INV WAD-36IN/ INV WAD-24IN/ INV 1 WAD-36IN/ IN V DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 63
CASETTE Type 24K,36K,48K,60K DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 64
Ceiling & Floor type 18k,48k,60k 24k,36k DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 65
2.Control board for outdoor unit 1) OUTDOOR CONTROL BOARD WAW-18/ INV ) WAW-18/ INV 1) CONTROL BOARD( ) WAW-24/ INV CONTROL BOARD( AC fan motor Heater N N OUT Earth AC N IN 4-way valve AC L IN Heater L Communication SI IPM-SI Communication N...
Page 66
) WAW-36/ INV CONTROL BOARD( 4-way valve Heater N 4-way valve N OUT Heater L AC N IN AC fan motor Earth AC L IN Electric expansion valve Communication SI IPM power IPM-SI Communication N AC L OUT Suction Sensor High pressure switch Outdoor Sensor Discharge Sensor...
Page 67
WAW-48/ INV WAW-48/ INV WAW-60/ INV ) CONTROL BOARD( Heater N Transformer Down fan motor Up fan motor POWER IN 4-valve AC contactor Heater L Transformer Communication N Communication SI Coil/defrost Sensor High pressure switch IPM-SI Outdoor Sensor Electric expansion valve Low pressure switch Suction sensor Discharge sensor...
Page 68
( ) WAW-18/INV1 WAW-24/INV1 WAW-36/INV1 By Pass valve Heater N 4-way valve N OUT Heater L AC N IN AC Fan Earth AC L IN Electric expansion valve Communication SI IPM power IPM-SI Communication N AC L OUT Suction Sensor High pressure switch Outdoor Sensor Discharge Sensor...
Page 69
IPM Board IPM Board(WAW-18/ INV ) To Electrolytic Capacitor + To PFC Inductor-2 AC L IN To PFC Inductor-1 To Electrolytic Capacitor - AC N IN IPM Power To Compressor W To Compressor V To Compressor U To Main Control To Electrolytic Board Capacitor +...
Page 70
WAW-48/INV WAW-60/INV AC IN-W Compressor AC IN-V Contacto Compressor AC IN-U Inductor Compressor AC IN Inductor L1 Contact IPM-SI DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
5-4. Digital Display Switch of Outdoor Digital Display Switch Introduction It can be used to check outdoor running parameters. There are 3 buttons on the digital display board: 1)SWITCH button:Indoor parameters and outdoor parameters can be selected in turn by pressing it. P--outdoor unit, H--indoor unit;...
Page 73
The parameters will be displayed after 3s when the checking numbers are selected. Parameters can be checked as following table below. Parameter Descriptions code Protect Code or Error Code Target Frequency Driver Frequency Outdoor Electronic expansion valve Opening Outdoor Electronic expansion valve Target Opening Upper DC Motor Revolving Speed AC Input Voltage Current...
5-5. Static Pressure Setting (only for duct type) CHANGE OF STATIC PRESSURE The static pressure outside the indoor unit can be chosen . Models except DC FAN MOTERS(AUD-24UX4SALH1 & AUD-36UX4SAMH1) : You can change the static pressure by changing the fan motor terminal which refer to following Fig.below: FOR DC FAN MOTER DUCT AIR CONDITIONERS(AUD-24UX4SALH1 &...
Page 75
5-6 System Parameter Adjustment Internal control parameter adjustment can be performed. OPERATION: ①Hold down both“MODE”button and“ADD.FUNC.”button for 3 seconds, symbol and parameter number blinking at the same time. ②Press“ ”“ ”button to adjust parameter number until display “17”. And press “ENTER”button to entering system parameter adaption state, symbol stop blinking.
Page 76
PARAMETER PARAMETER VALUE&REPRESENTATION PARAMETER DESCRIPTION NOTE CODE DATA TYPE REPRESENTATION(FUNCTION CODE) Temperature Adjustment-Heating Character -10~10℃(Single Character with symbol) =0,Cooling/Heating Temperature Limit are all Invalid =1,Cooling Temperature Limit is valid,Heating Temperature Limit is invalid Cooling/Heating Temperature Limit Integer =2, Cooling Temperature Limit is invalid, Heating Temperature Limit is valid =3,Cooling/Heating Temperature Limit are all valid The Lowest Set Temperature in...
