Bay control REC670
Pre-configured
Product version: 1.2
Table 99. IEC Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
k
(
)
ç
÷
P
-
è
ø
I
1
EQUATION1251-SMALL V1 EN
I = I
/I
measured
set
Time delay to reset, IEC inverse time
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
k
(
)
ç
÷
P
-
è
ø
I
C
EQUATION1370-SMALL V1 EN
Reset characteristic:
TR
=
×
t
k
(
)
PR
-
I
CR
EQUATION1253-SMALL V1 EN
I = I
/I
measured
set
Table 100. RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1
=
×
t
k
0.236
-
0.339
I
EQUATION1137-SMALL V1 EN
I = I
/I
measured
set
RD type logarithmic inverse characteristic
æ
ö
I
-
ç
×
÷
=
5.8
1.35
In
t
è
ø
k
EQUATION1138-SMALL V1 EN
I = I
/I
measured
set
ABB
Range or value
k = (0.05-999) in steps of 0.01
(0.000-60.000) s
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
k = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
Range or value
k = (0.05-999) in steps of 0.01
k = (0.05-999) in steps of 0.01
1MRK511232-BEN E
Accuracy
-
± 0.5% of set time ± 10 ms
IEC 60255-151, 5% + 40
ms
Accuracy
IEC 60255-151, 5% + 40
ms
71