Carrier 40GRQ Installation Instruction page 10

High- wall ductless split system
Hide thumbs Also See for 40GRQ:
Table of Contents

Advertisement

Outdoor Unit
A
B
Service Valve
Fig. 18 - Service Valve
Manifold Gage
500 microns
Low side valve
Charge hose
Low side valve
Fig. 19 - Manifold
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water. (See Fig. 20)
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0
1
2
3
MINUTES
Fig. 20 - Deep Vacuum Graph
Indoor Unit
Refrigerant
Low Side
C
D
High Side
A07360
High side valve
Charge hose
Vacuum pump
A07361
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT
DRY SYSTEM
4
5
6
7
Triple Evacuation Method
The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water.
Refer to Fig. 21 and proceed as follows:
1. Pump system down to 28 in. of mercury and allow pump to
continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen will be able to diffuse
throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 21. The system is
then free of any contaminants and water vapor.
BREAK VACUUM WITH DRY NITROGEN
BREAK VACUUM WITH DRY NITROGEN
CHECK FOR TIGHT, DRY SYSTEM
RELEASE CHARGE INTO SYSTEM
Fig. 21 - Triple Evacuation Method
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.
A95424
10
EVACUATE
WAIT
EVACUATE
WAIT
EVACUATE
(IF IT HOLDS DEEP VACUUM)
A95425