Quick setup
Quick configurations
Setup Wizard
18
This setting will reserve inputs and outputs for the following compressors and fans:
The various connections are shown on the next page.
App. no. Display
17
3CDA + 2CB + FS
16
2CDA + 2CB + 3F
15
3CSA + 2CB + FS
14
2CSA + 2CB + 3F
13
4CA + 3CB + FS
12
3CA + 2CB + FS
11
2CA + 2CB + 3F
10
4CDA + FS
9
3CDA + FS
8
3CDA + 3F
7
2CDA + 2F
6
4CSA + FS
5
4CA + FS
4
4CA + 4F
3
3CSA + FS
2
3CA + FS
1
3CA + 3 F
0
None
After making a selection you must:
1. Set the type of refrigerant
2. Check the types of pressure transmitters
3. Check the min. and max. settings on the pressure transmitters
Factory setting:
Po A/B = AKS 32R, min=-1.0 bar, max.=12 bar
Pc = AKS 32R, min. = -1.0 bar, max. = 34 bar
SdA = NTC 86K
This wizard will lead you through the necessary settings, i.e. a total of approximately
20 to 35 display screens, depending on what is selected along the way.
The selection will also result in a connection to a given input and output. You yourself
will see this connection in the IO configuration menu. If applicable, see page 20.
User Guide RS8GY302 © Danfoss 2015-06
Suction group A
Speed
Digital
1-step
(Scroll / steam)
1
2
1
1
1
2
1
1
4
3
2
1
3
1
2
1
2
1
1
1
3
4
4
1
2
3
3
After making a selection, the setting will return to "None"
Suction group
Condenser
B
1-step
Step
Speed
2
x
2
3
2
x
2
3
3
x
2
x
2
3
x
x
3
2
x
x
4
x
x
3