Install Duct Connection; Configuring Units For Downflow Discharge; Supply And Return Duct Opening - Carrier 48VG-A Installation Instructions Manual

Table of Contents

Advertisement

FIRE
OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage,
-Connect gas pipe to unit using a backup wrench to avoid
damaging gas controls,
-Never
purge
a gas line into a combustion
chamber.
Never
test for gas leaks with
an open
flame.
Use a commercially
available
soap solution
made specifically
for the detection
of
leaks to check
all connections.
A fire or explosion
may result
causing
property
damage,
personal
iniury or loss of life.
-Use
proper
length
of pipe
to avoid
stress
on gas control
manifold.
-If a flexible
connector
is required
or allowed
by authority
having
jurisdiction,
black
iron
pipe
shall
be
installed
at
furnace
gas valve
and extend
a minimum
of 2 in. (51 mm)
outside furnace
casing.
-If
codes
allow
a flexible
connector,
always
use
a new
connector.
Do
not use
a connector
which
has
previously
serviced
another
gas appliance.
8. Check
for
gas
leaks
at
the
field-installed
and
factory-installed
gas lines after all piping
connections
have
been completed.
Use a commercially
availaMe
soap solution
(or method
specified
by local codes and/or regulations).
Step 9 -- Install
Duct Connections
The unit has duct flanges
on the supply-
and return-air
openings
on the side and bottom
of the unit. For downshot
applications,
the
ductwork
connects
to
the
roof
curb
(See
Fig.
3
and
4 for
connection
sizes and locations).
Configuring
Units for Downflow (Vertical) Discharge
NOTE:
These
panels
are held in place with
tabs similar
to an
electrical
knockout.
Reinstall
horizontal
duct
covers
(see Fig. 9)
shipped
on
unit
from
factory.
Insure
openings
are
air
and
watertight.
NOTE:
The design
and installation
of the duct system
must be in
accordance
with
the standards
of the
NFPA
for installation
of
nonresidence-type
air conditioning
and ventilating
systems,
NFPA
90A
or
residence-type,
NFPA
90B;
and/or
local
codes
and
ordinances.
Basepan
Downflow
(Vertical)
Supply
_
Knockout
Horizontal
Duct Covers
A09076
Basepan
Downflow
Return
Knockout
ELECTRICAL
SHOCK
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
Before
installing
or servicing
system,
always
turn off main
power
to system
and install
lockout
tag.
There
may be
more than one disconnect
switch.
1. Open
all electrical
disconnects
before
starting
any service
work.
2. Remove
horizontal
(metal)
duct
covers
to access
vertical
(downflow)
discharge
duct knockouts
in unit basepan.
(See
Fig. 9.)
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage,
Collect ALL screws that were removed. Do not leave screws
on rooftop as permanent damage to the roof may occur.
To remove
downflow
return
and supply
knockout
covers,
break
front
and
right
side
connecting
tabs
with
a screwdriver
and
hammer.
Push cover down to break rear and left side tabs.
A09077
Fig. 9 - Supply
and Return
Duct Opening
Adhere
to
the
following
criteria
when
selecting,
sizing,
and
installing
the duct system:
1. Units
are
shipped
for
horizontal
duct
installation
(by
removing
duct covers).
2. Select
and
size
ductwork,
supply-air
registers,
and
return-air
grilles according
to American
Society
of Heating,
Refrigeration
and Air Conditioning
Engineers
(ASHRAE)
recommendations.
3. Use flexible
transition
between
rigid ductwork
and unit to
prevent
transmission
of vibration.
The transition
may be
screwed
or bolted
to duct flanges.
Use suitaMe
gaskets
to
ensure weather-tight
and airtight seal.
4. All units must have field-supplied
filters or accessory
filter
rack
installed
in
the
return-air
side
of
the
unit.
Recommended
sizes for filters are shown
in Table 1.
5. Size
all ductwork
for maximum
required
airflow
(either
heating
or cooling)
for unit being
installed.
Avoid
abrupt
duct
size increases
or decreases
or performance
may be
affected.
6. Adequately
insulate
and weatherproof
all ductwork
located
outdoors.
Insulate
ducts
passing
through
unconditioned
space, and use vapor
barrier in accordance
with latest issue
of Sheet
Metal and Air Conditioning
Contractors
National
Association
(SMACNA)
and Air Conditioning
Contractors
of America
(ACCA)
minimum
installation
standards
for
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents