5 Installation Instructions ProfiHub B5

5.1 Location

The ProfiHub B5 can be installed everywhere in a non-hazardous area that complies with IP 20 (DIN
o
40 050) and the specified temperature range of -20 to +60
Celsius.

5.2 Position

The ProfiHub B5 can be installed in every position, but it is recommended to install it with the cables
pointing down. In this position it is also easier to read the status display.

5.3 Mounting

The ProfiHub B5 has to be mounted on 35 mm DIN-rail with a minimum width of 167 mm.

5.4 Power Supply

The 3-pin screw type power connector is located on the bottom left of the ProfiHub B5 (
).
Fig. 15
1 = + (left)
2 = - (middle)
3 = Indirect grounding (right)
Fig. 15 - Power connector and LEDs
The power supply has to comply with the following specifications:
- Voltage: 10 to 32 Vdc
- Current: Min. 130 mA
2
- Wire diameter: < 2,5 mm
_______________________________________________
Version 2.1.1 – June 2014
Page 32 / 59
ProfiHub-A5B5-Manual-EN