Refrigerant Piping Work
5.

Charging with refrigerant

• If the total length of piping for all rooms exceeds 20m, additionally charge with (R32) 20g of refrigerant for each additional
meter of piping.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Do not vent gases into the atmosphere.
R32
Refrigerant type:
(1)
675
GWP
value:
(1)
GWP = global warming potential
Please fill in with indelible ink,
the factory refrigerant charge of the product,
1
the additional refrigerant amount charged in the field and
2
the total refrigerant charge
1 + 2
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve
cover).
R32
6
5
NOTE:
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate
official national language on the unit. Therefore an additional multilingual fluorinated greenhouse gases label is supplied
with the unit.
Sticking instructions are illustrated on the backside of that label.
CAUTION
• Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long
period of time.
• Do not overfill with refrigerant. This will break the compressor.
9
1 factory refrigerant charge of the product: see unit name plate
4
2 additional refrigerant amount charged in the field
1
3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the Kyoto Protocol
2