Piping Preparation - LG Multi V ARUN053GF2 Installation Manual

Variable refrigerant flow outdoor unit 4.4 tons
Hide thumbs Also See for Multi V ARUN053GF2:
Table of Contents

Advertisement

Piping Preparation

• Do not allow the refrigerant to leak during brazing; if the refrigerant combusts, it generates a toxic gas.
• Do not braze in an enclosed location, and always test for gas leaks before / after brazing.
Multi V Space II Pipe Connections
1. Do not use kinked pipe caused by excessive bending in one specific area on its length.
2. Braze the pipes to the service valve pipe stub of the outdoor unit.
3. After brazing, check for refrigerant gas leaks.
4. When selecting flare fittings, always use a 45° fitting rated for use with high pressure refrigerant R410A. Selected fittings must also
comply with local, state, or federal standards.
Creating a Flare Fitting
One of the main causes of refrigerant leaks is defective flared
connections. Create flared connections using the procedure below.
1. Cut the pipe to length.
• Measure the distance between the indoor unit and the outdoor unit.
• Cut the pipes a little longer than measured distance.
2A. Remove the burrs.
• Completely remove all burrs from pipe ends.
• When removing burrs, point the end of the copper pipe down to
avoid introducing foreign materials in the pipe.
2B. Slide the flare nut onto the copper tube.
3. Flaring the pipe end.
• Use the proper size flaring tool to finish flared connections as
shown.
• ALWAYS create a 45° flare when working with R410A.
4. Carefully inspect the flared pipe end.
• Compare the geometry with the figure to the right and dimensions
as detailed in Figure 8.
• If the flare is defective, cut it off and re-do procedure.
• If flare looks good, blow clean the pipe with dry nitrogen.
Figure 8: Dimensions of the Flare.
90°
2
A
R=0.4~0.8
General InstallatIon GuIDelInes
Table 5: Flared Connection Dimensions.
Indoor /unit
(Btu/h)
Vapor (in. O.D.)
1
≤19,100
<54,600
≤76,400
ARNU093-123-153TN*2, ARNU183-243TM*2, ARNU153-183-243BG*2 piping connections: 5/8 in. O.D.
1
Vapor Piping, 3/8 in. O.D. Liquid Piping; Flare Size "A": 5/8 ~ 11/16 in. Vapor, 5/8 ~ 11/16 in. Liquid.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Copper
1.
tube
90°
Pipe
2A
Reamer
Point
down
3.
Bar
Copper pipe
Clamp handle
n ide i hin with no rat he
4.
Smooth
ven length
Pipe
Liquid (in. O.D.)
1/2
1/4
5/8
3/8
3/4
3/8
Piping Preparation
Slanted Uneven Rough
2B.
Flare nut
Copper
tube
andle
Bar
o e
Cone
Red arrow
n orre t Flare
Slanted
amanged
Cra ed
Uneven
ur a e
thi ne
"A"
Vapor (in.)
Liquid (in.)
5/8 ~ 11/16
7/16 ~ 1/2
5/8 ~ 11/16
5/8 ~ 11/16
3/4 ~ 13/16
5/8 ~ 11/16
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents