Page 1
INSTALLATION MANUAL Branch Kit To prevent injury to the user or other people and property damage, the following instructions must be followed. WARNING This symbol indicates the possibility of death or serious injury. CAUTION This symbol indicates the possibility of injury or damage. WARNING •...
Page 2
Separately use a branch pipe depending on indoor capacity for installation. Unbalance type of branch pipe must be connected depending on large capacity or small capacity. Indoor Classification Model Name Capacity Ratio(%) Remark 2 UNIT PMUB11A 50:50 (1:1) PMUB23A 40:60 (2:3) Unbalance type 3 UNIT PMUB122A 20:40:40 (1:2:2)
Page 3
4 . Pipe length and difference between high and low Install the branch pipe so that pipe length and difference between high and low will not exceed below SPEC. Branch Pipe Length(m) Spec. Total(Main+Branch) Main Pipe(L1) Branch Pipe----Total Each In out (h1) In-In (h2) L1+L2/L3/L4/L5 Indoor-Indoor_(b)