6-1 Indoor control mode 1.Major general technical parameters 1 Remote receiver distance: 8 m. 2 Remote receiver angle: Less than 80 degrees. 3 Temperature control accuracy: ±1℃. 4 Time error: Less than 1%. 2. Functions of the controller Control function 2.1 Emergency switch Press the emergency button can realize the starting or closing Machine, starting up according to the automatic mode of operation(invalid for duct type air-conditioner)...
Page 86
will start in the timer off condition. When the set time is up, the air conditioner will turn off after receiving a signal from the remote controller. If the air conditioner has not received a signal from the remote controller when the set time is up, it will turn off automatically. 3.
Page 87
The heating mode, remote shutdown, such as indoor heat exchanger temperature is higher, the wind blowing out opportunities continue to run the waste heat. Cool and dehumidification mode , after the compressor close, indoor machine will continue to set the speed of operation for a period of time. 2.9 automatically model This model does not automatically model function, emergency button cannot set the automatic mode of operation, can use the emergency switch shutdown, remote setting the...
Page 88
6-2 Outdoor mode control Control function 1.Cooling Anti-freeze Protection To prevent indoor air conditioner evaporator temperature is too low, the indoor coil sensor for real time detection of evaporator. If the indoor coil temperature is too low, the compressor will protect. 2.
Page 89
Four-way valve of the outdoor machine shuts down when cooling and defrosting but starts when heating. During the heating process, the four way valve to stop working for a period of time after compressor disconnect. 7. Start-up Protection: To prevent compressor from restart frequently in the condition that system pressure has not been completely balanced, it can’t be restarted within 3 minutes.
Trouble guide When the air conditioner failure occurs, the fault code will displays on control board , wire remote controller or display panel. HOW TO CHECK FAULT CODES INDOOR UNIT 1.WALL MOUNTED TYPE For Free-match series Run the air-conditioner by wireless remote controller , continue pressing “SLEEP ”button for 4 times, fault codes will flashing rapidly on the...
Page 91
MOEDL:YXE-C01U FIG.2 ERROR CODE DISPLAY ON WIRE REMOT CONTROLLER (2)CHECK ERROR CODES BY DISPLAY PANEL(CASSETTE type and CEILING &FLOOR type) Display by lamp indicator Lamp RUN(LED2 ,red) and Lamp DEFROST(LED5 ,green)flashing,Lamp RUN display fault code ten digit number, lamp DEFROST display fault code single digit number (as shown fig. below). For example,fault code 36:...
Page 92
DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 93
LED FALSH CONTROL:flash 300mS(T1),off 300mS(T2),after 2000mS(T3)fault code repeat displays. (as shown below) T1 T2 Fig.2 LED FALSH CONTROL 3.Duct type indoor units of VRF---FAULT CODE DISPLAY BY INDOOR BOARD LED2 and LED5 are failure indicate lamps, LED2(YELLOW) indicate fault code ten digit number, LED5(GREEN) indicate single digit number code DC INVERTER AIR CONDITIONER TECHNICAL&...
Page 94
2.OUTDOOR UNIT FAULT CODE DISPLAY (1) ON/OFF UNITARY TYPE(with outdoor control box) Fault code display by indicate lamps of outdoor control board flash. The times that the lamp flashes equal to fault code. LED2-fault code lamp LED FALSH CONTROL: flash 300mS(T1), off 300mS(T2), after 900mS(T3)fault code repeat displays. (as shown below) T1 T2 (2)INVERTER UNITARY AIR CONDITONER , MULTI-SPLIT TYPE AIR CONDITONER&VRF:...
Page 95
Outdoor Control Board Digital Tube FOR INVERTER UNITARY AIR CONDITONER&VRF * VRF: Indoor unit can indicate both indoor failure and outdoor failure ,but outdoor only indicate outdoor’s. FOR MULTI-SPLIT TYPE Error code display on digital tube board directly. DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 96
3.Fault code display ( Driver Board ) The lamp of driver board flash shows failure occur. Or, fault code can be check on digital tube board . DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 97
The following is the fault code table of outdoor. sheet 1 Outdoor Error Code Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1.Reconnect the outdoor ambient 1.The outdoor ambient temperature sensor temperature sensor; connect loose; Outdoor ambient temperature 2.Replace the outdoor ambient 2.The outdoor ambient temperature sensor is...
Page 98
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code Applied to 1.Replace outdoor ambient ON/OFF 1.Outdoor ambient temperature sensor fault; temperature sensor; air-condition Motor blockage protection 2. Outdoor coil temperature sensor fault; 2.Replace outdoor coil temperature ers with 2 3.Outdoor control board fault.
