Installation

3.4.5.2 Control Terminal Types

Illustration 3.10 and shows the removable adjustable
frequency drive connectors. Terminal functions and default
settings are summarized in Table 3.2.
Illustration 3.10 Control Terminal Locations
Illustration 3.11 Terminal Numbers
Connector 1 provides four programmable digital
input terminals, two additional digital terminals
programmable as either input or output, a 24V
DC terminal supply voltage, and a common DC
voltage for optional customer-supplied 24 V. A
digital input for STO (Safe Torque Off) function.
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
Connector 3 provides two analog inputs, one
analog output, 10V DC supply voltage, and
commons for the inputs and output
Connector 4 is a USB port available for use with
the DCT-10
Also provided are two Form C relay outputs that
are in various locations depending upon the
adjustable frequency drive configuration and size.
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option.
See 8.1 General Technical Data for terminal ratings details.
AF-650 GP Quick Guide
Terminal Parameter
12, 13
18
19
32
33
27
29
20
37
39
42
50
53
54
55
DET-759A
Terminal description
Default
setting
Description
Digital inputs/outputs
-
+24V DC
24 V DC supply
voltage. Maximum
output current is
200mA total for all
24V loads. Usable for
digital inputs and
external transducers.
E-01
[8] Start
E-02
[10] Reversing
E-05
[0] No
Digital inputs.
operation
E-06
[0] No
operation
E-03
[0] No
Selectable for either
operation
digital input or
output. Default setting
E-04
[14] JOG
is input.
-
Common for digital
inputs and 0V
potential for 24V
supply.
-
Safe Torque
Safe input. Used for
Off (STO)
STO.
Analog inputs/outputs
-
Common for analog
output
AN-50
[0] No
Programmable analog
operation
output. The analog
signal is 0–20 mA or
4–20 mA at a
maximum of 500Ω
-
+10V DC
10V DC analog supply
voltage. 15mA
maximum commonly
used for potenti-
ometer or thermistor.
AN-1#
Reference
Analog input.
Selectable for voltage
AN-2#
Feedback
or current. Switches
A53 and A54 select
mA or V.
-
Common for analog
input
3
3
9