Page 1
KTIM INSTALLATION MANUAL Four-way Cassette Type Thank you very much for purchasing our air conditioner, Before using your air conditioner , please read this manual carefully and keep it for future reference.
Page 2
Table of Contents Installation Manual Accessories ............ Safety Precautions ........Installation Overview ....... Indoor Unit Installation Indoor Unit Installation ............a. Indoor Unit Parts ......... b. Indoor Unit Installation Instructions ..08 Outdoor Unit Installation ......a. Outdoor Unit Installation Instructions ..
Refrigerant Piping Connection ....... A. Notes on Pipe Length and Elevation ....16 B. Refrigerant Piping Connection Instructions ...17 Wiring ..........a. Outdoor Unit Wiring ....b. Indoor Unit Wiring ...... c. Power Specifications ....d. Wiring Diagram ......Air Evacuation ..........
Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. Name Shape Quantity...
Safety Precautions Read Safety Precautions Before Installation Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION. Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations.
Installation Overview INSTALLATION ORDER Install the indoor unit Install the outdoor unit Install the drainpipe (Page 7) (Page 11) (Page 14) Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes (Page 23) (Page 19) (Page 16) Install the front panel Perform a test run (Page 25) (Page 27)
Indoor Unit Installation Indoor Unit Parts Drain pump (within indoor unit) Drain pipe Air outlet Air inlet Front grille Louver Display panel Refrigerant pipe Fig. 4.1 Safety Precautions CAUTION WARNING • Securely install the indoor unit on a • Install the indoor and outdoor units, cables structure that can sustain its weight.
Indoor Unit Installation Instructions CAUTION NOTE: Panel installation should be done after DO NOT install the unit in the following piping and wiring. locations: In areas with oil drilling or fracking Step 1: Select installation location In coastal areas with high salt content in the air The indoor unit should be installed in a location that meets the following requirements: In areas with caustic gases in the air, such...
Page 9
Table 4.1: Distance from ceiling relative to height of indoor unit MODEL Length of A (mm/inch) Length of H (mm/inch) 205/8 > 235/9.3 205/8 > 235/9.3 205/8 > 235/9.3 30-48 245/9.6 > 275/10.8 48-60 287/11.3 > 317/12.5 Step 2: Hang indoor unit. 1.
Page 10
5. Mount the indoor unit. You will need two NOTE: Ensure that the indoor unit is level. The people to lift and secure it. Insert suspension unit is equipped with a built-in drain pump and bolts into the unit’ s hanging holes. Fasten float switch.
Outdoor Unit Installation The area must be free of combustible gases Outdoor Unit Installation Instructions and chemicals. The pipe length between the outdoor and Step 1: Select installation location. indoor unit may not exceed the maximum The outdoor unit should be installed in the allowable pipe length.
Page 12
Split Type Outdoor Unit Vertical Discharge Type Outdoor Unit (Refer to Fig 5.4, 5.5, 5.6, 5.10 and Table 5.1) (Refer to Fig 5.7, 5.8, 5.9 and Table 5.2) (Wall or obstacle) Air Outlet >120cm / 47” Fig. 5.4 Fig. 5.7 Fig.
Page 13
NOTE: The minimum distance between the Notes On Drilling Hole In Wall outdoor unit and walls described in the You must drill a hole in the wall for the installation guide does not apply to airtight refrigerant piping, and the signal cable that will rooms.
Drainpipe Installation The drainpipe is used to drain water from the NOTE ON DRAINPIPE INSTALLATION unit. Improper installation may cause unit and When using an extended drainpipe, tighten • property damage. the indoor connection with an additional protection tube to prevent it from pulling CAUTION loose.
Page 15
3. Using a 65-mm (2.5”) core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 12mm (0.5”). This will ensure proper water drainage (See Fig.
Refrigerant Piping Connection Safety Precautions Notes On Pipe Length and Elevation Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between WARNING the indoor and outdoor units meets the • All field piping must be completed by a requirements shown in Table 7.1: licensed technician and must comply with the local and national regulations.
Step 2: Remove burrs. Table 7.2 Burrs can affect the air-tight seal of refrigerant Permitted length piping connection. They must be completely Total piping length 18K+18K 30/98’ L+Max (L1, L2) removed. 24K+24K 50/164’ 1. Hold the pipe at a downward angle to 30K+30K prevent burrs from falling into the pipe.
Page 18
6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 7.5. Table 7.5: PIPING EXTENSION BEYOND FLARE Fig.
Wiring Follow these instructions to prevent distortion Safety Precautions when the compressor starts: • The unit must be connected to the main WARNING outlet. Normally, the power supply must • Be sure to disconnect the power supply have a low output impedance of 32 ohms. before working on the unit.
b. Using wire strippers, strip the rubber jacket 2. Open the front panel of the indoor unit. Using from both ends of signal cable to reveal a screwdriver, remove the cover of the electric about 15cm (5.9”) of the wires inside. control box on your indoor unit.
Power Specifications NOTE: Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A. Indoor Power Supply Specifications ≤18K (Btu/h) MODEL 19K~24K 25K~36K 37K~48K 49K~60K PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase POWER FREQUENCY 208-240V 208-240V 208-240V...
Air Evacuation 4. Turn on the vacuum pump to evacuate the Safety Precautions system. 5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG CAUTION (-1x105Pa). 6. Close the Low Pressure side of the manifold •...
Note On Adding Refrigerant CAUTION • Refrigerant charging must be performed after wiring, vacuuming and the leak test. DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. • Doing so can damage or impact the unit’ s function. •...
Panel Installation Step 3: Install the panel CAUTION Align the front panel to the main body, taking into account the position of the piping and DO NOT place the panel facedown on the floor, drain sides. Hang the four latches of the against a wall, or on uneven surfaces.
Page 26
2. Remove foam stops from inside the fan. 5. Close the front grille. 3. Attach the side of the front grille to the 6. Fasten the installation covers at all four panel. corners by pushing them inwards. (See Fig.10.6) 4. Connect the display panel cable to the corresponding wire on the main body.
Test Run f. Check to see that the drainage system is Before Test Run unimpeded and draining smoothly. A test run must be performed after the entire g. Ensure there is no vibration or abnormal system has been completely installed. Confirm noise during operation.
Page 28
The Klimaire logo is a registered Trademark of Klimaire Products Inc. Copyright 2016 Klimaire Products Inc. 2190 NW 89 Place, Doral, FL 33172 - USA Tel: (305)594-4972 Fax (305) 675-2212 www.klimaire.com sales@klimaire.com The design and specifications are subject to change without prior notice for product...
Need help?
Do you have a question about the KTIM series and is the answer not in the manual?
Questions and answers