Advanced Lock Control Type

- To use the advanced lock function (Run Mode lock, Fan Speed lock,
Temperature Lock, and Temperature Range lock; adjustable only within certain boundary)
by central controller, Set up the fifth dip switch according to the type of outdoor product.
- In case of advanced lock function, it can use only the central controller applied to LGAP.
ON
' 1, 4 and 5 ON, All others OFF :
MultiV Products (Except CRUN products) or MPS Inverter Product
1 2 3 4 5 6 7 8
+ Central Controller (All types) - Using LGAP
ON
' 2, 4 and 5 ON, All others OFF :
Multi Standard Product + Central Controller (All types) - Using LGAP
1 2 3 4 5 6 7 8
ON
' 1, 2, 3, 4and 5 ON, All others OFF :
MultiV CRUN Product + Central Controller (All types) - Using LGAP
1 2 3 4 5 6 7 8
NOTE : The advanced lock setting
Some products do not support advanced lock function.
In this case, The fifth dip switch on PI485 must be on.
In case of product applied to advanced function, it can process the advanced lock function without fifth dip
switch ON.
If all units support advanced lock function,
It is recommended that the fifth dip switch be off, so that advanced lock function is processed faster.
Advanced Capacity Control Type
ON
' 1, 4, 5 and 6 ON, All others OFF :
Single & Multi Product(Only Pressure Control type) + PUDCA0
1 2 3 4 5 6 7 8
CAUTION:
The wrong setting of air-conditioner switch could cause malfunctioning.
Switch setting must be done carefully.
After setting the dip switch, PI485 must be reset
Installation Guide
Installation Manual 9