Jumper Controls - ABB REL 301 Instruction Leaflet

Numerical distance relay
Hide thumbs Also See for REL 301:
Table of Contents

Advertisement

I.L. 40-386.4
Relay Output Test
All relay outputs can be tested using the procedure described below
(1) Open the red FT switches, of the breaker trip circuits, making sure that the following FT switch
is not opened:
(2) Move the spare blue jumper to position JP5 on the Microprocessor module (refer to Table 5-3).
(3) Press the SELECT push-button until the TEST mode is displayed; then depress the RAISE or
LOWER key until the output function to be tested appears in the FUNCTION and VALUE fields,
respectively.
(4) Press the ENTER push-button for the desired duration of the output relays operation.
(5) Press the RAISE push-button to select the following parameters, as desired:
Function
Field
m RX1
m RX2
m RX1, RX2
Trip
BFI
RI2=3RI
RB
u Fail Alarm
Trip Alarm
Gen Start
m Send
m Stop
s OC1
s OC2
s OC3
s OC4
s OC5/Stop
:
Note
m denotes for pilot option only.
u a Vac balanced 3-phase voltage must be applied to relay
s denotes available with programmable contact output option.
NOTE:
(6) After completion of this test, restore the system to its operating state by moving the blue jumper
to position JP3 on the Microprocessor module, and closing the FT switch red handles.
4. 5.

JUMPER CONTROLS

All jumpers are set at the factory; the customer normally does not need to move the jumpers. Refer
to Tables 5-1, 5-2 and 5-3 for the recommended jumper positions.
4-6
Value
Field
Simulate
Simulate
Simulate
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
Relay
for change of state to occur; without it the Failure alarm is
always in the Alarm State.
Pressing the ENTER push-button operates selected output relays.
FT-5 BFI/Reclose Enable
Description
Carrier Receiver #1 Simulated Test
Carrier Receiver #2 Simulated Test
Carrier Receiver #1 and #2 Simulated Test
Trip
Breaker Failure
3-Pole Reclose Initiate
Reclose Block
Failure Alarm
Trip Alarm
General Alarm
Send
Stop
Programmable Output Contact, 1
Programmable Output Contact, 2
Programmable Output Contact, 3
Programmable Output Contact, 4
Programmable Output Contact, 5/Stop