Troubleshooting
6. E5 malfunction
E5 display
Voltage protection of compressor
No
Check the voltage of outdoor unit power supply, whether the voltage
Check the power supply
between L(1) and N is about 172-265V
Yes
Yes
Replace the power board, then check whether the system can run normally
Trouble is solved
No
Replace outdoor main board
39