TP9600-TP9630 PNEUMATIC THERMOSTATS
Calibration
CAUTION
The thermostat is very sensitive and should
not be heated by excessive handling during
calibration.
NOTE: Reference in the following procedures to a 30 psi
gage implies the gage and gage adapter listed in
INSTALLATION TOOLS section.
TP9600
1. Remove the thermostat cover and install a 30 psi
gage into the gage tap.
2. Set the temperature setpoint indicator at the
indicated temperature.
3. Turn the calibration screw (see Fig. 4) until the gage
reads 0 psi.
4. Turn the calibration screw in the opposite direction
until the gage reads 8 psi (56 kPa) plus or minus
1 psi (7 kPa). The thermostat is now calibrated.
5. Remove the gage and replace cover.
TP9610
1. Remove the thermostat cover and install a 30 psi
gage into the gage tap.
2. Set the temperature setpoint indicator at the
indicated temperature.
3. With 13 psi (91 kPa) (DAY) main air pressure, turn
the DAY (left) calibration screw (see Fig. 4) until the
gage reads 0 psi.
4. Turn the calibration screw in the opposite direction
until the gage reads 8 psi (56 kPa) plus or minus
1 psi (7 kPa).
5. With 18 psi (126 kPa) (NITE) main air pressure,
rotate the night setpoint dial until its setting agrees
with the indicated temperature.
6. Repeat Steps 2, 3, and 4 using the NITE setpoint
and (right) calibration screw. The thermostat is now
in calibration.
7. Remove the gage and replace cover.
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, MN 55408-0524
95-7550 10-96 Printed in U.S.A
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 2C9
TP9620
1. Remove the thermostat cover and install a 30 psi
gage into the gage tap.
2. Set the temperature setpoint indicator to the
indicated temperature.
3. With 13 psi (91 kPa) (SUMMER) main air pressure,
turn the SUMMER (left) calibration screw
(see Fig. 4) until the gage reads 0 psi.
4. Turn the calibration screw in the opposite direction
until the gage reads 8 psi (56 kPa) plus or minus
1 psi (7 kPa).
5. With 18 psi (126 kPa) (WINTER) main air pressure,
repeat Steps 3 and 4, using the WINTER (right)
calibration screw. The thermostat is now in calibration.
6. Remove the gage and replace the cover.
TP9630
Same as TP9600.
By using this Honeywell literature, you agree
that Honeywell will have no liability for any
damages arising out of your use or modification
to, the literature. You will defend and indemnify
Honeywell, its affiliates and subsidiaries, from
and against any liability, cost, or damages,
including attorneys' fees, arising out of, or
resulting from, any modification to the literature
by you.
Helping You Control Your World
®

Advertisement

loading

This manual is also suitable for:

Tp9630