Page 99
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 3.Replace the outdoor control board supply models Application 1. Normally protection 1.Three-phase power is abnormal; 2. Check the wiring connection refer to three-phase voltage absent phase 2.The outdoor wiring connect wrong; the wiring diagram;...
Page 100
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1.Reconnect the wiring of the suction 1.The wiring of the suction temperature temperature sensor; Suction temperature sensor sensor connect loose; 2.Replace the suction temperature fault 2. The suction temperature sensor is failure; sensor;...
Page 101
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 2.The sensor of the expansion valve A(thick 2. Replace the sensor for the &inverter tube)is failure; expansion valve A(thick tube); unitary types 3.The sampling circuit is abnormally 3.
Page 102
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 2.The high-pressure pressure sensor is 2.Replace the high-pressure pressure failure sensor; 3.The sampling circuit of the high-pressure 3.Replace the outdoor control board. pressure sensor is failure 1.The wiring of the low-pressure pressure 1.Reconnect the wiring of the sensor connect loose;...
Page 103
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code as capillary, expansion valve) 4. Normally protection. 1.Reconnect the wiring of the up DC 1.The wiring of the up DC fan motor connect fan motor; loose; 2.Replace the up DC fan motor; 2.
Page 104
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The wiring of the sensor connect loose; 1. Reconnect the wiring of the sensor; Expansion valve E 2.The sensor of the expansion valve Eis 2. Replace the sensor for the FOR Branch temperature sensor fault failure;...
Page 105
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code the refrigerant of the unit is not Discharge the refrigerant and charge The refrigerant of the unit is not enough enough fault the refrigerant refer to the rating label 1.The wiring of the 4-way valve coil connect 1.
Page 106
The following is the fault code table of indoor. Sheet 2 Indoor Error Code List Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The buttons are failure; 1. Replace the display board; 2. The cable of the display board is 2.
Page 107
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The connection cable between the indoor unit and the outdoor unit connect 1. Reconnect the connection cable wrong; refer to the indoor and outdoor 2.The communication cable between wiring diagram;...
Page 108
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. Check whether there are something to block the drain hose or the height of the drain hose is too 1. The water level of the drain pan high;...
Page 109
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 4.Indoor control board is failure. 1. The cable of the water tank water temperature sensor 2 connect loose; 1. Reconnect the cable of the water 2. The cable of the water tank water temperature sensor 2;...
Page 110
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code indoor unit and the outdoor unit is wiring diagram; failure or 4. Replace the indoor control board; the cable between the indoor control 5. Replace the outdoor control board. board to terminal is failure or the cable between...
Page 111
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The cable of the room temperature 1.Reconnect the cable of the room sensor connect loose; temperature sensor; Indoor ambient 2. The room temperature sensor is 2. Replace the room temperature Temperature Sensor Fault failure;...
Page 112
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1. The cable of the temperature sensor 1. Reconnect the able of the temperature sensor of the outlet of The outlet of water the outlet of water side is failure; water side;...
Page 113
Fault Fault Description Possible Reason of Abnormality How to Deal With REMARKS code 1.The wiring between the display board to 1. Reconnect the between the display the indoor control board connect loose; board to the indoor control board; 2.The sequence of the wiring between 2.
Page 114
The expansion valve or the capillary is failure Replace the expansion valve or the capillary Note 4:Over load in heating mode Overload in heating mode The root cause Corrective measure Discharge the refrigerant, and recharge the refrigerant refer to the The refrigerant is excessive rating label The indoor ambient temperature is too high...
The following is the fault code table of driver board. Analysis of the Driving Board Fault (Except Free-match 20K&16K DUAL TYPES), Driver board fault codes trouble shooting details see sheet 5. I. Driver fault code display by indicate lamps of driver board flashing. The times that the lamp flashes equal to fault code.
Page 116
Fault Fault Description Possible Reason of Abnormality How to Deal With code Communication between 1,Communication wire connect not well; 1, Check compressor wire connect. driver board and control 2,Driver board fault; 2,Change the driver board; board fault 3,Control board fault; 3,Change the control board ;...
Page 117
1 time flash 1 time flash LED ON LED ON LED OFF LED OFF 1.0sec 1.0sec 0.5sec 0.5sec For example,fault code 4: Indicator light flash 4 times1-second short LED on/off Intervals for a period of time again, reports No. 4 fault. LED ON LED OFF 3.0sec...
Page 118
Fault Fault Description Possible Reason of Abnormality How to Deal With code 2、 Driver board failure; board; 3、PFC failure; 3、Change the PFC. DC voltage detected abnormal . 1、 Input voltage is too high or 1,Check the power supply. too low; PFC LOW voltage detected failure.
