Siemens SIPROTEC 7SS52 Operation Manual page 196

Table of Contents

Advertisement

6300 SETTINGS:
Supervision ?
6301 ISO TRA TIM =7.00
6302 ISO MAL RES =alarm only
6303 DIFF SUPERV =active
6304 T–DIFF SUPV =2
6305 I>SUPERV:BZ =.10
6306 I>SUPERV:CZ =.10
6307 DIFF SUP BZ =alarm only
6308 DIFF SUP CZ =alarm only
6309 ZERO CR SUP =active
6310 I> ZERO
CR =.50
6311 AUTO
TEST =active
6312 TEST
FAULT =alarm only
6313 I< MAN TRIP =.05
6314 MON T BF CI =1.00
6315 FLT T BF CI =.06
6316 FLTREC RELE =automatic
6317 RELE BOS BU =released
_______________
For supervision of run time, breaker fault and auxiliary voltage
Ino – Normalized nominal current related to base current transformer (current transformer with
highest transformation ratio)
IN – Nominal current of bay current transformer
Two fault record buffers, each 300 ms(200 ms before and 100 ms after the fault) are available.
Release auto: The fault record is automatically switched over to the other memory after each
end of a fault. A previous fault record, still existing there, is overwritten.
Release manual: After storing two fault records, the fault recording function remains blocked
until released via operation in DA 8300. If released, then both buffers are erased, independent
of their contents.
s
(min.
1.00 – max.
1)
(alarm only, blockAutoReleas,
block storage)
(inactive, active)
s
(min.
1
2)
I/Ino
(min.
0.05 – max.
2)
I/Ino
(min.
0.05 – max.
(alarm only, blockAutoReleas,
block storage)
(alarm only, blockAutoReleas,
block storage)
(inactive, active)
2)
I/Ino
(min.
0.20 – max.
(inactive, active)
(alarm only, block protect.)
3)
I/IN
(min.
0.00 – max.
s
(min.
0.02 – max.
s
(min.
0.06 – max.
(automatic, manual)
(blocked,released)
180.00)
– max.
10
)
0.80)
0.80)
4.00)
0.50)
10.00)
1.00)
4)