Rel301/302 Relay Program Functions - ABB REL 301 Instruction Leaflet

Numerical distance relay
Hide thumbs Also See for REL 301:
Table of Contents

Advertisement

I.L. 40-386.4
-Initialization
POWER
-Self-Checks
ON
1-14
Mode =
Background
START
Sample V and I
dc Offset
Correction
Compute V and I
Phasors Using
Fourier Algorithm
Mode?
Background
Y
Disturbance
Ι?
in
V or
N
- Operator Panel
Interface
- Hardware Self-Checks
Figure 1-6 REL301/302 Relay Program Functions
Fault
Relaying Calculations:
Zone-1 and Pilot Zone
Mode =
Fault
Relaying Calculations
- Zone-2
- Zone-3
- Out-of-Step Blinders
- Inst. Overcurrent
- Ground Backup
- Phase Selector
Checks and Logic
- Non-Pilot Trip Logic
- Loss-of-Pot. And Loss-of-Current
- Data Communications
- Contact Inputs
- Programmable Output Contact Update
Pilot Logic and
Channel Control
Mode =
Y
No Fault for
Background
3 Cycles?
N
ESK00252 dtp

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel 302

Table of Contents