8-1. Check refrigerant system TEST SYSTEM FLOW Conditions: ① Compressor is running. ② The air condition should be installed in good ventilation. Tool: Pressure Gauge Technique: ① see ② feel ③ test ----- Tube defrost. FEEL ----- The difference between tube’s temperature. TEST ----- Test pressure.
Page 120
Test system flow Cooling mode Test system The pressure on the pressure.Does the low high side. pressure normal at service part ? Recharge refrigerant after air purging with If the pressure is The pressure on the the vacuum close to static low side.
8-2.Check parts unit 1. INDOOR FAN MOTOR Duct type YSK110-40-4-A (HS16) M1:146±15%Ω M2: 33±15%Ω M3: 43±15%Ω A1: 63±15%Ω A2: 23±15%Ω A3: 119±15%Ω DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 122
WAD-24IN/ INV Y6S419C56 WAD-24IN/ INV 1 DC MOTOR WAD-36IN/ INV 1 DC MOTOR DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 123
WAD-36IN / INV Y7S423C024 DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 124
48K,60K DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 125
Cassette 25℃ 24K,36K,48K,60K DC-MOTOR DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 126
Ceiling & Floor type YSK110-22-4-A M: 187Ω A1:37.5Ω A2:27.8Ω A3:146Ω 24K-- DC MOTOR SIC-70CW-F1100-6 36K-- DC MOTOR SIC-70CW-F1140-3 48K,60K Y7S423C032 WHITE-BLACK:42.69 BLACK-BLUE:9.19 BLUE-YELLOW:9.09 RED-BLACK:36.41 DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 127
Test in resistance. TOOL: Multimeter. Test the resistance of the main winding. The indoor fan motor is fault if the resistance of main winding 0(short circuit)or∞(open circuit). Test in voltage TOOL: Multimeter. Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage “YELLOW”...
Page 128
2. OUTDOOR FAN MOTOR MOTOR EXAMINE AND REPAIR Circuit diagram WAW-18/ INV1 WAW-24/ INV1 WAW-36/INV1 —DC MOTOR 18K-- MOTOR MODEL:ARW4401QH 24K-- MOTOR MODEL:SIC-71FW-D8121-1 36K-- MOTOR MODEL:SIC-71FW-D8121-1 Circuit diagram WAW-18/INV YDK29-6I-22: Winding BROWN "M"-The Main Winding "A"-The Auxiliary Winding Capacitor Hot Protector 130℃ WHITE PINK PURPLE...
Page 129
BROWN YELLOW WINDING M: Main winding A: Auxiliary winding Capacitor Hot protector WHITE BLACK BLUE Winding resistance ( at 20℃) M1:59.1Ω M2:20.3Ω M3:15.3Ω A: 85.8Ω 48K,60K YDK65-6-9024、YDK65-6-9061 Winding resistance ( at 20℃) M:83.0Ω A1:23.4Ω A2:14.0Ω A3: 63.5Ω Test in resistance. TOOL: Multimeter.
Page 130
3. COMPRESSOR COMPRESSOR EXAMINE AND REPAIR WAW-18/ INV :DA130S1C-20FZ WAW-18/INV 1 DA131S1B-28FZ WAW-24/INV DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 131
WAW-24/INV 1 DA230S2C-31MT DA250S2C-30MT (TNB306FPNMC) DC INVERTER AIR CONDITIONER TECHNICAL& SERVICE MANUAL V3.3...
Page 132
(LNB42FSAMC) Test in resistance. TOOL: Multimeter. Test the resistance of the winding. The compressor is fault if the resistance of winding 0(short circuit)or∞(open circuit) Familiar error: 1)Compressor motor lock. 2)Discharge pressure value approaches static pressure value . 3)Compressor motor winding abnormality. Notes:...
Page 133
4. INDUCTANCE Familiar error: 1)Sound abnormality 2)Insulation resistance disqualification. 5. STEP MOTOR Test in resistance. TOOL: Multimeter. Test the resistance of winding. The stepper motor is fault if the resistance of winding 0(short circuit)or∞(open circuit). 6. FUSE Checking continuity of fuse on PCB ASS’Y. 1) Remove the PCB ASS’Y from the electrical component box.
Page 134
* The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its original position. * The range of deflection and deflection time differ according to the capacity of the capacitor. Multimeter Compressor motor capacitor Fan motor capacitor...