CONNECTION OF THE AC CABLING
This is a Safety Class I product (supplied with a protective grounding terminal). Uninterrupted protective
grounding must be provided at the AC input and/or output terminals and/or chassis grounding point located
externally on the product.
The MultiPlus is provided with a ground relay that automatically connects the Neutral output to the chassis if
no external AC supply is available. If an external AC supply is provided, the ground relay H will open before the
input safety relay closes. This ensures the correct operation of an earth leakage circuit breaker that is connected
to the output. An uninterrupted grounding can also be secured by means of the grounding wire of the AC input.
Otherwise the casing must be grounded.
The mains -input & output terminal connector can be found on the bottom of the MultiPlus. The mains cable
must be connected to the connector with a three-wire cable via the terminal blocks found on the printed circuit
board. Use a three-wire cable with a flexible core and a cross section of 2.5mm².
PROCEDURE
Proceed as follows to connect the AC cables:
The AC input cable (from mains) can be connected to the terminal block "AC–in". From left to right: "PE"
(earth), "N" (neutral) and "L" (phase). The AC input must be protected by a fuse or magnetic circuit breaker
rated at 16A or less, and cable cross-section must be sized accordingly. If the input AC supply is rated at a
lower value, the fuse or magnetic circuit breaker should be down sized accordingly
The AC output cable (to control panel or pump 1) can be connected directly to the terminal block "AC-
out-1". From left to right: "PE" (earth), "N" (neutral) and "L" (phase). With its PowerAssist feature the Multi
can add up to 3kVA (that is 3000 / 230 = 13A) to the output during periods of peak power requirement.
Together with a maximum input current of 16A this means that the output can supply up to 16 + 13 = 29A.
An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be
included in series with the output, and cable cross-section must be sized accordingly. The maximum rating
of the fuse or circuit breaker is 32A. Do not use AC output 2

QUICK INSTALL GUIDE

The steps in bold are indicated on the figure on page 8:
1. Screw the top bracket to a suitably strong substrate using the screws provided. Rawl plugs will be required
for the screws for certain wall types (not supplied)
2. Place unit onto the bracket using the lugs to the rear of the unit. Screw the bottom of the unit to the wall
3. Unscrew and remove the front panel. Note: All cables will pass up though the bottom of the unit prior to
connections being made
4. Wire AC IN with correctly rated mains cable. Add 3-pin mains plug or wire to a switched fused spare,
both of which should be fitted with a 13amp fuse. Do not plug in or turn on at the spur at this stage
5. Wire AC OUT with correctly rated mains cable from either a Newton automatic pump, or from the 'pump
2' connection of the CP2 or CP9 control panel
6. Wire the temperature sensor cable into the T-SENSE terminal
7. Connect the black battery cable to the left Negative terminal
8. Connect the red battery cable to the right Positive terminal
9. Connect the black battery cable and the temperature sensor cable to the negative terminal on the battery
10. Connect the red battery cable to the positive terminal on the battery
11. The system will start running off the batteries
12. Plug the AC IN into mains power or switch on the fused spur
Call us for more information on +44 (0)1732 360095