Indicators; Memory Map - AB Quality 1794-IB16 Installation Instructions Manual

24v dc flex i/o digital input modules
Table of Contents

Advertisement

8
24V dc FLEX I/O 16 Sink Input Module

Indicators

Allen Bradley
24 VDC SINK INPUT
0
1
2
3
4
5
6
7
8
9
A
A = Status indicators – yellow – show status of individual inputs.
B = Insertable label for writing individual input designations.

Memory Map

Dec.
15
14
13
12
11
10
09
08
Octal
17
16
15
14
13
12
11
10
Read 0
D
D
D
D
D
D
D
D
15
14
13
12
11
10
9
8
Read 1
C = 16 bit Counter Value of Input 15
Not
CF CR
Not used
Write
used
Where: D = Data Input - 0 = input off, 1 = input on
C = Counter value for input 15
FT = Input Filter Time
CR = Counter Reset
CF = Counter Fast - where 1 = Fast Input (raw) data, 0 = Standard Input filtered data
NOTE: C, CR and CF not available when used with any series 1794 ASB or 1794 ASB2 Remote I/O
Adapter Modules
Publication 1794 IN072C-EN-P - October 2001
1794-IB16
2
10
11
12
13
14
15
B
07
06
05
04
03
02
01
00
07
06
05
04
03
02
01
00
D
D
D
D
D
D
D
D
7
6
5
4
3
2
1
0
FT 12-15
FT 00-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents