ABB Relion 670 series REC670 Product Manual page 80

Bay control
Table of Contents

Advertisement

Bay control REC670
Pre-configured
Product version: 1.2
Test switch
The test system COMBITEST intended for use with the IED
670 products is described in 1MRK 512 001-BEN and 1MRK
001024-CA. Please refer to the website:
www.abb.com/substationautomation
Due to the high flexibility of our product and the wide variety
of applications possible the test switches needs to be
selected for each specific application.
Select your suitable test switch base on the available
contacts arrangements shown in the reference
documentation.
However our proposals for suitable variants are;
Single breaker/Single or Three Phase trip with internal neutral
on current circuits (ordering number RK926 315-AK).
Single breaker/Single or Three Phase trip with external neutral
on current circuits (ordering number RK926 315-AC).
Protection cover
Protective cover for rear side of RHGS6, 6U, 1/4 x 19"
Protective cover for rear side of terminal, 6U, 1/2 x 19"
Protective cover for rear side of terminal, 6U, 3/4 x 19"
Protective cover for rear side of terminal, 6U, 1/1 x 19"
External resistor unit
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for
20-100V operating voltage
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for
20-100V operating voltage
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for
100-400V operating voltage
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for
100-400V operating voltage
Combiflex
Key switch for settings
Key switch for lock-out of settings via LCD-HMI
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
Side-by-side mounting kit
80
for detailed information.
Multi-breaker/Single or Three Phase trip with internal neutral
on current circuits (ordering number RK926 315-BE).
Multi-breaker/Single or Three Phase trip with external neutral
on current circuit (ordering number RK926 315-BV).
The normally open "In test mode" contact 29-30 on the RTXP
test switches should be connected to the input of the test
function block to allow activation of functions individually
during testing.
Test switches type RTXP 24 is ordered separately. Please
refer to Section
"Related documents"
corresponding documents.
RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and
the on/off switch for dc-supply are ordered separately. Please
refer to Section
"Related documents"
corresponding documents.
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
Quantity:
1MRK511232-BEN E
for reference to
for reference to
1MRK 002 420-AE
1MRK 002 420-AC
1MRK 002 420-AB
1MRK 002 420-AA
1
2
3
RK795101-MA
RK795101-MB
1
2
3
RK795101-CB
RK795101-DC
1MRK 000 611-A
1MRK 002 420-Z
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Red670 relion 670 series

Table of Contents